SINGLE AUDAX PRO V2 MINIMUM INSTALLATION DISTANCES

With the back side of the
unit facing a wall
2000 min.
With the top and front sides
of the unit facing a wall
Place of installation:
The place of installation is very important and must be estab-
lished by the system's designer or by a specifically qualified
person, and must consider the technical requirements, standards
and laws in force.
• The condensing unit must be installed outside the building
only; the indoor unit must be installed inside the building or
outdoors in a partially protected place;
• It is recommended to avoid:
- positioning in basement windows;
- obstacles or barriers that cause recirculation of exhaust air;
- places with aggressive atmospheres;
- limited spaces or anyhow in places where sound levels from
the appliance can be enhanced through reverberations or
resonance;
- positioning in corners where there is an accumulation of
dust, leaves and anything else that can reduce the appliance's
efficiency due to blocked passageways;
With the front side of the
unit facing a wall
300 min.
With the top and back sides
of the unit facing a wall
- prevent exhaust air from the device from coming into the
rooms through doors or windows, thus disturbing people;
• The appliances must:
- be placed on a level surface that is able to withstand its weight;
- be placed on a slab that is hard enough and which does not
transfer any vibrations to the underlying or adjacent rooms;
- installed by means of the vibration-dampening supports sup-
plied with the machine.
• If the unit is installed in zones subject to heavy snow, it will
be necessary to raise the machine by at least the height of the
strongest expected snowfall or, alternatively, use wall-support
brackets (optional).
With three sides of the unit
facing a wall
300 min.
600 min.
With the front and back
sides of the unit facing a
wall
11