10.5.11 TEST RUN.
TEST RUN is used to check correct operation of the valves, de-aeration, operation of the circulation pump, cooling, heating
and domestic hot water heating.
Go to MENU>FOR SERVICEMAN>11.TEST RUN.
Press OK. The following page will be displayed:
If YES is selected, the following pages will be displayed:
If POINT CHECK is selected, the following pages are displayed:
Press
to scroll to the components you want to check and press ON/OFF. For example, when the 3-way valve is se-
lected and ON/OFF is pressed, if the 3-way valve is open/closed, then operation of the 3-way valve is normal, as are the
other components.
CAUTION
Before the point check, make sure that the tank and water system are filled with water and air is ejected, otherwise the
pump could be damaged.
11 MODALITÀ TEST
11. TEST RUN
Active the settings and active the
Attivare le impostazioni e la
"MODO TEST"?
'TEST RUN'?
YES
NO
NO
OK
CONFERMARE
ENTER
11 MODALITÀ TEST
11. TEST RUN
11.1 CONTROLLO PUNTI
11.1 POINT CHECK
11.2 SFIATO ARIA
11.2 = AIR PURGE
11.3 POMPA CIRCOLATA IN FUNZIONE
11.3 CIRCULATED PUMP RUNNING
11.4 ATTIVAZIONE MODO FREDDO
11.4 COOL MODE RUNNING
11.5 ATTIVAZIONE MODO CALDO
11.5 HEAT MODE RUNNING
ENTER
OK
CONFERMA
11 MODALITÀ TEST
11. TEST RUN
11.6 ATTIVAZIONE MODO ACS
11.6 DHW MODE RUNNING
ENTER
OK
CONFERMA
11 MODALITÀ TEST
11. TEST RUN
VALV. 1 3-VIE
3 WAY-VALVE 1
3 WAY-VALVE 2
VALV. 2 3-VIE
PUMP I
POMPA I
PUMP O
POMPA O
PUMP C
POMPA C
ON/OFF
ON/OFF
ON/OFF
11 MODALITÀ TEST
11. TEST RUN
POMPA SOLARE
PUMPSOLAR
POMPA ACS
PUMPDHW
RISC. RISER. INTERNO
INNER BACKUP HEATER
RISC. ACC. ACS
TANK HEATER
VALV. 3 3-VIE
3 WAY-VALVE 3
ON/OFF
ON/OFF
ON/OFF
109
1/2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2/2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents