Uninterruptable Power
Supply for 208VAC Grid
L30US-IB80, L30US-IB00,
L40US
User Guide
Version 2.0 March 2022
Cat. No. 2MUM-

Advertisement

Table of Contents
loading

Summary of Contents for SolarEdge L30US-IB80

  • Page 1 Uninterruptable Power Supply for 208VAC Grid L30US-IB80, L30US-IB00, L40US User Guide Version 2.0 March 2022 Cat. No. 2MUM-...
  • Page 3 Important Notice Copyright © July 2021 SolarEdge Inc. Doc. Part 2MUM-SG-. All rights reserved.  No part of this document may be reproduced, stored in a retrieval system, or transmitted,  in any form or by any means, electronic, mechanical, photographic, magnetic, or otherwise, without the prior written permission of SolarEdge Inc.
  • Page 4 If you experience a problem with the UPS, please refer to the Troubleshooting section in this manual to correct the problem. If the problem is not corrected, please collect information so that the Technical Support personnel can more effectively assist you. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 5: Table Of Contents

    Introduction ..............................26 4.3.2. Data ................................... 27 4.3.3. Status ................................27 4.3.4. Main ..................................... 28 4.3.4.1. Bypass ..................................29 4.3.4.2. Output ..................................29 4.3.4.3. Battery ..................................30 4.3.4.4. Status info .................................. 31 4.3.4.5. Alarm ................................33 4.3.5. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 6 Operational status and mode(s) ....................55 4.4.2. Faults and alarms reports ......................56 4.5. PTIONAL FEATURES ...................................... SNMP card ..............................60 4.5.1. 4.5.1.1. Functions ..............................60 Relay card ................................ 61 4.5.2. APPENDIX 1: SPECIFICATIONS ..................... 63 APPENDIX 2: TROUBLESHOOTING ....................68 L30US-IB80, L30US-IB00, L40US UPS...
  • Page 7 5000 UPS ID IGURE USER SETTING PAGE ............................20 LCD IGURE CONTROL PANEL INTRODUCTION ............................21 SNMP IGURE CARD ....................................22 R ) ......................61 IGURE ELAY CONTACTS DRY CONTACT CARD 23 R IGURE ELAY OVERVIEW ..................................L30US-IB80, L30US-IB00, L40US UPS...
  • Page 8 ) ......................... 55 ABLE PERATIONAL STATUS AND MODE ABLE AULT NFORMATION ..................................ABLE LARM NFORMATION ..................................) ......................61 ABLE ELAY CONTACTS COMMUNICATION CARD 10 S ABLE PECIFICATIONS .................................... 11 P ABLE ROBLEMS AND SOLUTIONS ................................. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 9: Preface

    Denotes a warning. It calls attention to a procedure that, if not correctly performed or adhered to, could result in injury or loss of life. Do not proceed beyond a warning note until the indicated conditions are fully understood and met. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 10: Technical Support

    1.3. Technical Support You can contact technical support via any of the following methods: SOLAREDGE Inc. - Critical Power Service Department Available via email at Service.CP@SolarEdge.com ...
  • Page 11: Important Safety Instructions (Save These Instructions)

    2. Important Safety Instructions (Save These Instructions) SAVE THESE INSTRUCTIONS! This manual contains important instructions, for models L30US-IB80, L30US-IB00, and L40US, that should be followed during installation and maintenance of the UPS and batteries. CAUTION! To reduce the risk of fire, connect only to a circuit provided with DC 160...
  • Page 12 Remove watches, rings, or other metal objects. • Use tools with insulated handles. • Wear rubber gloves and boots. • Do not lay tools or metal parts on top of batteries. • Disconnect charging source prior to connecting or disconnecting battery terminals. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 13: Table 1 Batteries Quantity

    SolarEdge P/N Description L30US-IB80 30 kVA L30IBUS-L6G4V09001 L30US 3PH 4W UPS 208V 30KVA/30KW IB80 L30US-IB00 30 kVA L30IBUS-L6G0V09001 L30US 3PH 4W UPS 208V 30KVA/30KW IB00 L40US 40 kVA L40US-L6G0VNN001 L40US 3PH 4W UPS 208V 40KVA/40KW IB00 L30US-IB80, L30US-IB00, L40US UPS...
  • Page 14: Main Features

