Electric Connection Cables Features - Immergas MAGIS HERCULES PRO Manual

Floor-standing split heat pump, with 235 litre integrated dhw domestic hot water storage tank
Hide thumbs Also See for MAGIS HERCULES PRO:
Table of Contents

Advertisement

MAGIS HERCULES PRO 4-6-9
17
OUTDOOR UNIT
SUPPLY VOLTAGE
Single-phase with 2 wires
230 Vac
Features of the indoor unit connection. The outdoor unit
power cable (not standard supplied) must be suitable for outdoor
installation and must have at least a flexible polychloroprene
sheath (code IEC:60245 IEC 57 / CENELEC:H05RN-F
Outdoor Unit
AUDAX PRO 4 and
6 V2
AUDAX PRO 9 V2
Features of the connection between outdoor and indoor units.
Use H07RN-F or H05RN-F class cables to power the indoor
unit.
MAGIS HERCULES PRO Power supply (indoor unit)
Power supply
Max./Min.(V)
Mono-phase,
±10%
220-240V, 50Hz

ELECTRIC CONNECTION CABLES FEATURES

PROTECTION
SWITCHES
OUTDOOR
UNIT
COMMUNICATION
CABLE
Field of Tolerable
Nominal Values
Voltage
Hz
V
V
50
220 - 240
198
50
220 - 240
198
Main Power supply
Cable
2.5 mm², 3 wires
INDOOR
UNIT
or FG 16). Indicatively, the appropriate cable section can be
2.5 ~ 4 mm
for AUDAX PROX 4 and 6 V2 and of 4 ~ 6 mm
2
for AUDAX PRO 9 V2 to be checked depending on the specific
installation conditions.
Maximum absorbed
current (MAC) in
normal operation
V
A
264
16
264
22
If the indoor unit is installed in a room with a computer or in-
ternet server, you must use a double shielded FROHH2R class
cable (Aluminium tape/Polyester + Copper braid).
Power supply Cable
Power supply Cable
DHW (Domestic hot
System resistances
water) resistances
6 mm², 3 wires
4 mm², 3 wires
UNIT SUPPLY
SYSTEM INTEGRATING
VOLTAGE
RESISTANCE SUPPLY VOLTAGE
Mono-phase
2 conductors
to 230 Vac
Flow rate of the
MAC✴1.25 +
protective device
Additional Load
required for the
device
A
A
20.0
20
27.5
32
BUS communication cable
between outdoor units and
indoor units
0,75 ~ 1.5 mm², 2 wires
Mono-phase
2 conductors
to 230 Vac
2
39