If you experience a problem with the UPS, please refer to the Troubleshooting section in this manual to correct the problem. If the problem is not corrected, please collect information so that the Technical Support personnel can more effectively assist you. L30US-IB80, L30US-IB00, L40US UPS...
Page 6
UNCTION DESCRIPTION ................................11.2. EFINITION OF MALE PORT ..............................11.3. ACKFEED ROTECTION FUNCTION ............................11.4. ACKFEED INSTALLATION WITH RELAY ............................ APPENDIX 8 REPO INSTRUCTION .................... 64 APPENDIX 8 MAINT. INSTRUCTION ..................65 APPENDIX 9 BAT-SW INSTRUCTION ..................66 L30US-IB80, L30US-IB00, L40US UPS...
Page 7
IGURE PORT ....................................43 C PC RS232 UPS RS232 IGURE ONNECTION BETWEEN PORT AND PORT ..................44 RS485 IGURE PORT ....................................45 D IGURE RY CONTACT PORT ................................... 46 B IGURE ACKFEED INSTALLATION WITH RELAY ............................L30US-IB80, L30US-IB00, L40US UPS...
Page 8
IGURE ONNECTION BETWEEN THE BUTTON AND PORT ....................48 C AUX. UPS MAINT. IGURE ONNECTION BETWEEN THE EXTERNAL MAINTENANCE BREAKER PORT ........49 C AUX. UPS BAT-SW IGURE ONNECTION BETWEEN THE EXTERNAL BATTERY BREAKER PORT ..........L30US-IB80, L30US-IB00, L40US UPS...
Page 9
ONNECTION BETWEEN THE BUTTON AND EPO PORT ..................... 22 C AUX. UPS MAINT. ABLE ONNECTION BETWEEN THE EXTERNAL MAINTENANCE BREAKER PORT .......... 23 C AUX. UPS BAT-SW ABLE ONNECTION BETWEEN THE EXTERNAL BATTERY BREAKER PORT ........... viii L30US-IB80, L30US-IB00, L40US UPS...
Denotes a warning. It calls attention to a procedure that, if not correctly performed or adhered to, could result in injury or loss of life. Do not proceed beyond a warning note until the indicated conditions are fully understood and met. L30US-IB80, L30US-IB00, L40US UPS...
1.3. Technical Support You can contact technical support by any of the following methods. SOLAREDGE Inc. - Critical Power Service Department Available via email at Service.CP@SolarEdge.com ...
2. Important Safety Instructions (Save These Instructions) SAVE THESE INSTRUCTIONS! This manual contains important instructions for models L30US-IB80, L30US-IB00 and L40US that should be followed during installation and maintenance of the UPS and batteries. CAUTION! To reduce the risk of fire, connect only to a circuit provided with DC 160...
Page 13
The following precautions should be observed when working on batteries: • Remove watches, rings, or other metal objects. • Use tools with insulated handles. • Wear rubber gloves and boots. • Do not lay tools or metal parts on top of batteries. L30US-IB80, L30US-IB00, L40US UPS...
Page 14
Before conducting any maintenance, repair, or shipment, first ensure that all the UPS equipment is completely turned off and disconnected. For additional safety instructions, see the Safety section of the Service Manual. For batteries quantity, see Table 10. L30US-IB80, L30US-IB00, L40US UPS...
1. Remove the 2 fixing screws of the top cover, remove the top cover. Remove the 12 fixing screws of the left and right cover, remove the left and right cover. Figure 1 Remove covers 2. Reinstall the battery connector in the following order: L30US-IB80, L30US-IB00, L40US UPS...
Disconnected Remove the fixer Connect and reinstall the fixer Figure 3 Disconnecting battery connector: order of operations L30US-IB80, L30US-IB00, L40US UPS...
2nd-stage: Constant Voltage in order to vitalize battery and make sure batteries are fully charged. 3rd stage: Floating mode. This 3-stage charging method will extend life of the batteries and guarantee fast charging. L30US-IB80, L30US-IB00, L40US UPS...
Backup time required will indicate the battery size needed. If the load is less than the UPS nominal power rating, then the actual backup time is longer. The following options are available with extra charge: SNMP/WEB card Relay card L30US-IB80, L30US-IB00, L40US UPS...
Should the equipment not be installed immediately it must be stored in a room that protects it against excessive humidity and/or heat sources. L30US-IB80, L30US-IB00, L40US UPS...
9843 11483 13123 14764 16404 (m/ft) Load 100% coefficient The UPS should be kept in a well-ventilated room. There are many ventilation holes on front and rear, they must not be blocked by any obstacles. L30US-IB80, L30US-IB00, L40US UPS...
(do not discard them), 4 adjustable legs, and castor stoppers are supplied with the system. Figure 6 400mm wide unit mounting device Unit wheels can be locked as shown below. Figure 7 Unit wheels locking device L30US-IB80, L30US-IB00, L40US UPS...
