Immergas System Manager Kit Instructions And Warnings

Electronic control
Hide thumbs Also See for System Manager Kit:
Table of Contents

Advertisement

Quick Links

System Manager
IE
Instructions and
Kit
warnings
Installer
User
Electronic control
Maintenance technician

Advertisement

Table of Contents
loading

Summary of Contents for Immergas System Manager Kit

  • Page 1 System Manager Instructions and warnings Installer User Electronic control Maintenance technician...
  • Page 3 Congratulations for having chosen a top-quality Immergas product, able to assure well-being and safety for a long period of time. As an Immergas customer you can also count on Qualified Post-Sales Service, prepared and updated to guarantee constant efficiency of your "System Manager Kit".
  • Page 4: Table Of Contents

    5.10 Telephone dialler..........26 Display - firmware revision ........8 5.11 Reset counter............26 5.12 Manual management........... 26 “System manager kit” user settings ....9 5.13 Initialization............27 Start-up..............9 5.14 Cascade parameters..........27 2.1.1 Main page ............... 9 2.1.2 Programming current time and day ....
  • Page 5 INDEX PAGE System operator - connection to victrix 9.34 System manager - connection to dominus..84 superior 2022............67 9.35 System manager - connection to domotics 9.10 System manager - connection to boiler via with digital signals..........85 modbus rs-485 electronic board.
  • Page 6: Foreword

    • The instruction manual must be considered a part of the “System Manager Kit” and must be “kept for future reference”. • The “System Manager Kit” is intended only for the use for which it has been expressly designed. Any other use must be considered improper and therefore dangerous.
  • Page 7: Description Control Panel

    DESCRIPTION CONTROL PANEL Key: BUTTONS DESCRIPTION. 1. Button to change the operating mode summer/ The button (Ref. 1 Fig. 1-1) allows you to change the winter/stand-by ( operating mode of the system, specifically: • Summer (only DHW management). 2. Access button to submenus ( •...
  • Page 8: Description Of The Display Screen

    Summer - only the dhw heating function is - “Info” menu, to view the “System Manager Kit” input enabled; data (ex. external temperature, flow temperature, set flow temperature, DHW temperature, solar storage Comfort temperature is active;...
  • Page 9: System Manager Kit" User Settings

    “SYSTEM MANAGER KIT” USER 2.1.2 Programming current time and day SETTINGS Press the button to enter the navigation menu. Press buttons until selecting menu “02. PRO- It is possible to set / modify the following parameters: GRAMMING”. - DHW temperature;...
  • Page 10: Selection Of Operating Mode

    In this status the current day and time are still displayed, along The “System Manager Kit” is factory set as shown in with any operating faults, present humidity percentage the table below. If this should not satisfy requirements, and ambient temperature in the main area.
  • Page 11: Operation In Winter Mode

    (see Parag. 2.5). (DHW band enab.) blink. The “System Manager Kit” is factory set as shown in Set as desired by pressing arrows . At the end, the table below. If this should not satisfy requirements,...
  • Page 12: Domestic Hot Water Temperature Setting On Boiler Side

    • COMFORT SET: it lets you set the DHW set-point in SETTING COMFORT AND REDUCED ROOM TEMPERATURE. the COMFORT time range (refer to settings of DHW time slots) (M03); It is possible to set two different room temperature levels: - setpoint COMFORT; •...
  • Page 13: Programming Operating Time In Comfort Mode

    PROGRAMMING OPERATING TIME IN 2.6.2 Weekly hourly program COMFORT MODE. Press the button to enter the navigation menu. In this menu it is possible to: Press buttons until selecting menu “02. PRO- - set 4 calendars for 4 different time slots; GRAMMING”.
  • Page 14: Holiday Program

    2.6.3 Holiday program SYSTEM MANAGEMENT In this menu it is possible to: With this menu it is possible to temporarily disable - activation of SEPARATE HEATING / COOLING system requests with the exception of: MANAGEMENT; - room antifreeze function; - activation of the FANCOIL IN WINTER function. - managing thermal solar system.
  • Page 15: Floor Drying Function

