ELECTRIC CONNECTION.

The board consists of three relays (relay 1 = K1; relay 2 = K2
and relay 3 = K3). The relays can be configured according to
the boiler model. Therefore, different functions can be obtained
depending on the connection (see boiler instruction booklet).
N.B.: for the configuration of the functioning options, refer to the
P.C.B. programming paragraph in the boiler instruction book.
EXTERNAL 3-WAY VALVE WIRING DIAGRAM.
By setting relay 1 as "3-way external system" it's possible to obtain
on the K1 control the replication of the 3-way status inside the
boiler. Relay K1 will be energized (by closing contacts 54-56)
when a heating request is active (CH), while it will be at rest
(closing contacts 54-55) both with boiler in stand-by and during
DHW operation (DHW ). The diagram shows as an example
the possible connections of an external 3-way valve with 230 V
power supply: if it's necessary to use an external 3-way valve on
RELAY BOARD
RELAY BOARD
Phase
Phase
Blue
Blue
Brown
Brown
230V Connection terminal board
230V Connection terminal board
230 Vac 50 Hz
230 Vac 50 Hz
power supply
power supply
Fig. 1-2
Relay board technical data.
Power supply voltage: ............................................. 230VAC 50Hz
contact K1 max capacity: ..........................230VAC 1.00A cosφ 1
contact K2 max capacity: ..........................230VAC 0.75A cosφ 1
contact K3 max capacity: ..........................230VAC 0.75A cosφ 1
Relay K2 enabling contact (X25) SELV 24VDC 10mA (low
voltage in safe conditions)
Attention: do not exceed the maximum load allowed by the fuses
on the mother board (it is added to the boiler load) (3.15A fuse).
the boiler, the hydraulic system must be adapted, excluding the
action of the 3-way valve inside the boiler. In cases where it's
necessary to have a signal corresponding to the boiler's DHW
operation, it's necessary to "add" both the '3-way status in DHW'
and the 'boiler circulator active' signal.
Very low
Very low
safety
safety
voltage
voltage
INTEGRATED P.C.B.
INTEGRATED P.C.B.
3-WAY VALVE
3-WAY VALVE
Phase
Phase
Phase
Phase
Neutral
Neutral
Low voltage connection terminal board
Low voltage connection terminal board
33