     2nd-stage: Constant Voltage in order to vitalize battery and make sure batteries are fully  charged. 3rd stage: Floating mode.  This 3-stage charging method will extend life of the batteries and guarantee fast charging. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 15: System Configuration

    Backup time required will indicate the battery size needed. If the load is less than the UPS  nominal power rating, then the actual backup time is longer. The following options are available with extra charge:  SNMP/WEB card  Relay card  L30US-IB80, L30US-IB00, L40US UPS...
  • Page 16: Cabinet View

    3.4. Cabinet view Figure 1 Front view/Side view of L30US-IB80, L30US-IB00 and L40US Figure 2 Front view (without door) and Rear View of L30US-IB80 and L30US-IB00 L30US-IB80, L30US-IB00, L40US UPS...
  • Page 17: Figure 3 Front View (Without Door) And Rear View Of L40Us

    (1) LCD panel (2) Front door and lock (3) Mains input breaker (4) Bypass input breaker (5) Maintenance breaker cover (6) Maintenance breaker (7) Output breaker (8) Communication panel (9) Rear cover (10) Terminal block cover L30US-IB80, L30US-IB00, L40US UPS...
  • Page 18: Dimensions And Weight

    3.5. Dimensions and Weight Figure 4 Dimensions L30US-IB80, L30US-IB00, L40US UPS...
  • Page 19: Table 3: Dimensions And Weights

    Table 3: Dimensions and Weights Model Width Depth Height Weight L30US-IB80 400mm (15.75”) 935mm (36.8”) 1065mm (41.9”) 374kg (825lb) L30US-IB00 400mm (15.75”) 935mm (36.8”) 1065mm (41.9”) 162kg (357lb) L40US 400mm (15.75”) 935mm (36.8”) 1065mm (41.9”) 145kg (320lb) L30US-IB80, L30US-IB00, L40US UPS...
  • Page 20: Communication Panel

    (12) Intelligent Slot 1 (SNMP card/ Relay card) (13) Intelligent Slot 2 (SNMP card/ Relay card) 3.6. Computer access 1. With the USB cable, connect the USB port of the UPS to the computer. 2. Open the Muser5000 software, click the System button. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 21: Figure 6 Muser5000 Homepage

    3. On Software Parameter Setting, choose COM according to your UPS, choose 9600 for baud rate, choose modbus for protocol, then click Save setting. Figure 7 Muser5000 communication setting page 4. On the main page of Muser5000, click the Append button, Append equipment screen opens. Enter the Password: YDC3350. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 22: Figure 8 Muser5000 Append Equipment Page

    6. Click the Append button. Connection between the UPS and the computer is now established. CAUTION! When the UPS works on inverter: to set the output voltage and frequency using your PC, you must shut down the inverter first. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 23: Operation

    In case the AC mains input power fails, the inverter starts obtaining power from the battery and supplies the critical AC load. There is no power interruption to the critical load. The UPS will automatically return to Normal mode when AC recovers. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 24: Maintenance Mode (Manual Bypass)

    AC load. This is to avoid paralleling of unsynchronized AC sources. This interruption is programmable but typically set to be less than an electrical cycle e.g., less than 15ms (50Hz) or less than 13.33ms (60Hz). L30US-IB80, L30US-IB00, L40US UPS...
  • Page 25: Eco Mode

    Line-interactive mode, that is, on bypass supply. When the AC is out of the set window, the UPS will transfer from bypass to inverter and supply power from the battery. SINGLE INPUT: Mains Input DUAL INPUT: Mains Input and Bypass Input Figure 14 ECO mode L30US-IB80, L30US-IB00, L40US UPS...
  • Page 26: Ups Operation

    Turn on the MAINS to simulate utility recovery, the rectifier will restart automatically  after 20 seconds and the inverter will supply the load. The UPS can be loaded up to its maximum capacity during load test. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 27: Maintenance Bypass

    2. Turn on MAINTENANCE breaker. 3. Turn OFF the MAINS breaker. 4. Turn OFF the BYPASS breaker. 5. Turn OFF the OUTPUT breaker. The load will be fed through the MAINTENANCE breaker. Switch to normal operation (from mechanical bypass) 4.2.5. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 28: Cold Start Procedure