    2.7.1 Floor Drying function. During active operation, it is possible to check in the INFO pages (I47): A “Floor Drying” function can be enabled to perform - Active Setpoint. Temperature calculated during screed thermal shock on new radiant panel systems, as required heater operation.
  • Page 16 - Heat pump temporary enable command (D05). The option lets you enable heat pumps according to the time slots that will be set in the next page (D06). Press button for the option “Disable heat pumps” to start blinking. Press arrows to confirm (YES) or cancel (NO) any option.
  • Page 17: Information

    INFORMATION DHW MENU. - D.H.W. data (I51, I52 and I53) Info In the following pages it is possible to view the main system information, in particular parameters relating to: - zone management; Setpoint 40 °C DHW Temp 45.0 °C - domestic hot water; Request - heat pump management;...
  • Page 18: Diagnostics And Errors

    Press arrows to scroll and display all extant alarms. The anomalies displayed in the “System manager kit” are listed in the “Anomalies list” chapter. If no alarm has been triggered, it is still possible to view the “Alarms log” by proceeding as follows:...
  • Page 19: Service Menu

    Some of these - INTEGRATION: detailed information on integration submenus are protected by a code (which can be used generators. exclusively by the Immergas technician) while others are also visible to the user. - INPUT/OUTPUT: system inputs and outputs. Press the arrows and select “02.
  • Page 20: System Definition

    SYSTEM DEFINITION Furthermore, if the setpoint calculated for the dehumid- Within this menu it is possible to set the features of the ification is too high to carry out a request, the alarm is system that need to be managed. signalled and the dehumidifier is stopped.
  • Page 21: Heat Pumps (P31)

    5.4.2 Heat pumps (P31) - Separate management of central heating and cooling (P65). Allows to control a 3-way valve to choose wheth- The system allows you to choose the model of heat pump er to use the central heating system or the cooling one. used (max.
  • Page 22: Setpoint Correction (P81 ÷ P84)

    CENTRAL HEATING (P68) - Enable external temperature probe presence. - Hysteresis ON (P68). The generator turns on for a - Not present setpoint lower than setpoint required + Hysteresis ON. - From heat pump - From boiler - Hysteresis OFF (P68). The generator turns on for a - From the system manager setpoint lower than setpoint required + Hysteresis OFF.
  • Page 23: Temperature Regulation (T01 ÷ T20)

    TEMPERATURE REGULATION (T01 ÷ DOMESTIC HOT WATER. T20). This menu will be enabled only if "Yes" has been set under In this menu it will be possible to: “DHW” in the “System definition” menu. - activate operation with external probe; Press the arrows and select “Sanitario”...
  • Page 24: Solar System

    SOLAR SYSTEM. N.B.: As soon as the temperature of the manifold falls In this section it will be possible to set the values to below the set setpoint this function is disabled. The manage the solar pump. This menu will be enabled only storage tank's cooling system is also enabled when the if “1”...
  • Page 25: Integration

    INTEGRATION. - Integration limit (X04). If the flow temperature of the In this section it is possible to define auxiliary sources heat pumps is lower than the heating-set value minus to be used to integrate the central heating or integration the activation band divided by 2, then after a period mode of action.
  • Page 26: Supervisor

    SUPERVISOR. 5.10 TELEPHONE DIALLER. In this section it is possible to set the type of supervision Using digital supervision, illustrated in the previous of the system management kit. paragraph, it is possible to use a telephone dialler to There are two types of supervision: digital and with manage system operational modes.
  • Page 27: Initialization

    5.13 INITIALIZATION. - Activation Band to Start or Stop HP (C02). The In this section it is possible to restore the factory settings. cascade generators are activated/deactivated if the By performing this operation all of the operations previ- common delivery probe is outside the set-point range ously carried out will be deleted including time periods, ±...
  • Page 28: List Of Programmable Parameters

