Inverter Configuration - Setup Mode - SolarEdge SE3K-RWB Installation Manual

Table of Contents

Advertisement

46
  Inverter Configuration – Setup Mode
Inverter Configuration – Setup Mode
You can configure the inverter using one of the following:
The internal LCD user
removed.
The external LCD light
is not required. This option of configuration includes a less detailed set of menus.
Configuring the Inverter Using the Internal LCD User Buttons
After inverter installation, an installer may perform basic system configuration.
Configuration is done when the inverter is in Setup mode.
To enter Setup mode:
 1. Turn the inverter ON/OFF switch to OFF (AC remains ON).
WARNING!
If the inverter was operating properly (power was produced by the power
optimizers), the following message is displayed.
 
This message is displayed until the DC voltage is safe (50V). Do not open the
cover until the voltage is safe or until at least five minutes have passed.
 2. Press the Enter button for at least 5 seconds. The following message is displayed:
P l e a s e
P a s s w o r d
* * * * * * * *
 3. Use the three rightmost internal LCD user buttons to type in the following password:
12312312. The following menu is displayed:
C o u n t r y < I t a l y >
L a n g u a g e < E n g >
C o m m u n i c a t i o n
P o w e r C o n t r o l
D i s p l a y
M a i n t e n a n c e
I n f o r m a t i o n
The inverter is now in Setup mode and all its LEDs are lit. The inverter automatically exits
Setup mode if no buttons are pressed for more than 2 minutes.
buttons. When using this option, the inverter cover is
button. When using this option, removing the inverter cover
D C V O L T A G E N O T S A F E
D O N O T D I S C O N N E C T
V D C : 7 2 . 0
e n t e r
Three Phase System MAN-01-00507-4.2