Analog Input Module (AIM) 6DR4004-6F / -8F

 
 
The Analog Input Module (AIM) 6DR4004-6F and -8F is required to connect a Non-Contacting Sensor (NCS) or Position Trans‐
For devices without explosion protection, other types of potentiometers with resistance values between 3 and 20 KΩ can be
R-potentiometer
Peak values when supplied by other ba‐
sic devices (6DR50/1/2/3/9)
Maximum values when powered by the
base unit with PA (6DR55) or FF com‐
munication (6DR56)
Signal 20 mA
Rated signal range
Internal load R
B
SIPART PS2 (6DR5...)
Compact Operating Instructions, 11/2022, A5E03436620-AG
Without explosion pro‐
tection or suitable for use
in Ex d version
6DR4004-8J
-
-
-
Electrically isolated from the alarm option and safely isolated from the basic device
Without explosion
protection
6DR4004-8F
mitter 6DR4004-1ES to -4ES.
connected.
 
U
= 5 V
max
U
= 5 V
max
 
0 ... 20 mA
200 Ω
With explosion protec‐
tion Ex "ia", "db ia"
6DR4004-6J
≤ 0.3%
≤ 0.1%/10  K (≤ 0.1%/18 °F)
≤ 0.1%
≤ 1 %
U
 ≤ DC 30 V
i
I
 ≤ 100 mA
i
P
 ≤ 1 W
i
C
 ≤ 11 nF
i
L
 = negligibly small
i
DC 840 V, 1 s
With explosion protec‐
tion
Ex "ia", "db ia", "ic"
6DR4004-6F
 
U
 ≤ 5 V
o
I
 ≤ 100 mA
o
P
 ≤ 33 mW
o
C
 ≤ 1 μF
o
L
 ≤ 1 mH
o
U
 ≤ 5 V
o
I
 ≤ 75 mA static
o
I
 ≤ 160 mA transient
o
P
 ≤ 120 mW
o
C
 ≤ 1 μF
o
L
 ≤ 1 mH
o
 
Technical data
7.4 Option modules
With explosion protec‐
tion
Ex "ic", "ec", "tb"
6DR4004-6J
"ic":
U
≤ DC 30 V
i
I
 ≤ 100 mA
i
"ec"/"tb":
U
 ≤ DC 30 V
n
I
 ≤ 100 mA
n
P
 ≤ 1 W
n
C
 ≤ 11 nF
i
With explosion protec‐
tion
Ex "ec", "tb"
6DR4004-6F
 
U
= 5 V
max
U
= 5 V
max
 
-
-
71