    LIST OF PROGRAMMABLE PARAMETERS. “Main” menu. Range Value Value Description page adjustment default customis. Stand-by, Summer, Working modes Summer with Cooling, Stand-by Winter DHW Time bands enab. No / Yes 10 - 50 (60 with boiler/ DHW Manual set (permanent) electrical res.) DHW Manual set (permanent) 30 - 60...
  • Page 29 "Set point" menu. Range Value Value Description page adjustment default customis. Party mode No / Yes Winter - Zone 1 Comfort Set 5 - 35 Winter ZN1 Economy Set 5 - 35 Winter - Zone 2 Comfort Set 5 - 35 Winter ZN2 Economy Set 5 - 35 Winter - Zone 3 Comfort Set...
  • Page 30 “Programming” menu. Range Value Value Description page adjustment default customis. Time 0 - 23 Minutes 0 - 59 Monday / Tuesday / Wednesday / Thursday Day of the week / Friday / Saturday / Sunday Day of year 1 - 31 Month of year 1 - 12 Year...
  • Page 31 Range Value Value Description page adjustment default customis. CAL1, CAL2, Zone 1: Tuesday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 1: Wednesday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 1: Thursday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 1: Friday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 1: Saturday CAL1 CAL3,CAL4 CAL1, CAL2,...
  • Page 32 Range Value Value Description page adjustment default customis. CAL1, CAL2, Zone 4: Friday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 4: Saturday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 4: Sunday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 5: Monday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 5: Tuesday CAL1 CAL3,CAL4 CAL1, CAL2,...
  • Page 33 Range Value Value Description page adjustment default customis. CAL1, CAL2, Zone 7: Sunday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 8: Monday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 8: Tuesday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 8: Wednesday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 8: Thursday CAL1 CAL3,CAL4 CAL1, CAL2,...
  • Page 34 Range Value Value Description page adjustment default customis. Holiday end day 1 - 31 Holiday end month 1 - 12 Holiday end year 0-99 Enable holiday Yes/No “System Management” menu. Range Value Value Description page adjustment default customis. Set cooling (separate heating / cooling 5-25 management) Enable use of fancoil in WINTER...
  • Page 35 Range Value Value Description page adjustment default customis. CAL1, CAL2, Heat Pump Power Reduction: Monday CAL1 CAL3,CAL4 CAL1, CAL2, CAL3, Heat Pump Power Reduction: Tuesday CAL1 CAL4 CAL1, CAL2, CAL3, Heat Pump Power Reduction: Wednesday CAL1 CAL4 CAL1, CAL2, CAL3, T Heat Pump Power Reduction: hursday CAL1 CAL4...
  • Page 36 “Service \ System definition” menu. Range Value Value Description page adjustment default customis. Plant type 1 - 8 Zones number No / Yes DHW Enable No / Yes Mode Hot, Cold, Hot/Cold NO, Rem. Control, Remote panel, Zone Comm. Remote panel Control, Temp-humid probe Thermostat...
  • Page 37 Range Value Value Description page adjustment default customis. Mode Hot, Cold, Hot/Cold Comm. No, temp-hum. probe Thermostat No / Yes Type Fixed / Mixed Mixed Zone probe No / Yes Humidostat No / Yes Dew Point No / Yes En. Dehum. No / Yes Mode Hot, Cold, Hot/Cold...
  • Page 38 Range Value Value Description page adjustment default customis. 5 = Room 5 6 = Room 6 Names Zone 5,6,7,8 7 = Room 7 8 = Room 8 Main zone 1 - 4 Dehum. Set Max 15 - 50 Alarm set 15 - 50 Request from fancoil zone OFF/ON...
  • Page 39 Range Value Value Description page adjustment default customis. Power 50-100 % 75 % Pump Logic Max sp / Modul Modul Minim. Speed 19-50 % 50 % Max. Speed 50-100 % 100 % Delta T 2-20 Circulator anti-block Yes/No Flow switch Reduction enable NO/YES Power...
  • Page 40 Range Value Value Description page adjustment default customis. Audax 6/ Audax 8 / Audax 12/ Audax 16 /Audax 16 Mono / Audax Top 6 /Audax Top 8/Audax Top 12 / Ind. 14 Audax Top 16 /Audax Top 18 / Audax Top 21 /Audax 6 kW/ Audax 8 –...
  • Page 41 Range Value Value Description page adjustment default customis. Maintain: NO/YES Pump NO/YES Upon Request / In In tempera- Zone Activation On Request temperature ture Central Heating - Hyst. ON -10 - +20 Central Heating - Hyst. OFF -10 - +20 Central Heating - Offset gen -10 - +30 Puffer Cooling - Hyst.
  • Page 42 Range Value Value Description page adjustment default customis. Zone 05 - Heating phase Set max 20 – 85* Room probe Yes/No Zone 01 - Heating phase External probe No/Yes Zone 06 - Heating phase Set min 20 – 85* Zone 06 - Heating phase Set max 20 –...
  • Page 43 Range Value Value Description page adjustment default customis. Zone 01 - Heating phase External probe No/Yes Set min 20 – 85* Set max 20 – 85* External t. limit - Heating phase Min ext. -20 - 0 External t. limit - Heating phase Max ext. 5 - 25 Set Deum.
  • Page 44 “Assistance \ Solar” menu. n° Range Value Value Description pagina adjustment default customis. Solar pump 1 Δt On 1 - 20 Solar pump 1 Δt Off 0,5 - 19,5 Solar pump 2 Δt On 1 - 20 Solar pump 2 Δt Off 0,5 - 19,5 Tank Max.
  • Page 45 “Assistance \ Supervisor” menu. Range Value Value Description page adjustment default customis. Digital Mangement Sys Enable No / Yes ---, Carel, Modem RS Protocol supervision system 1 Winload 232, Modbus, Winload 1200, 2400, 4800, Baudrate supervision system 1 19200 9600, 19200 Address supervision system 1 1 - 100 ---, Carel, Modem RS...
  • Page 46 Range Value Value Description page adjustment default customis. STOP/OPEN/ Expansion 2: Zone pump CLOSE Expansion 2: 3P Valve OFF/ON Expansion 2: Dehumidification OFF/ON Expansion 2: Deh. and Clim. OFF/ON STOP/OPEN/ Expansion 3: Zone pump CLOSE Expansion 3: 3P Valve OFF/ON Expansion 3: Dehumidification OFF/ON Expansion 3: Deh.
  • Page 47 Range Value Value Description page adjustment default customis. Audax 1: Mode -120 - 120 Audax 1: Set Freq. NO/YES Audax 1: High pressure switch test 0 - 100 Off, Cooling Test, Heating Test, Ramp Audax 2: Circ. Test Speed Cooling Test, Ramp Heating Test Audax 2: Mode -120 - 120...
  • Page 48: Notes For Devices For Zones

