Commissioning
5.1 Basic safety instructions
Opening device in energized state
Risk of explosion in hazardous areas
• Only open the device in a de-energized state.
• Check prior to commissioning that the cover, cover locks, and cable inlets are assembled in
Exception: Devices having the type of protection "Intrinsic safety Ex i" may also be opened in
energized state in hazardous areas.
Water in compressed air line
Device damage and possibly loss of type of protection. The factory setting for the purging air
selector is "IN". In the "IN" position, water from the compressed air line may enter the device
from the pneumatics during initial commissioning.
• Before commissioning, make sure that no water is present in the compressed air line.
If you cannot be sure that there is no water in the compressed air line:
• Set the purging air selector to "OUT". In this way, you prevent water from the compressed
• Only set the purging air selector to "IN" again when all water has been discharged from the
Increased sound pressure level
Changes to the sound absorber of the positioner or the mounting of pneumatic components
or pneumatic options on the positioner can cause a sound pressure with a level of 80 dBA to be
exceeded.
• Wear suitable hearing protection to protect yourself against hearing damage.
40
WARNING
accordance with the directives.
WARNING
air line from penetrating the device.
compressed air line.
CAUTION
Compact Operating Instructions, 11/2022, A5E03436620-AG