1. Do not tilt the UPS when unpacking. 2. Check the appearance to see if the UPS is damaged during the transportation, do not switch on the UPS if any damage is found! Please contact SolarEdge Critical Power support. 3. Check the accessories according to the packing list.
8. Place the incline board to the ground, use the screws unfastened from the last step to fasten the incline board with pallet, use a wrench to raise the four leveling feet. Slowly slide down the cabinet from pallet. Figure 13 Remove UPS from the pallet L30US-IB80, L30US-IB00, L40US UPS...
5.5. Cabinet view Figure 14 Front view/Side view of L30US-IB80, L30US-IB00 and L40US Figure 15 Front view (without door) and Rear View of L30US-IB80 and L30US-IB00 L30US-IB80, L30US-IB00, L40US UPS...
5.6. LCD control panel view Figure 18 LCD Control Panel Table 5 LCD and LED display Fault LED Bypass mode LED Battery mode LED Inverter work LED LCD display 5.7. Electrical Diagrams Figure 19: Remote EPO NO and NC port L30US-IB80, L30US-IB00, L40US UPS...
Figure 20: External maintenance bypass auxiliary contacts Figure 21: Battery breaker position contacts Figure 22: Optional port is for backfeed and tripping the circuit breaker of the batteries L30US-IB80, L30US-IB00, L40US UPS...
(normal) for 125% of the current as listed below.Suggested breakers do not support overload condition. If such support is needed, please contact SolarEdge critical power support. 30kVA: 125A Input Circuit Breaker required. 40kVA: 150A Input Circuit Breaker required L30US-IB80, L30US-IB00, L40US UPS...
Recommended installed screw torque 5.9.2. Table 7 Recommended installed screw torque Position AC input AC output DC input Grounding Screw type Recommended torque (Nm) CAUTION! Protective ground cable: connect each cabinet to ground, following the shortest route possible. WARNING! L30US-IB80, L30US-IB00, L40US UPS...
Page 36
Verify that the UPS is totally isolated from its external power source and all the system breakers are off and power isolators of the UPS are opened. Post any necessary warning signs. Open the rear panel; remove covers of the terminals for easy wiring. L30US-IB80, L30US-IB00, L40US UPS...
All cabinets in the UPS must be grounded properly. CAUTION! The PE/ground and neutral bonding arrangement must be in accordance with local and national codes of practice. L30US-IB80, L30US-IB00, L40US UPS...
The 30K UPS is built-in 4 group battery, the capacity of the battery is 9Ah. Connections for built-in battery Figure 26 Built-in battery connection L30US-IB80, L30US-IB00, L40US UPS...
The user can choose the capacity and the numbers of the batteries according to their desire. The figure below shows external battery connections for long-run units. L30US-IB80, L30US-IB00, L40US UPS...
Ensure correct polarity battery string series connection. i.e., inter-tier and inter-block connections are from (+) to (-) terminals. Do not mix batteries with different capacity or of different brands, and don’t even mix up new and old batteries, either. L30US-IB80, L30US-IB00, L40US UPS...
2. Ensure that the installation site environmental conditions are in accordance with the unit’s working specifications to avoid overheating and excessive moisture. 3. Do not place the unit in a dusty or corrosive environment, or near any flammable objects. 4. This unit is not designed for outdoor use. L30US-IB80, L30US-IB00, L40US UPS...
Connect all the UPS systems needed to be put into parallel system as shown below. CAUTION! Only two UPS systems of this model can be connected in a parallel system with decentralized battery. Common input: Figure 32 Common input connection. L30US-IB80, L30US-IB00, L40US UPS...
Make sure the N, L1, L2, L3 lines are correct, and grounding is well connected. Parallel cable installation 5.11.2. Shielded and double insulated control cables available must be interconnected in a ring configuration between UPS units as shown below. The ring configuration ensures high reliability of the control. L30US-IB80, L30US-IB00, L40US UPS...
2. The outputs of all the UPS systems must be connected to a common output bus. 3. The length and specification of power cables including the bypass input cables and the UPS output cables should be the same. This facilitates load sharing when operating in bypass mode. L30US-IB80, L30US-IB00, L40US UPS...
2. Open the Muser5000 software, click the System button. Figure 35 Muser5000 homepage 3. On Software Parameter Setting, choose COM according to your UPS, choose 9600 for baud rate, choose modbus for protocol, then click Save setting. L30US-IB80, L30US-IB00, L40US UPS...
4. On the main page of Muser5000, click the Append button, Append equipment screen opens. Enter the Password: YDC3350. Figure 37 Muser5000 Append equipment page 5. Fill the UPS name in the Equipment Name field, fill the UPS ID address in the Equipment address field. L30US-IB80, L30US-IB00, L40US UPS...
6. Click the Append button. Connection between the UPS and the computer is now established. CAUTION! When the UPS works on inverter: to set the output voltage and frequency using your PC, you must shut down the inverter first. L30US-IB80, L30US-IB00, L40US UPS...