    NOTES FOR DEVICES Procedure to change parameters FOR ZONES In this mode, all symbols are shut off, except for the following fields: NOTES FOR ZONE CONTROL indicates the value of the parameter currently being changed; 88:88 indicates the name of the parameter currently being changed.
  • Page 49: Notes For Zone Remote Control

    NOTES FOR ZONE REMOTE Programming current time and day. Press and hold CONTROL the “time band ” button until the “ ” func- Clock Please refer to the relevant instructions sheet for instal- tion appears. lation instructions. The required addresses to use are: 31 = Zone 1 32 = Zone 2 33 = Zone 3...
  • Page 50 Time slots adjustment. The “Time band” parameter Ignition. Press and hold the “on / off ” button; the enables to adjust the room temperatures in time slots, remote control goes into stand-by and displays the it is possible to adjust up to a maximum of 6 time slots operating modes, the room temperature and the time.
  • Page 51 - Select the time slots, which are shown according to the Time slot activation. By pressing the button “ ” one sequence below: can activate system operation according to the settings made previously. The activation of the time slot mode is signalled by the activation of the relative symbol “...
  • Page 52 Room temperature manual adjustment. In the event the Anomalies display. In the event there is an anomaly in time slots are not used, one can set the room temperature progress, the remote control displays the status via the simply by turning the main selector. symbol “...
  • Page 53: Notes For The Zone Remote Panel

    12:34 Ma 8 Lug 2014 20.6 °C 13°C Zona 1 Set ambiente 21.0°C Modo Menu Zona Key: 1 - Main parameters switch with button to confirm and save data 2 - Left context button 3 - Right context button 4 - Display 7-12 NOTES FOR THE NOTES FOR DOMINUS (OPTIONAL).
  • Page 54: Generators Configuration

    GENERATORS 8.1.2 Magis pro V2 configuration CONFIGURATION Parameter T02 and the parameter families UXX, RXX, IXX are automatically set by the system operator. HEAT PUMPS CONFIGURATION. Required settings on the indoor unit panel: - A12 = OFF; 8.1.1 Communication analysis - A13 = 1;...
  • Page 55: Magis Combo V2 Configuration

    8.1.3 Magis Combo V2 configuration 8.1.4 Magis M configuration Parameter T02 and the parameter families UXX, RXX, For correct operation of the System Manager with IXX are automatically set by the system operator. Magis M, it is ALWAYS necessary to install the Magis Required settings on the indoor unit panel: M hybrid system coupling resistor (supplied as stand- - A12 = OFF;...
  • Page 56: Audax Configuration