    Set the Battery Breaker to ON for long-run UPS.  Refer to the section Important Safety Instructions (Save These Instructions) in this  manual. Turn on the OUTPUT breaker.  Trigger the cold start button. (see the figure below).  L30US-IB80, L30US-IB00, L40US UPS...
  • Page 29: Shutdown Procedure

    This procedure will be followed by complete shutdown the UPS and the load. After all power switches, isolators and circuit breakers are opened, there will be no output. 1. For L30US-IB80, L30US-IB00, shut down the inverter; navigate to common → inv on/off → single off (see 4.3.9.1).
  • Page 30: Parallel Setting

    Connect the UPS to the computer (See 3.6). Power on the UPS.  Open Muser5000 software; after connecting to the UPS successfully, click System >User  Set. Figure 16 Muser5000 homepage Click Set at User Set screen. The password is YDC3350.  L30US-IB80, L30US-IB00, L40US UPS...
  • Page 31: Figure 17 Muser5000 User Setting Page

    At the screen of Data Set, click Ups ID, write a value for the parallel UPS ID at the right  side, such as 1, then click Set (see the figure below). If the UPS sounds a beep, the setting is correct. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 32: Figure 19 Muser5000 Ups Id Setting Page

    Parallel cable cannot be connected when setting the parallel parameters. After setting the UPS systems that need to be paralleled, power off all the UPS systems.  Connect all the UPS systems in parallel cable installation, then power on the UPS systems. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 33: Lcd Control Panel

    4.3. LCD control panel Overview 4.3.1. Figure 20 LCD control panel introduction Table 5 LCD and LED display Fault LED Bypass mode LED Battery mode LED Inverter work LED LCD display L30US-IB80, L30US-IB00, L40US UPS...
  • Page 34: Introduction

    This chapter describes the UPS GUI, its functions and navigation. On any screen, click return to return to the previous screen, click home to return to the main screen. CAUTION! The setting of most parameters cannot be set when the UPS is in Inverter mode. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 48: Bypass Settings

    The value range is ±1%, ±2%, ±4%, ± 5%, ±10%(default). Bypass Rate Tracking Rate: Inverter frequency tracking to bypass frequency rate. The value range is 0.5~2Hz/s and is 1 by default. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 49 Bypass mode and Normal mode within 1 hour, which ensures system security. The value range is 3 to 10, default is 10. EPO Transfers To BYP: Specifies whether to transfer to Bypass mode when the EPO button is pressed. The default value is Disable. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 50: Advanced Settings

    Advanced settings 4.3.7. Click advanced setting, input the correct password. The user password is 499283. NOTE! This operation is recommended to be operated by professionals, or under the guidance of professionals. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 53: Parallel Setting

    The value can be 0~1, default value is 0, maximum allowed value is 1, because only two UPS systems of this model can be connected in a parallel system. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 57: Dry Contact Setup

    External Maint. Breaker (MT): Enable or disable external maintenance breaker connection detection. The default value is Disable. Battery breaker (BAT): Enable or disable battery breaker connection detection. The default value is Disable. NOTE! Each dry contact can be N.O or N.C. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 59: Timing Daily

    Timing daily 4.3.8.2. Modify the check date and time (10S (default), 10min, EOD). Timing weekly 4.3.8.3. Modify the check date and time (10S (default), 10min, EOD). L30US-IB80, L30US-IB00, L40US UPS...
  • Page 63: Display Messages And Troubleshooting

    NO Beeps Beeps UPS Static Bypass NO Beeps Mode Beeps UPS Maintenance NO Beeps Bypass Mode Beeps UPS Frequency NO Beeps Converter Mode Beeps UPS Load Overload Beeps/1s Blink/2s Beeps/2s or UPS Warnings Blink/2s Blink/2s Beeps/1s L30US-IB80, L30US-IB00, L40US UPS...
  • Page 64: Faults And Alarms Reports

