The board of the main hydraulic module supplies two types of control signal ports:
Type 1: Potential-free contact.
Type 2: The port supplies the signal with 220V voltage.
If the load current is <0.2A, the load can be connected directly to the port.
If the load current is ≥0.2A, an AC contactor must be connected for the load.
The connectors CN11/CN7 of the board of the main hydraulic module: the active solar station contact, the 3-way valves,