    8.1.5 Audax configuration - Configure (P41). Select “Yes” to start parameterisation. - Orientation. In presence of several heat pumps com- This heat pump family includes the following models: municating with each other, setting the machines with - Audax 6 different addresses is required. - Audax 8 Machine Address...
  • Page 57: Work Range Of Heat Pumps

    8.1.6 Work range of heat pumps. - Test cooling - Test central heating The maximum and minimum temperatures of the heat pumps depend on the type of machine installed. - Test cooling with ramp The following tables highlight the operational limits. - Test central heating with ramp - Set Freq.: Magis M...
  • Page 58: Boiler Configuration

    The connection of boilers to the System Manager can be - Connection via dry contact (boiler ON/OFF). made in 4 different ways, which can be set on page X01 The following table shows in which mode Immergas depending on the model: boilers must be connected and which functions are - Connection via Immergas BMS (BMS boiler);...
  • Page 59: Connection Via Immergas Bms

    8.2.1 Connection via Immergas BMS. 8.2.4 Connection via analogue 0-10 V signal and DHW thermostat. Connection via Immergas BMS takes place on the ter- minals dedicated to BMS communication in supported This mode activates heating requests via the 0-10 V input products.
  • Page 60: Wiring Diagrams

    WIRING DIAGRAMS SYSTEM MANAGER - POWER SUPPLY CONNECTION. PWM 0/10V J8 ISOLATED input voltage: 24Vac (+10%-15%); 50/60Hz 48Vdc (36Vmin...71Vmax) max power:8VA/6W Key: A13 - System manager T1 - Class II transformer of at least 30 VA with 24 Vac output voltage (not supplied with the System manager) 1 - Power supply 230 Vac - 50 Hz 2 - Transformer 230 Vac - 24 Vac...
  • Page 61: System Manager - Connection To Magis Pro V2 And Magis Combo V2

    SYSTEM MANAGER - CONNECTION TO MAGIS PRO V2 AND MAGIS COMBO V2. 61 61...
  • Page 62: System Operator - Connection To Magis M

    SYSTEM OPERATOR - CONNECTION TO MAGIS M. J8 ISOLATED GNX + - Modbus connection AWG 20/22 type Collegamento Modbus shielded cable cavo schermato tipo AWG 20/22 Screen Schermo (H2) (H1) (Y) (E) For the correct connection betwe- en control panel and CN30 con- nector, please refer to the heat pump's operating and installation manual...
  • Page 63: System Mananger - Magis Pro V2 Battery Connection

    SYSTEM MANANGER - MAGIS PRO V2 BATTERY CONNECTION J8 ISOLATED J9 input voltage: max power:8VA/6W Key: A13 - System manager 1 - Internal Unit Magis Pro V2 n°1 2 - Set: A21 = 11 3 - Internal Unit Magis Pro V2 n°2 4 - Set: A21 = 12 5 - Internal Unit Magis Pro V2 n°3 6 - Set: A21 = 13...
  • Page 64: System Operator - Magis M Battery Connection

    SYSTEM OPERATOR - MAGIS M BATTERY CONNECTION 64 64...
  • Page 65: System Manager - Connection To Common Flow Probe

    SYSTEM MANAGER - CONNECTION TO COMMON FLOW PROBE. PWM 0/10V J8 ISOLATED input voltage: 24Vac (+10%-15%); 50/60Hz 48Vdc (36Vmin...71Vmax) max power:8VA/6W Key: A3 - System manager B1 - Common flow probe 1 - Input for generic boiler alarm 65 65...
  • Page 66: System Manager - Connection To Electric Central Heating Integration Resistance

    K25: - Support relay EMR 230/24 Vac 16A (not supplied) 1 - Power supply 230/24 Vac - 50 Hz 2 - Power supply 400+N/230Vac - 50 Hz Note: - The B2 probe is fitted as standard on the Immergas storage tanks. 66 66...
  • Page 67: System Operator - Connection To Victrix Superior 2022

