Immergas MAGIS HERCULES PRO Manual

Immergas MAGIS HERCULES PRO Manual

Floor-standing split heat pump, with 235 litre integrated dhw domestic hot water storage tank
Hide thumbs Also See for MAGIS HERCULES PRO:
Table of Contents

Advertisement

Quick Links

HEAT PUMPS
MAGIS HERCULES PRO
Floor-standing split Heat
Pump, with 235 litre integrated
DHW (Domestic hot water)
storage tank

Advertisement

Table of Contents
loading

Summary of Contents for Immergas MAGIS HERCULES PRO

  • Page 1 HEAT PUMPS MAGIS HERCULES PRO Floor-standing split Heat Pump, with 235 litre integrated DHW (Domestic hot water) storage tank...
  • Page 3: Table Of Contents

    43 HYDRAULIC DIAGRAM: MAGIS HERCULES PRO WITH 1 DIRECT ZONE (HOT / COLD WITH DEHUMIDIFICATION) + PHOTOVOLTAIC........................90 44 HYDRAULIC DIAGRAM: MAGIS HERCULES PRO WITH 3 ZONES (1 DIRECT and 2 MIXED) + SOLAR THERMAL SYSTEMS ..............................92 45 OPTIONAL FOR MAGIS HERCULES PRO .........................95...
  • Page 4 MAGIS HERCULES PRO MAGIS HERCULES PRO is the range of split inverter air-water heat pumps with outdoor condensing unit and indoor floor-standing unit, including a 235 litre domestic hot water storage tank (single product, with single code for indoor unit + condensing unit).
  • Page 5: Magis Hercules Pro 4 - 6 - 9 Features (Single-Phase)

    MAGIS HERCULES PRO 4-6-9 MAGIS HERCULES PRO 4 - 6 - 9 FEATURES (SINGLE-PHASE) Split inverter reversible single-phase air/water heat pumps, BOOST function for DHW (Domestic hot water) - makes it • composed of an outdoor condensing unit and an indoor floor possible to use all the power available (HP + electrical resist- standing unit;...
  • Page 6: Magis Hercules Pro 12- 14 - 16 Features (Single-Phase Or Three-Phase)

    MAGIS HERCULES PRO 12-14-16 2 MAGIS HERCULES PRO 12- 14 - 16 FEATURES (SINGLE-PHASE OR THREE-PHASE) Split inverter reversible single-phase or three-phase air/water heat BOOST function for DHW (Domestic hot water) - makes it • pumps, composed of an outdoor condensing unit and an indoor possible to use all the power available (HP + electrical resist- floor standing unit;...
  • Page 7: Magis Hercules Pro Dimensions And Connections (Indoor Unit)

    MAGIS HERCULES PRO MAGIS HERCULES PRO DIMENSIONS AND CONNECTIONS (INDOOR UNIT) Model Height mm Width mm Depth mm MAGIS HERCULES PRO 1970 Key: V1 - 3 zone electrical connections V2 - Additional resistance power supply electrical connections V3 - Power supply cable electrical connections...
  • Page 8: Separation Into Two Parts (With Dedicated Frame)

    MAGIS HERCULES PRO SEPARATION INTO TWO PARTS (WITH DEDICATED FRAME) To simplify the work of the installers, this heat pump only system into two parts that can be disassembled from each other with was designed with particular attention to the how the product appropriate mechanical and electrical set-ups.
  • Page 9: Audax Pro V2 Dimensions And Connections (Condensing Unit)

    MAGIS HERCULES PRO 4-6-9 AUDAX PRO V2 DIMENSIONS AND CONNECTIONS (CONDENSING UNIT) AUDAX PRO 4 / 6 V2 54.1 Height = 638 mm Width = 880 mm Depth = 361 mm Condensate drain = Ø 20 mm Model LP (Cooling liquid)
  • Page 10: Ue Audax Pro V2 Dimensions And Connections (Condensing Unit)

