PHYSICAL DATA

Model
Rated Cooling Capacity
Rated Heating Capacity
Refrigerant Charge
Cooling
Rated Power Input
Heating
Cooling
Rated Current
Heating
Type
Compressor
Qty.
Qty.
Fan
Power Input
Type
Cooler
Flow Rate
Type
Connection
Diameter
Water Pressure Drop
L
Dimension
W
H
Shipping
Weight
Operation
Notes
The units are tested in compliance with GB/T 18430.1:
1. Cooling condition: LWT 7℃, water flow rate 0.172m
2. Heating condition: LWT 45℃, water flow rate 0.172m
Cooke Industries - Phone: +64 9 579 2185
SECTION 5 – TECHNICAL DATA
YCAE065X
kW
65.0
kW
66.0
kg
12.5
kW
20.4
kW
20.0
A
38
A
37
-
Scroll
PCS
2
PCS
2
kW
1.8
-
BPHE
m3/h
11.18
-
Thread
-
DN50
kPa
61
mm
1650
mm
760
mm
1700
kg
519
kg
503
Email: sales@cookeindustries.co.nz
YCAE100X
100.0
100.7
8.3+11.5
29.2
31.0
55
58
Scroll
3
2
0.87+1.65
BPHE
17.2
Victaulic
DN65
50
2250
1200
2420
898
864
3
/(h.kW), ambient temperature 35℃;
3
/(h.kW), ambient temperature 7/6℃.
Web: www.cookeindustries.co.nz
YCAE130X
130.0
131.9
11.5×2
39.3
42.8
74
80
Scroll
4
2
1.65*2
BPHE
22.36
Victaulic
DN65
60
2250
1200
2420
1016
982