Electrical Notes - York YCAS Series Wiring Diagram

Air-cooled screw liquid chillers
Table of Contents

Advertisement

NOTES & LEGEND
LEGEND
ACR-LINE
ACROSS THE LINE START
C.B.
CIRCUIT BREAKER
D.E.
DUAL ELEMENT FUSE
DISC SW
DISCONNECT SWITCH
FACT CB
FACTORY-MOUNTED CIRCUIT BREAKER
FLA
FULL LOAD AMPS
HZ
HERTZ
MAX
MAXIMUM
MCA
MINIMUM CIRCUIT AMPACITY
MIN
MINIMUM
MIN NF
MINIMUM NON-FUSED
RLA
RUNNING LOAD AMPS
S.P. WIRE
SINGLE-POINT WIRING
Y-∆
WYE-DELTA START
X-LRA
ACROSS-THE-LINE INRUSH LOCKED ROTOR AMPS
Y-LRA
WYE-DELTA INRUSH LOCKED ROTOR AMPS
NOTES
1. MRA is Maximum Running Amps, the maximum continuous current at any operating point in the rating range. Also referred to as MCA, or
Minimum Circuit Ampacity to be provided by the installer. If a Factory Mounted Control Transformer is provided, add 3 amps to the system
#1 MCA values in the YCAS Tables.
2. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440 - 12A1.
3. Minimum recommended fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs. Minimum fuse rating =
(1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,
per N.E.C. 440-22. Maximum fuse rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
5. Minimum recommended circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit. Minimum circuit breaker
rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per
U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other com pres sor RLAs + ( # fans x each fan motor
FLA).
7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), or (3)
indicate the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must be
determined based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based on the
National Electrical Code and using copper connectors only. Field wiring must also comply with local codes.
8. A ground lug is provided for each compressor system to accommodate fi eld grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied.
9. The fi eld supplied disconnect is a "Disconnecting Means" as defi ned in N.E.C. 100.B, and is intended for isolating the unit from the available
power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
10. Two-compressor machines with single-point power connection, and equipped with Star-Delta compressor motor start must also include
Factory provided circuit breakers in each motor control center.
11. Consult factory for Electrical Data on units equipped with "High Static Fan" option. 50Hz High Static Fans are 3.5kW each.
12. FLA for each "Low Noise Fan" motor: 380v/50Hz = 4.1A.
4

ELECTRICAL NOTES

ELECTRICAL NOTES
FORM 201.19-W3 (1104)
VOLTAGE CODE
-50 = 380-3-50
YORK INTERNATIONAL

Advertisement

Table of Contents
loading

Table of Contents