    SYSTEM OPERATOR - CONNECTION TO VICTRIX SUPERIOR 2022. Modbus connection AWG 20/22 type collegamento MODBUS shielded cable cavo schermato tipo AWG 20/22 J8 ISOLATED J9 input voltage: max power:8VA/6W Key: A3: - Boiler P.C.B. A13 - System manager B2-1: - DHW probe S50: - DHW thermostat X40: - Room thermostat jumper X70: - Room thermostat bridge Low temperature...
  • Page 68: System Manager - Connection To Boiler Via Modbus Rs-485 Electronic Board

    9.10 SYSTEM MANAGER - CONNECTION TO BOILER VIA MODBUS RS-485 ELECTRONIC BOARD. 9-10 Key: A13 - System manager A18 - Modbus interface board A3 - Boiler P.C.B. (generic) RS485 GND A Modbus connection AWG 20/22 type Collegamento Modbus shielded cable cavo schermato tipo AWG 20/22 J8 ISOLATED J9 input voltage:...
  • Page 69: System Manager - Connection To Hercules Condensing Erp, Hercules Mini Condensing Erp And Ares Condensing 32 Erp Boilers Via External Probe Input

    9.11 SYSTEM MANAGER - CONNECTION TO HERCULES CONDENSING ERP, HERCULES MINI CONDENSING ERP AND ARES CONDENSING 32 ERP BOILERS VIA EXTERNAL PROBE INPUT. 9-11 PWM 0/10V J8 ISOLATED input voltage: 24Vac (+10%-15%); 50/60Hz 48Vdc (36Vmin...71Vmax) max power:8VA/6W Key: A13 - System manager A3 - Boiler P.C.B.
  • Page 70: System Manager - Connection To Victrix Pro Via 0-10 V Input And Sanitary Thermostat

    9.12 SYSTEM MANAGER - CONNECTION TO VICTRIX PRO VIA 0-10 V INPUT AND SANITARY THERMOSTAT. 9-12 J8 ISOLATED input voltage: max power:8VA/6W Key: A3 - Boiler P.C.B. A13 - Boiler manager X40 - Room thermostat jumper K31 - DHW thermostat relay (SSR 6 Vdc type) K35 - Support relay EMR 230 Vac 5A (not supplied).
  • Page 71: System Manager - Connection To Boiler Through Ta Input

    9.13 SYSTEM MANAGER - CONNECTION TO BOILER THROUGH TA INPUT. 9-13 J8 ISOLATED J9 input voltage: Key: max power:8VA/6W A13 - System manager A3 - Boiler P.C.B. (generic) K20 - Relay EMR 12 V DC Note: - The K20 relay contact must be connected to the boiler TA clamps 9.14 SYSTEM MANAGER - CONNECTION TO BOILER ALARM SIGNAL.
  • Page 72: System Manager - Expansions Power Supply Connection

    9.15 SYSTEM MANAGER - EXPANSIONS POWER SUPPLY CONNECTION. 9-15 72 72...
  • Page 73: System Manager - Expansion Communication Cable Connection

    9.16 SYSTEM MANAGER - EXPANSION COMMUNICATION CABLE CONNECTION. 9-16 J8 ISOLATED Key: A13 - System manager F2 - Special functions 2 I3 - Address 3 A15 - Expansion Z4 - Zone 4 I4 - Address 4 F - Function Z5 - Zone 5 I5 - Address 5 I - Expansion Addresses Z6 - Zone 6...
  • Page 74: System Manager - Ta Request Connection With 1 Fixed Zone

    3 - B (to system) input voltage: 24Vac (+10%-15%); 50/60Hz Note: - The B2 probe is fitted as standard on 48Vdc (36Vmin...71Vmax) the Immergas storage tanks max power:8VA/6W - Control (J10): Open -> switch to system Closed -> switch to storage tank...
  • Page 75: System Manager - Expansion Zone Pump Connection

    9.19 SYSTEM MANAGER - EXPANSION ZONE PUMP CONNECTION. F - Function I - Expansion Addresses Z1 - Zone 1 Z2 - Zone 2 Z3 - Zone 3 Z4 - Zone 4 Z5 - Zone 5 Z6 - Zone 6 Z7 - Zone 7 Z8 - Zone 8 I1 - Address 1 I2 - Address 2...
  • Page 76: System Manager - Expansion Zone Mixer Connection