    MAGIS HERCULES PRO 12-14-16 UE AUDAX PRO V2 DIMENSIONS AND CONNECTIONS (CONDENSING UNIT) Gas side pipe Liquid side pipe Height = 1420 mm Width = 940 mm Depth = 384 mm Condensate drain = Ø 20 mm R410A Model LP (Cooling liquid)
  • Page 11: Single Audax Pro V2 Minimum Installation Distances

    MAGIS HERCULES PRO SINGLE AUDAX PRO V2 MINIMUM INSTALLATION DISTANCES With the back side of the With the front side of the With three sides of the unit unit facing a wall unit facing a wall facing a wall 300 min.
  • Page 12: Audax Pro V2 Minimum Installation Distances (Several Appliances)

    MAGIS HERCULES PRO 8 AUDAX PRO V2 MINIMUM INSTALLATION DISTANCES (SEVERAL APPLIANCES) The front side of the unit facing a wall With three sides of the units facing a wall 300 min. 600 min. 600 min. 600 min. With the top and back sides 300 min.
  • Page 13: Drain Holes And Condensate Drain

    MAGIS HERCULES PRO DRAIN HOLES AND CONDENSATE DRAIN If the produced condensate is drained through the drain pipe, connect the standard supplied drain fitting (1) in one of the drainage holes on the bottom of the appliance and close the...
  • Page 14: Cooling Circuit With R32 Functioning Limits

    MAGIS HERCULES PRO 4-6-9 COOLING CIRCUIT WITH R32 FUNCTIONING LIMITS Central heating System KEY: TM - Flow water temperature (°C) TE - Outdoor air temperature (°C) Domestic hot water TB (°C) KEY: TB - Storage tank temperature probe (°C) TE - Outdoor air temperature (°C) A = Work area covered by D.H.W.
  • Page 15: Cooling Circuit With R410A Functioning Limits

    MAGIS HERCULES PRO 12-14-16 COOLING CIRCUIT WITH R410A FUNCTIONING LIMITS Central heating System TM (°C) KEY: TM - Flow water temperature (°C) TE - Outdoor air temperature (°C) TE (°C) Domestic hot water TB (°C) KEY: TB - Storage tank temperature probe (°C) TE - Outdoor air temperature (°C)
  • Page 16: 12 3 Kw System Integrative Resistance Kit, 2 Kits Can Be Installed

    MAGIS HERCULES PRO 3 kW SYSTEM INTEGRATIVE RESISTANCE KIT (CODE 3.030889) IT IS POSSIBLE TO INSTALL 2 KITS Resistance Resistance Resistance Resistance KEY: 1 - 3 kW Electric resistance TECHNICAL DATA (for each resistance)* 2 - O.R. seal 3 - Cover...
  • Page 17 MAGIS HERCULES PRO 12.1 ELECTRICAL CONNECTION WITH DOUBLE 3 kW SYSTEM INTEGRATIVE RESISTANCE KIT (CODE 3.030889) Colour code key: KEY: - Blue 1 - Main panel - Brown 2 - Optional kit panel - Green/Yellow 3 - External power supply 230 Vac...
  • Page 18: 13 2.3 Kw Dhw (Domestic Hot Water) Integrative Resistance Kit, 2 Kits Can Be Installed (In Addition To The Standard One)

    MAGIS HERCULES PRO 13 2.3 kW DHW (DOMESTIC HOT WATER) INTEGRATIVE RESISTANCE KIT (CODE 3.030862) IT IS POSSIBLE TO INSTALL 2 KITS (IN ADDITION TO THE STANDARD ONE) Resistance Resistance KEY (kit composition): TECHNICAL DATA (for each resistance)* 5 - Integrative 2,3 kW resistance 6 - O.R.
  • Page 19 MAGIS HERCULES PRO 13.1 ELECTRICAL CONNECTION WITH DOUBLE 2,3 kW DHW (DOMESTIC HOT WATER) INTEGRATIVE RESISTANCE KIT (CODE 3.030862) KEY: 1 - Main panel Colour code key: 2 - Optional kit panel - Blue 3 - External power supply 230 Vac...
  • Page 20: Indoor Unit Main Components