7. Connect the load, and check whether the output current is balanced. 8. Turn the utility breaker on and off to test that the whole UPS converters system, from utility to battery and restored function, is working properly. L30US-IB80, L30US-IB00, L40US UPS...
Once per 2 seconds Fault LED lit Rectifier Fault Beeps continuously Fault LED lit Inverter Fault Beeps continuously Fault LED lit INV IGBT SHORT Beeps continuously Fault LED lit Inverter relay Short Beeps continuously Fault LED lit L30US-IB80, L30US-IB00, L40US UPS...
Page 55
Fault LED blinking Beeps continuously Fault LED lit Bypass SCR Broken Beeps continuously Fault LED lit Beeps continuously Fault LED lit Bypass SCR short Beeps continuously Fault LED lit BPS Over Temperature Beeps continuously Fault LED lit L30US-IB80, L30US-IB00, L40US UPS...
Once per 2 REC Comm. Error INVERTER LED blinking seconds Once per 2 Mains input lost seconds Once per 2 Set Data Err. FAULT LED blinking seconds INV Par. cable Once per 2 FAULT LED blinking abnormal seconds L30US-IB80, L30US-IB00, L40US UPS...
Page 57
Once per 2 ECU Par. cable abnormal FAULT LED blinking seconds Once per 2 ECU Abnormal FAULT LED blinking seconds Once per second BYPASS LED blinking BPS Phase Reversed Once per second BYPASS LED blinking L30US-IB80, L30US-IB00, L40US UPS...
Support scheduled tasks (timed self-test, power on/off); Historical events and historical data storage functions; Remote UPS monitoring and management can be performed through HTTP, SNMP, SSH, Telnet; Complete equipment event handling (including event recording and notification); L30US-IB80, L30US-IB00, L40US UPS...
Parallel system (integrated parallel / Static Switch Cubicle) Up to 2 Standalone Parallel Frequency Configuration converter s or architecture Bus Synchronization without external box Input THDI (100% Load) <3% PF (100% R Load) >0.99 Frequency tolerance 40-70Hz L30US-IB80, L30US-IB00, L40US UPS...
Page 62
Battery test Manual and automatic programmable by time or voltage Decentralized battery in Support parallel mode Output Online mode 110% 60mins, 125% 10mins, 150% 1mins Overload Battery mode 110% 60mins, 125% 10mins, 150% 1mins THDU Linear load L30US-IB80, L30US-IB00, L40US UPS...
Page 64
Acoustical Noise from <68dB <72dB 1m distance Altitude Up to 3280.84 ft without derating Physical Dimension D×W×H (mm) See Table 2 Back 500mm/ 20’’ Service Right side 1000mm/ 40’’ 500mm/20’’ Access Left side 1000mm/ 40’’ 500mm/20’’ L30US-IB80, L30US-IB00, L40US UPS...
Page 65
Wheels and leveling feet See Table 2 Net weight Standards Approving Agency TUV RHEINLAND CHINA & CCIC Agency Standard Tested UL1778 5th Edition Canadian Approvals CSA 22.2-107.3-14 EMI Approvals FCC Part15 Subpart B Class A/ ANSI C63.4 2014 L30US-IB80, L30US-IB00, L40US UPS...
7. Appendix 2: Troubleshooting Failures in the UPS work can be caused by wrong installation, wiring, or operation. Check these aspects first. If this is not the case, please consult your local SolarEdge agent, providing the product model name and serial number.
Page 67
5. Switch on the power 5. Power breaker on breaker. the rear panel is off. Buzzer beeps UPS is out of order. Consult with your local agent continuously and for repair. LCD indicates 1,3,5,9,15, etc. fault codes L30US-IB80, L30US-IB00, L40US UPS...
Byte length 8bit End bit 1bit Parity check none CAUTION! USB, RS232 and RS485 interface cannot be used at the same time, you can only use one of them at one time. L30US-IB80, L30US-IB00, L40US UPS...
Byte length 8bit End bit 1bit Parity check none CAUTION! USB, RS232 and RS485 interface cannot be used at the same time, you can only use one of them at one time. L30US-IB80, L30US-IB00, L40US UPS...
End bit 1bit Parity check none CAUTION! USB, RS232 and RS485 interface cannot be used at the same time, you can only use one of them at one time. RS485 port pin7 is 12VDC! L30US-IB80, L30US-IB00, L40US UPS...
UVR (Under Voltage Release) functionality can be used for this purpose. The isolation device must be able to carry the UPS input current (common input in case of single source, bypass input in case of dual source). L30US-IB80, L30US-IB00, L40US UPS...
2. Connect the fuse F, the auxiliary contact of relay R, and the coil of C as shown below. 3. Connect C (L1, L2, L3) with UPS bypass input (L1, L2, L3) as shown below. 4. Connect bypass input (N) with mains feeding (N) in the distribution switchgear. Figure 46 Backfeed installation with relay L30US-IB80, L30US-IB00, L40US UPS...