Table 4 - Electrical Lug Data - York YVAA Installation Operation & Maintenance

Air-cooled screw liquid chillers, air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

Form 201.47-ICOM1
Issue date: 17/11/2022

Table 4 - Electrical lug data

FIELD WIRING LUGS
YVAA-B MODEL
EVAP
YVAA0161/0571
2004
YVAA0201/0701
2004
YVAA0166/0586
2004
YVAA0211/0741
2004
JOHNSON CONTROLS
STANDARD 2HP (with & Without VSD) CONDENSER FANS
TERMINAL BLOCK
INPUT
INPUT
WIRES
VOLTS
FREQ
PER
PHASE
SINGLE POINT WIRING
200
60
4
230
60
4
380
60
2
400
50
2
460
60
2
575
60
2
200
60
4
230
60
4
380
60
3
400
50
3
460
60
2
575
60
2
200
60
4
230
60
4
380
60
2
400
50
2
460
60
2
575
60
2
200
60
4
230
60
4
380
60
2
400
50
2
460
60
2
575
60
2
CIRCUIT BREAKER
LUG
WIRES
LUG
WIRE
PER
WIRE
RANGE
PHASE
RANGE
#2 – 600
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
2
2/0 ~ 500
kcmil
kcmil
#2 – 600
2
2/0 ~ 500
kcmil
kcmil
#2 – 600
2
2/0 ~ 500
kcmil
kcmil
#2 – 600
2
#1 ~ 500
kcmil
kcmil
#2 – 600
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
3
3/0 ~ 400
kcmil
kcmil
#2 – 600
2
#1 ~ 500
kcmil
kcmil
#2 – 600
2
#1 ~ 500
kcmil
kcmil
#2 – 600
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
2
2/0 ~ 500
kcmil
kcmil
#2 – 600
2
2/0 ~ 500
kcmil
kcmil
#2 – 600
2
2/0 ~ 500
kcmil
kcmil
#2 – 600
2
#1 ~ 500
kcmil
kcmil
#2 – 600
kcmil
#2 – 600
4
4/0 ~ 500
kcmil
kcmil
#2 – 600
2
#1 ~ 500
kcmil
kcmil
#2 – 600
2
#1 ~ 500
kcmil
kcmil
#2 – 600
2
2/0 ~ 500
kcmil
kcmil
#2 – 600
2
#1 ~ 500
kcmil
kcmil
SECTION 4 - INSTALLATION
NON-FUSED DIS-
CONNECT SWITCH
WIRES
LUG
PER
WIRE
PHASE
RANGE
2
#2 – 600
kcmil
2
#2 – 600
kcmil
2
#2 – 600
kcmil
2
#2 ~ 600
kcmil
3
#2 – 600
kcmil
3
#2 – 600
kcmil
3
#2 – 600
kcmil
2
#2 ~ 600
kcmil
2
#2 – 600
kcmil
2
#2 – 600
kcmil
2
#2 – 600
kcmil
2
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
3
#2 ~ 600
kcmil
2
#2 – 600
kcmil
2
#2 ~ 600
kcmil
45