"POWER" AND "ABSORPTION" IN CENTRAL HEATING MODE
MAGIS HERCULES PRO
12
Air temperature °C
d.b.
(w.b.)
-20
(-21)
-15
(-16)
-10
(-11)
-7
(-8)
-2
(-3)
2
(1)
7
(6)
10
(9)
15
(14)
20
(19)
MAGIS HERCULES PRO
12
Air temperature °C
d.b.
(w.b.)
-20
(-21)
-15
(-16)
-10
(-11)
-7
(-8)
-2
(-3)
2
(1)
7
(6)
10
(9)
15
(14)
20
(19)
MAGIS HERCULES PRO
12
Air temperature °C
d.b.
(w.b.)
-20
(-21)
-15
(-16)
-10
(-11)
-7
(-8)
-2
(-3)
2
(1)
7
(6)
10
(9)
15
(14)
20
(19)
- Correction factor stated DC = 0.9
- TOL = -25 °C
MAGIS HERCULES PRO 12
Water flow temperature °C
25
Max. output
Max. absorbed
(kW)
(kW)
9.67
3.19
11.01
3.37
12.70
3.55
12.20
3.40
12.04
3.01
11.88
2.62
12.96
2.15
14.16
2.17
16.15
2.20
18.14
2.23
Water flow temperature °C
40
Max. output
Max. absorbed
(kW)
(kW)
8.61
4.10
9.91
4.31
11.41
4.51
11.06
4.63
10.72
3.98
10.39
3.34
11.75
2.91
12.86
2.94
14.71
2.95
16.56
3.02
Water flow temperature °C
55
Max. output
Max. absorbed
(kW)
(kW)
9.95
5.46
9.95
5.30
9.27
5.42
8.80
4.41
11.01
3.83
11.35
4.09
13.02
4.18
14.69
4.28
30
Max. output
Max. absorbed
(kW)
(kW)
9.40
3.42
10.71
3.61
12.35
3.81
11.87
3.65
11.71
3.23
11.55
2.81
12.60
2.31
13.76
2.33
15.70
2.36
17.64
2.39
45
Max. output
Max. absorbed
(kW)
(kW)
8.26
4.52
9.62
4.57
11.05
4.75
10.82
5.15
10.30
4.34
9.78
3.52
11.50
3.23
12.61
3.27
14.47
3.35
16.32
3.42
35
Max. output
Max. absorbed
(kW)
(kW)
8.95
3.84
10.20
4.06
11.76
4.28
11.30
4.10
11.15
3.63
11.00
3.16
12.00
2.59
13.11
2.61
14.95
2.65
16.80
2.69
50
Max. output
Max. absorbed
(kW)
(kW)
9.33
4.79
10.72
4.98
10.38
5.22
9.78
4.88
9.29
3.97
11.26
3.53
11.98
3.68
13.74
3.77
15.50
3.85
65