Commissioning
5.6 Commissioning linear actuators
Initializing the linear actuator automatically
Note
Interrupting initialization
An ongoing initialization can be interrupted at any time. To do this, press
configured until then are retained.
All parameters are reset to factory settings only if you have explicitly activated the preset settings
in the "PRST" parameter.
Note
Commissioning of a tight-closing valve
If the valve is tight-closing, set the "YCLS" parameter before commissioning. This ensures that
the end positions are approached for at least 15 seconds during initialization.
1. Switch to the "Configuration" mode. To do this, keep the
seconds. The display shows the following:
2. Call the "2.YAGL" parameter. To do this, press
depending on the setting:
3. Check whether the value displayed in the "2.YAGL" parameter matches the setting of the
transmission ratio selector. If required, change the setting of the transmission ratio selector
to 33° or 90°.
46
button pressed for at least 5
. The following is shown on the display
Compact Operating Instructions, 11/2022, A5E03436620-AG
. The settings
SIPART PS2 (6DR5...)