    Beeps continuously Fault LED lit Once per 2 seconds Fault LED lit Unit insert fault Once per 2 seconds Fault LED lit Rectifier Fault Beeps continuously Fault LED lit Inverter Fault Beeps continuously Fault LED lit L30US-IB80, L30US-IB00, L40US UPS...
  • Page 65 Beeps continuously Fault LED lit ECU Initializes Fault Once per 2 seconds Fault LED blinking Beeps continuously Fault LED lit Bypass SCR Broken Beeps continuously Fault LED lit Bypass SCR short Beeps continuously Fault LED lit L30US-IB80, L30US-IB00, L40US UPS...
  • Page 66: Table 8 Alarm Information

    Mains Freq. Once per 2 seconds INVERTER LED blinking Abnormal Mains Volt. Once per 2 seconds INVERTER LED blinking Abnormal REC Comm. Error Once per 2 seconds INVERTER LED blinking Mains input lost Once per 2 seconds L30US-IB80, L30US-IB00, L40US UPS...
  • Page 67 FAULT LED blinking Once per second BYPASS LED blinking BPS Phase Reversed Once per second BYPASS LED blinking Once per 2 seconds BYPASS LED blinking BPS Unable To Trace Once per 2 seconds BYPASS LED blinking L30US-IB80, L30US-IB00, L40US UPS...
  • Page 68: Optional Features

    Remote UPS monitoring and management can be performed through HTTP, SNMP,  SSH, Telnet. Complete equipment event handling (including event recording and notification).  Can be extended to connect 2 channels of temperature and humidity monitoring  modules. L30US-IB80, L30US-IB00, L40US UPS...
  • Page 69: Relay Card

    Table. Figure 22 Relay contacts (dry contact card) Table 9 Relay contacts (communication card) Function Description Input or Output Utility Failure Battery Low Output Bypass On UPS Fault L30US-IB80, L30US-IB00, L40US UPS...
  • Page 70: Figure 23 Relay Overview

    Inverter On Summary Alarm Common Remote Shutdown + Input (5~12V) Figure 23 Relay overview L30US-IB80, L30US-IB00, L40US UPS...
  • Page 71: Appendix 1: Specifications

    Parallel system (integrated parallel / Static Switch Cubicle) Up to 2 Standalone Parallel Frequency Configuration converter s or architecture Bus Synchronization without external box Input THDI (100% Load) <3% PF (100% R Load) >0.99 Frequency tolerance 40-70Hz L30US-IB80, L30US-IB00, L40US UPS...
  • Page 72 Manually and automatically programmable by time or Battery test voltage Decentralized battery in parallel Support mode Output Online mode 110% 60mins, 125% 10mins, 150% 1mins Overload Battery mode 110% 60mins, 125% 10mins, 150% 1mins THDU Linear load L30US-IB80, L30US-IB00, L40US UPS...
  • Page 73 (heat pipe, liquid, air) Cooling Air inlet: front Air flow input / output Air outlet: rear Internal 125A 3P 150A 3P mains Internal 125A 3P bypass Internal Breaker Internal maintenance 125A 3P bypass Internal 125A 3P output L30US-IB80, L30US-IB00, L40US UPS...
  • Page 74 Acoustic Noise from <68dB <72dB 1m distance Altitude Up to 3280.84 ft without derating Physical Dimension D×W×H (mm) See Table 3 Back 500mm/ 20’’ Service Access Right side 1000mm/ 40’’ 500mm/20’’ Left side 1000mm/ 40’’ 500mm/20’’ L30US-IB80, L30US-IB00, L40US UPS...
  • Page 75 Wheels and leveling feet Net weight See Table 3 Standards Approving Agency TUV RHEINLAND CHINA & CCIC Agency Standard Tested UL1778 5th Edition Canadian Approvals CSA 22.2-107.3-14 EMI Approvals FCC Part15 Subpart B Class A/ ANSI C63.4 2014 L30US-IB80, L30US-IB00, L40US UPS...
  • Page 76: Appendix 2: Troubleshooting

    6. Appendix 2: Troubleshooting Failures in the UPS work can be caused by wrong installation, wiring, or operation. Check these aspects first. If this is not the case, please consult your local SolarEdge agent, providing the product model name and serial number.
  • Page 77 5. Switch on the power breaker. 5. Power breaker on the rear panel is off. Buzzer beeps UPS is out of order. Consult with your local agent continuously and for repair. LCD indicates 1,3,5,9,15, etc. fault codes L30US-IB80, L30US-IB00, L40US UPS...