Installing the Inverter
29
SolarEdge Installation Guide for Three Phase Inverters – EU
Connecting the Inverter
Inverter Connection Overview
The SolarEdge inverter can be configured in the field for an AC grid,
including AC voltage and frequency. If the inverter's default settings are
not suited to the country of the installation site, then please refer to page 57
for a description of how to configure the inverter for the required country.
With the SolarEdge Configuration Tool, you can configure the inverter's
AC settings to different settings than those provided by default for the
country of the installation site, or perform other modifications. A full
description of the Configuration Tool is provided in the SolarEdge
Configuration Tool Software Guide.
WARNING!
A 32 A
fuse or circuit breaker are required at the connection point of the Three
AC
Phase Inverter to the grid.
WARNING!
It is essential to connect the PE (ground) wiring before connecting the AC Line and
Neutral wires.
WARNING!
Grounding of the DC side is prohibited because the Three Phase Inverter has no
transformer.