Creating an RS485 Bus Connection

The RS485 option enables creating a bus of connected inverters, consisting of up to 31
follower inverters and 1 leader inverter. Using this option, inverters are connected to
each other in a bus (chain), via their RS485 connectors. The first and last inverters in the
chain must be terminated as described on page 61.
RS485 wiring specifications:
Cable type: CAT6
Maximum nodes: 32
Maximum distance between first and last devices: 1 km /3300 ft
 
NOTE
If grounded metal conduits are used for routing the communication wires, a
lightning protection device is not required.
The following sections describe how to physically connect the RS485 bus and how to
configure the bus.
To connect the RS485 communication bus:
 1. Release the six Allen screws and carefully remove the Synergy Manager cover
 2. Remove the seal from one of the openings in communication gland #2 and insert
the wire through the opening.
 3. Pull out the 6-pin RS485 terminal block connector, as shown in Figure 32 .
Three Phase Inverters with Synergy Technology
Chapter 6: Setting Up Communication with the Monitoring Platform
    59