    MAGIS HERCULES PRO INDOOR UNIT MAIN COMPONENTS 20 - Liquid phase detection probe KEY: - Elbow fitting 21 - Sacrificial anode - Storage tank draining valve 22 - System shut-off cock - Sacrificial anode 23 - System shut-off cock - Solar panels probe (optional)
  • Page 21: Magis Hercules Pro Hydraulic Diagram

    MAGIS HERCULES PRO MAGIS HERCULES PRO HYDRAULIC DIAGRAM KEY: - 16 litre DHW (Domestic hot water) 13 - Y-Filter that can be inspected expansion vessel 14 - One-way valve direct zone 1 - 235 litre Stainless steel DHW (Domestic 15 - Direct zone 1 pump / circulator...
  • Page 22 MAGIS HERCULES PRO 15.1 MAGIS HERCULES PRO HYDRAULIC DIAGRAM WITH OPTIONAL KIT KEY: 15 - Y-Filter that can be inspected - 16 litre DHW (Domestic hot water) 16 - Direct zone 1 pump / circulator expansion vessel 17 - Polyphosphate dispenser kit (optional)
  • Page 23 MAGIS HERCULES PRO 15.2 AUDAX PRO V2 (EXTERNAL CONDENSING UNIT) HYDRAULIC DIAGRAM KEY: - Compressor - Compressor temperature - Compressor outlet temperature - Silencer - High pressure switch - 4-way valve - Temperature of fluid in finned coil - External probe/installation room temperature...
  • Page 24: Electronic Management Functions Magis Hercules Pro

    (to be purchased separately with special optional Kit). In this case MAGIS HERCULES PRO can be connected to The integrated electronics also manage the screed heating func- remote zone panels (code 3.030863) via Bus connections (up...
  • Page 25 MAGIS HERCULES PRO 16.1 DISPLAY AND PROGRAMMING MENU KEY: - Display - “DHW (Domestic hot water)” menu button - “Zones” button - Functioning mode button - ON/OFF Button - Zones area (number and information of zone in use) - Operating mode...
  • Page 26 MAGIS HERCULES PRO 16.2 USER PROGRAMMING MENU “DHW (Domestic hot water)” Menu. Press the “DHW (Domestic hot water)” button to access a list of variables that enable you to customise use of the DHW (Domestic hot water). Hereunder is a list of available menus:...
  • Page 27 Disabling of request to the dehumidifier, according to the daily time slot. NO/Yes Hourly disabling start Time of dehumidification request disabling phase start. 0-23 Hourly disabling end Time of dehumidification request disabling phase end. 0-23 * 55 °C refers to MAGIS HERCULES PRO 12-14-16, MAGIS HERCULES PRO 12 T-14 T-16 T...
  • Page 28 MAGIS HERCULES PRO ZONES/GENERAL INFORMATION Menu item Description Range Default Outside temperature External temper. detected by the external probe (optional). System flow set Flow temperature set on the system. Zone 1 flow set Flow temperature set on zone 1. Request present on zone 1...
  • Page 29 MAGIS HERCULES PRO MENU/CLOCK AND PROGRAMS Menu item Description Range Default Zone 1 Program Zone 1 time scheduling. Zone 1: Monday CAL1, CAL2, CAL3,CAL4 CAL1 Zone 1: Tuesday CAL1, CAL2, CAL3,CAL4 CAL1 Zone 1: Wednesday CAL1, CAL2, CAL3,CAL4 CAL1 Zone 1: Thursday...
  • Page 30 MAGIS HERCULES PRO MENU/CLOCK AND PROGRAMS Menu item Description Range Default Recirculation Program Recirculation operation time programming. CAL1, CAL2, Recirculation - Monday CAL1 CAL3,CAL4 CAL1, CAL2, Recirculation - Tuesday CAL1 CAL3,CAL4 CAL1, CAL2, Recirculation- Wednesday CAL1 CAL3,CAL4 CAL1, CAL2, Recirculation - Thursday...
  • Page 31 MAGIS HERCULES PRO MENU/USER/SCREED HEATER Menu item Description Range Default Stay time Defines the time spent at minimum operating temperature during 1 - 7 days at minimum set the active function. Rise gradient Defines the ascent gradient of the temperature.
  • Page 32 MAGIS HERCULES PRO 16.3 MAINTENANCE TECHNICIAN PROGRAMMING MENU DHW (DOMESTIC HOT WATER) Menu item Description Anti-legionella Manages the anti-legionella function. Configuration DHW (Domestic hot water) configuration parameters. DHW (DOMESTIC HOT WATER)/ANTI-LEGIONELLA Menu item Description Range Default Anti-legionella Establishes the time of activation of the anti-legionella function.
  • Page 33 With the external probe present it defines at what maximum external tem- -5 - +45 °C temperature perature the system must operate at the minimum flow temperature. * 55 °C refers to MAGIS HERCULES PRO 12-14-16, MAGIS HERCULES PRO 12 T-14 T-16 T...
  • Page 34 MAGIS HERCULES PRO ZONES/ZONE 1/CONFIGURATION/COOL. THERMOREG. (Similar settings for zone 2 and 3 if present) Menu item Description Range Default Without the external probe it defines the maximum flow that can be set by the user. With the external probe present it defines the maximum flow Maximum flow set 5 ÷...
  • Page 35 MAGIS HERCULES PRO To access the “assistance menu”, press the “MENU” button. You can exit the assistance menu by entering the appropriate Access the submenu “General settings” and select “Access lev- access code under the “Access level” item and selecting the el”.
  • Page 36 MAGIS HERCULES PRO MENU/ASSISTANCE/HEAT PUMP Menu item Description Powers See description below. Timers See description below. Pump See description below. MENU/ASSISTANCE/HEAT PUMP/POWERS Menu item Description Range Default Setting of the connected outdoor condensing unit. No / 4 / 6 / 9 / 12 / PdC Model Do not use the item No.
  • Page 37 MAGIS HERCULES PRO MENU/ASSISTANCE/INTEGRATION Menu item Description Range Default Domestic hot water It is the maximum time of operation in DHW in case of simultaneous re- 0 - 540’ 60’ priority time quest. Central heating priority It is the maximum time of operation in central heating in case of simulta- 0 - 540’...
  • Page 38 MAGIS HERCULES PRO operating modes available both with external probe and without By setting the parameters in the “Temperature control” menu, in relation to the different zones (direct or mixed). you can adjust how the system operates. The following graphs show the default settings in the various...
  • Page 39: Electric Connection Cables Features

