Technical data
7.2 With 4 to 20 mA/HART
Note
The following applies for exhaust air outlet with sound absorber
The positioner is supplied as standard with a sound absorber. To provide an outlet for the exhaust
air, replace the sound absorber by a G¼ pipe coupling.
The following applies for enclosure ventilation
1. With the "flameproof enclosure" device version in an aluminum enclosure with order suffix
-Z K50 "Operation with natural gas", you can completely collect and discharge the escaping
natural gas.
2. In all other device versions, the escaping natural gas is released into the environment.
Maximum values for escaping natural gas
• The quantity of escaping natural gas is negligible during regulated operation.
• If a control error occurs, a maximum of 30 Nl/min of natural gas will escape at the enclosure
vent
7.2
With 4 to 20 mA/HART
7.2.1

Electrical data

 
Current input I
W
Rated signal range
Test voltage
Digital input DI1 (terminals
9/10; galvanically connected to
basic device)
 
2-wire connection
6DR50.. and 6DR53.. 4 ... 20 mA
6DR51.. and 6DR52.. HART
Current to maintain the auxiliary
power
Required load voltage U
B
sponds to Ω at 20 mA)
6DR50.0/1/2/3
 
Typical
 
Max.
64
and a maximum of 89 Nl/min at the control air outlet
Electronics
without explosion
protection
 
(corre‐
 
 
6.36 V (= 318 Ω)
6.53 V (= 327 Ω)
Electronics with ex‐
plosion protection
Ex "db"
 
4 ... 20 mA
840 V DC, 1 s
Suitable only for floating contact; max. contact load
< 5 μA at 3 V
≥ 3.8 mA
 
6.36 V (= 318 Ω)
6.53 V (= 327 Ω)
Compact Operating Instructions, 11/2022, A5E03436620-AG
:
and control air outlet
.
Electronics with ex‐
Electronics with ex‐
plosion protection
plosion protection
Ex "ia", "db ia"
Ex "ic", "ec", "tb"
 
 
 
 
7.8 V (= 390 Ω)
7.8 V (= 390 Ω)
8.3 V (= 415 Ω)
8.3 V (= 415 Ω)
:
SIPART PS2 (6DR5...)