7.4.7
External position detection
7.4.7.1
Rated conditions for external position detection
Rated conditions
Ambient temperature
•
Permissible ambient temperature for operation
Degree of protection
1)
Climate class
•
Storage
•
Transport
•
Operation
) Impact energy max. 1 joule.
1
See also
Construction (Page 59)
7.4.7.2
External NCS sensors 6DR4004-6N / -8N
Travel range
•
Linear actuator 6DR4004-6/-8N.20
•
Linear actuator 6DR4004-6/-8N.30
•
Part-turn actuator
Linearity (after corrections made by
positioner)
Hysteresis
Temperature influence (range: rota‐
tion angle 120° or stroke 14 mm)
Climate class
•
Storage
•
Transport
Vibration resistance
•
Harmonic oscillations
(sine) according to IEC 60068-2-6
•
Bumping according to IEC
60068-2-29
SIPART PS2 (6DR5...)
Compact Operating Instructions, 11/2022, A5E03436620-AG
In hazardous areas, observe the maximum permissible ambient tem‐
perature corresponding to the temperature class.
-40 ... +90 °C (-40 ... +194 °F)
IP66 / Type 4X to UL 50E
According to IEC/EN 60721-3
1K5, but -40 ... +90 °C (1K5, but -40 ... +194 °F)
2K4, but -40 ... +90 °C (2K4, but -40 ... +194 °F)
4K3, but -40 ... +90 °C (4K3, but -40 ... +194 °F)
Without explosion pro‐
tection
6DR4004-8N
10 to 130 mm (0.39 to 5.12"); up to 200 mm (7.87") on request
≤ 0.1 %/10 K (≤ 0.1 %/18 °F) for -20 to +90 °C (-4 to +194 °F)
≤ 0.2%/10 K (≤ 0.2%/18 °F) for -40 to -20 °C (-40 to -4 °F)
1K5, but -40 to +90 °C (-40 to +194 °F)
2K4, but -40 to +90 °C (-40 to +194 °F)
3.5 mm (0.14"), 2 to 27 Hz, 3 cycles/axis
98.1 m/s² (321.84 ft/s²), 27 to 300 Hz, 3 cycles/axis
300 m/s
With explosion protec‐
tion
Ex "ia", "db ia", "ic"
6DR4004-6N
3 to 14 mm (0.12 to 0.55")
30 to 100°
± 1 %
± 0.2 %
According to IEC/EN 60721-3
(984 ft/s
), 6 ms, 4000 shocks/axis
2
2
Technical data
7.4 Option modules
With explosion protec‐
tion
Ex "ec"
6DR4004-6N
75