    FROHH2R class Use H07RN-F or H05RN-F class cables to power the indoor cable (Aluminium tape/Polyester + Copper braid). unit. MAGIS HERCULES PRO Power supply (indoor unit) BUS communication cable between outdoor units and Power supply Cable...
  • Page 40 Use H07RN-F or H05RN-F class cables to power the indoor ternet server, you must use a double shielded FROHH2R class unit. cable (Aluminium tape/Polyester + Copper braid). MAGIS HERCULES PRO Power supply (indoor unit) BUS communication cable between outdoor units and Power supply Cable...
  • Page 41 MAGIS HERCULES PRO 12 T-14 T-16 T 17.2 ELECTRIC CONNECTION CABLES FEATURES OUTDOOR UNIT SUPPLY VOLTAGE Three-phase with 4 wires PROTECTION SWITCHES 380 - 415 V~ OUTDOOR UNIT INDOOR UNIT UNIT SUPPLY SYSTEM INTEGRATING VOLTAGE RESISTANCE SUPPLY VOLTAGE Mono-phase Mono-phase...
  • Page 42: Outdoor Unit Terminal Block Electrical Connections

    MAGIS HERCULES PRO 4-6-9 OUTDOOR UNIT TERMINAL BLOCK ELECTRICAL CONNECTIONS With use of the mono-phase safety switch (ELB). KEY: Depending on the model, the actual appear- - Safety Switch ance of the unit may differ from the one shown MCCB - Circuit breaker switch in the figure.
  • Page 43 MAGIS HERCULES PRO 12-14-16 18.1 OUTDOOR UNIT TERMINAL BLOCK ELECTRICAL CONNECTIONS Single-phase Depending on the model, the actual appear- ance of the unit may differ from the one shown in the figure. 1(L) 2(N) NOT USED Cable clamping clamp Power supply...
  • Page 44: Electrical Connections To The Control Panel (Top Part)

