Table 15 - Sensor Min/Max Outputs - York YCAV1039 Installation Operation & Maintenance

Air-cooled screw liquid chillers 50 hz style a 960-1815kw e/v high efficiency and s/p standard efficiency air-cooled screw liquid chillers r-134a
Table of Contents

Advertisement

MICRO PANEL
Sensor Displays
TABLE 15 lists all the sensors attached to the control
board associated with system data keys. The minimum
and maximum values displayed on the micro display
are provided.
If values exceed the limits in the table, a < or > sign
will be display along with the minimum or maximum
value.

TABLE 15 - SENSOR MIN/MAX OUTPUTS

SENSOR
Suction
Pressure
Oil
Pressure
Discharge
Pressure
Flash Tank
Level
Leaving Chilled
Liquid Temp.
Return Chilled
Liquid Temp.
Ambient Air
Temp.
Suction
Temp.
Oil Temp.
Discharge
Temp.
Compressor
Motor Temp.
Remote Temp.
Reset
Remote
Current Limit
Remote
Sound Limit
228
228
SYSTEM DATA KEYS 1-4
TYPE
Transducer
Transducer
Transducer
Capacitance
3Kohm
Thermistor
3Kohm
Thermistor
10Kohm
Thermistor
3Kohm
Thermistor
50Kohm
Thermistor
50Kohm
Thermistor
10Kohm
Thermistor
4-20mA/2-10VDC
0-20mA/0-10VDC
4-20mA/2-10VDC
0-20mA/0-10VDC
4-20mA/2-10VDC
0-20mA/0-10VDC
MIN.
MAX.
0.0 PSIG
125.0 PSIG
0.0 PSIG
275.0 PSIG
0.0 PSIG
275.0 PSIG
0.0%
100 %
-19.1ºF
110.2ºF
-19.1ºF
110.2ºF
-4.6ºF
137.9ºF
-4.1ºF
132.8ºF
40.3ºF
302.6ºF
40.3ºF
302.6ºF
-30.0ºF
302.0ºF
0 %
100 %
0 %
100 %
0 %
100 %