    9.21 SYSTEM MANAGER - EXPANSION ZONE MIXER CONNECTION. 9-21 Key: F - Function A15 - Zone expansion kit I - Expansion Addresses M31 - Zone mixing valve Z1 - Zone 1 1 - Power supply 230 Vac - 50 Hz Z2 - Zone 2 2 - Open Z3 - Zone 3...
  • Page 77: System Manager - Connection To Zone Room Thermostats

    9.22 SYSTEM MANAGER - CONNECTION TO ZONE ROOM THERMOSTATS. 9-22 Key: A15: - zone expansion kit S20 - Zone room thermostat or potential-free contact to request 1 - Power supply 24Vac - 50Hz 2 - Remove any jumper ID1-G to connect TA F - Function I - Expansion Addresses Z1 - Zone 1...
  • Page 78: System Manager - Connection To Safety Thermostat

    9.23 SYSTEM MANAGER - CONNECTION TO SAFETY THERMOSTAT. 9-23 PWM 0/10V J8 ISOLATED input voltage: 24Vac (+10%-15%); 50/60Hz 48Vdc (36Vmin...71Vmax) max power:8VA/6W Key: A13 - System manager Note: - This connection is necessary in the presence of zone expansions with TA contacts / temperature-humidity probes/zone controls.
  • Page 79: System Manager - Connection To Zone Remote Panels

    9.25 SYSTEM MANAGER - CONNECTION TO ZONE REMOTE PANELS. 9-25 J8 ISOLATED J9 input voltage: A32 - 1,2,3,HT max power:8VA/6W Key: A13 - System manager A32-1,2,3,HT - Zone remote panel 9.26 SYSTEM MANAGER - CONNECTION TO TEMPERATURE AND HUMIDITY PROBE. Key: 9-26 A15: - zone expansion kit...
  • Page 80: System Manager - Connection To Zone Remote Controls

    9.27 SYSTEM MANAGER - CONNECTION TO ZONE REMOTE CONTROLS. 9-27 80 80...
  • Page 81: System Manager - Connection To Dehumidifier Kit

    9.28 SYSTEM MANAGER - CONNECTION TO DEHUMIDIFIER KIT. 9-28 81 81...
  • Page 82: System Manager - High-Temperature Zone Valves Connection

    9.29 SYSTEM MANAGER - HIGH-TEMPERATURE ZONE VALVES CONNECTION. 9-29 Key: A15 - Address 4 zone expansion kit Y5 - High temperature two-way valve Y6 - Low temperature two-way valve 1 - Power supply 230 Vac - 50 Hz 2 - Expansion Addresses 3 - Address 4 Note: - Configure the expansion address as indicated...
  • Page 83: System Manager - Thermal Discharge Connection

    9.31 SYSTEM MANAGER - THERMAL DISCHARGE CONNECTION 9-31 Key: A15-5 - Address 5 zone expansion kit M7 - Thermal discharge circulator pump B22 - Boiler source probe B23 - Cold source probe 1 - Power supply 230 Vac - 50 Ha 2 - Expansion Addresses 3 - Address 5 Note: - Configure the expansion address as indicated...
  • Page 84: System Manager - Connection To Photovoltaic System

    9.33 SYSTEM MANAGER - CONNECTION TO PHOTOVOLTAIC SYSTEM. 9-33 A15-5 Key: A15-5 - Zone expansion kit with address 5 S39 - On/Off contact from photovoltaic system 1 - Power supply 24 Vac - 50 Hz 2 - Expansion Addresses 3 - Address 5 Note: - Configure the expansion address as indicated.
  • Page 85: System Manager - Connection To Domotics With Digital Signals

    9.35 SYSTEM MANAGER - CONNECTION TO DOMOTICS WITH DIGITAL SIGNALS. 9-35 Serial Address Serial Address 1 2 4 8 1 2 4 8 24Vac ALARM-IN Key: A15 - Zone expansion kit with address 5 A26 - Domotic system. 1 - Supply voltage 24 Vac - 50 Hz 2 - Expansion Addresses 3 - Address 5 Note: - Configure the expansion address as indicated.
  • Page 86: System Manager - Connection To Domotics With Communication Protocol

    9.36 SYSTEM MANAGER - CONNECTION TO DOMOTICS WITH COMMUNICATION PROTOCOL. 9-36 PWM 0/10V J8 ISOLATED input voltage: 24Vac (+10%-15%); 50/60Hz Serial Card 1 48Vdc (36Vmin...71Vmax) max power:8VA/6W Key: A3 - System manager Note: - Communication protocols: 1 - Domotics management system Modbus 9.37 SYSTEM MANAGER - CONNECTION TO PHONE DIALLER.
  • Page 87: System Manager - Connection To Thermoflue

