Technical data
7.4 Option modules
2 slotted initiators
•
Digital output (slot-type initiators) A1: Terminals 41 and 42
•
Digital output (slot-type initiators) A2: Terminals 51 and 52
•
Connection
•
Signal state High
(not triggered)
•
Signal state Low (triggered)
•
2 slotted initiators
•
Function
•
Connecting to circuits with the fol‐
lowing peak values
Effective internal capacitance
Effective internal inductance
1 fault message output
•
Digital output: Terminals 31 and 32
•
Connection
•
Signal state High
(not triggered)
•
Signal state Low (triggered)
•
Auxiliary power U
Aux
•
Connecting to circuits with the fol‐
lowing peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
7.4.7.6
Position Transmitter (NCS, MLS) 6DR4004-4ES
Degree of protection provided by en‐
closure
NCS module (NCS)
78
Without explosion pro‐
tection
2-wire system according to EN 60947-5-6 (NAMUR), for switching amplifier connected
Rated voltage 8 V, power
consumption:
≥ 3 mA (limit not activa‐
ted), ≤ 1 mA (limit activa‐
ted)
-
-
At switching amplifier in accordance with EN 60947-5-6: (NAMUR), U
R = 1.1 kΩ
R = 10 kΩ
U
≤ DC 35 V
Aux
I ≤ 20 mA
-
-
-
The 3 digital outputs are galvanically isolated from the basic unit.
Without explosion pro‐
tection
IP66 according to IEC/EN 60529; type 4X according to UL 50E
6DR4004-5L
With explosion protec‐
tion Ex "ia", "db ia", "ic"
on load side
> 2.1 mA
< 1.2 mA
Type SJ2-SN
NC (normally closed)
U
≤ DC 15 V
i
I
≤ 25 mA
i
P
≤ 64 mW
i
C
≤ 161 nF
i
L
≤ 120 μH
i
1 kΩ)
> 2.1 mA
< 1.2 mA
-
U
≤ DC 15 V
i
I
≤ 25 mA
i
P
≤ 64 mW
i
C
= 5.2 nF
i
L
= negligibly small
i
DC 840 V, 1 s
With explosion protec‐
tion Ex "ia", "db ia", "ic"
6DR4004-5LE
Compact Operating Instructions, 11/2022, A5E03436620-AG
With explosion protec‐
tion Ex "ec", "tb"
U
≤ DC 15 V
n
I
≤ 25 mA
n
-
-
= 8.2 V, R
=
Aux
i
> 2.1 mA
< 1.2 mA
-
U
≤ 15 V
i
I
≤ 25 mA
i
-
L
= negligibly small
i
With explosion protec‐
tion Ex "ec", "tb"
6DR4004-5LE
SIPART PS2 (6DR5...)