    9.38 SYSTEM MANAGER - CONNECTION TO THERMOFLUE. 9-38 A15-4 Key: A15-4: - Zone expansion kit with address 4 1 - Power supply 24 Vac - 50 Hz 2 - Fireplace heating system 3 - Function 4 - Expansion Addresses 5 - Special functions 1 6 - Address 4 THERMOFLUE: -On/Off contact from thermoflue.
  • Page 88: System Manager - Puffer Probe Connection

    9.39 SYSTEM MANAGER - PUFFER PROBE CONNECTION. 9-39 PWM 0/10V J8 ISOLATED J9 input voltage: 24Vac (+10%-15%); 50/60Hz 48Vdc (36Vmin...71Vmax) max power:8VA/6W A15 - 4 Serial Address 1 2 4 8 Serial Address 24Vac 1 2 4 8 Key: A13: - System manager A15-4 - Address 4 zone expansion kit M10 - Puffer spillage pump (if available) Note: - Configure the expansion...
  • Page 89: System Manager - Three-Way Connection Integration Into Systems With Puffer

    9.41 SYSTEM MANAGER - THREE-WAY CONNECTION INTEGRATION INTO SYSTEMS WITH PUFFER. 9-41 A15-4 Key: - Command (J7) 1 - Power supply 230 Vac - 50 Hz Open -> switch to PdC 2 - A (boiler) Closed -> switch to boiler 3 - B (heat pump) 4 - AB (puffer) - We recommend applying 2 commutation...
  • Page 90: System Manager - Connection To Inertial Storage Tank Probe

    9.42 SYSTEM MANAGER - CONNECTION TO INERTIAL STORAGE TANK PROBE. 9-42 J8 ISOLATED J9 input voltage: max power:8VA/6W A15 - 4 Key: A13 - System manager A15-4 - Address 4 zone expansion kit Notes: - Enable the expansion only when using the M10 - Bleeding circulator (optional) M10 circulator.
  • Page 91: System Manager - Connection To 2 Sloping Roofs Thermal Solar System

    9.44 SYSTEM MANAGER - CONNECTION TO 2 SLOPING ROOFS THERMAL SOLAR SYSTEM. 9-44 91 91...
  • Page 92: System Manager - Solar Return Probe Connection

    9.45 SYSTEM MANAGER - SOLAR RETURN PROBE CONNECTION. 9-45 A15 - 4 Serial Address 1 2 4 8 Serial Address 1 2 4 8 24Vac Key: A15-4 - Address 4 zone expansion kit B20 - Solar return probe 1 - Expansion Addresses 2 - Address 4 Note: - Configure the expansion address as indicated...
  • Page 93: System Manager - Connection To External Probe

    9.46 SYSTEM MANAGER - CONNECTION TO EXTERNAL PROBE 9-46 J8 ISOLATED J9 Key: input voltage: A13 - System manager - External probe max power:8VA/6W 9.47 SYSTEM MANAGER - CONNECTION TO PLATE EXCHANGER DOWNSTREAM OF HEAT PUMP. 9-47 Key: A15-5 - Zone expansion kit with address 5 K5 - Relay type EMR 12 V dc M11 - Pump downstream of the plate heat exchanger on heat pumps...
  • Page 94: List Of Anomalies

    LIST OF A0126 Zone 2 room temperature probe anomaly ANOMALIES. A0127 Zone 3 room temperature probe anomaly HT Zone room temperature probe A0128 Alarm malfunction alarm Alarm Description Code A0129 Zone 1 humidity probe anomaly Domestic hot water boiler/inlet probe A0012 A0130 Zone 2 humidity probe anomaly...
  • Page 95: Product Specifications

    Contribution to the environmental heating Class Description seasonal energy efficiency +4 % System manager kit System manager kit combined with 3 devices VIII +5 % (zone remote panel, zone remote control, humidity temperature sensor) 95 95...
  • Page 96 This instruction booklet is made of ecological paper immergas.com Immergas S.p.A. 42041 Brescello (RE) - Italy Tel. 0522.689011 Fax 0522.680617...