    MAGIS HERCULES PRO ELECTRICAL CONNECTIONS TO THE CONTROL PANEL (TOP PART)
  • Page 45 MAGIS HERCULES PRO 19.1 ELECTRICAL CONNECTIONS IN THE MAIN PANEL (MIDDLE PART) NOTES: Eliminate the X40-1 jumper before connecting the If Zone 2 and 3 remote panel is also connected, make sure there S20-1 room thermostat. When the Zone 1 remote panel is is a jumper between clamps 41 and 40-2 and 40-3.
  • Page 46 MAGIS HERCULES PRO 19.3 ELECTRICAL CONNECTIONS IN SECONDARY PANEL (BOTTOM PART)
  • Page 47: Temperature Control (Optional)

    MAGIS HERCULES PRO TEMPERATURE CONTROL (OPTIONAL) 20.1 ZONE REMOTE PANEL It is an electronic device equipped with a back-lit display to control and adjust the room's temperature and humidity. Con- nection to the terminal block is made via two BUS cables and two power supply cables.
  • Page 48 MAGIS HERCULES PRO 20.5 EXTERNAL PROBE It is a device for adjusting the heat provided by the system ac- cording to the outdoor temperature change. The external probe always acts when it is connected, inde- pendently from the presence and type of temperature control.
  • Page 49: Installing The Chiller Lines With R32 Coolant Gas

    MAGIS HERCULES PRO 4-6-9 INSTALLING THE CHILLER LINES WITH R32 COOLANT GAS The MAGIS HERCULES PRO 4-6-9 cooling circuit uses the AUDAX PRO 4 and 6 V2 AUDAX PRO 9 V2 refrigerant R32, therefore, it is necessary to take some measures for the proper operation of the machine: ≤...
  • Page 50 MAGIS HERCULES PRO 4-6-9 Selecting chiller line insulation. NOTE: The insulation cannot be interrupted and for this reason, - The gas and liquid chiller lines must be insulated with materials its junctions must be sealed with adhesive to prevent moisture selected based on their respective diameters.
  • Page 51: Installing The Chiller Lines With R410A Coolant Gas

    MAGIS HERCULES PRO 12-14-16 INSTALLING THE CHILLER LINES WITH R410A COOLANT GAS The Single-phase and Three-phase MAGIS HERCULES PRO UE AUDAX PRO 12/14/16 V2 - 12/14/16 V2 T 12-14-16 cooling circuit uses the refrigerant R410A, therefore, it is necessary to take some measures for the proper operation ≤...
  • Page 52 MAGIS HERCULES PRO 12-14-16 Selecting chiller line insulation. NOTE: The insulation cannot be interrupted and for this reason, - The gas and liquid chiller lines must be insulated with materials its junctions must be sealed with adhesive to prevent moisture selected based on their respective diameters.
  • Page 53: Product Fiche (Regulation 811/2013) Magis Hercules Pro 4

    MAGIS HERCULES PRO 4-6-9 PRODUCT FICHE (REGULATION 811/2013) MAGIS HERCULES PRO 4 MAGIS HERCULES PRO 4 MAGIS HERCULES PRO 4 Low temperature (30/35) Colder zones Average zones Hotter zones Parameter Value Annual energy consumption for the central heating mode (Q...
  • Page 54: Magis Hercules Pro 4

    MAGIS HERCULES PRO 4-6-9 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE MAGIS HERCULES PRO 4 MAGIS HERCULES Water flow temperature °C PRO 4 Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (w.b.)
  • Page 55 MAGIS HERCULES PRO 4-6-9 24.1 “POWER” AND “ABSORPTION” IN COOLING MODE MAGIS HERCULES PRO 4 MAGIS HERCULES Water flow temperature °C PRO 4 Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (kW)
  • Page 56: Product Fiche (Regulation 811/2013) Magis Hercules Pro 6

    MAGIS HERCULES PRO 4-6-9 PRODUCT FICHE (REGULATION 811/2013) MAGIS HERCULES PRO 6 MAGIS HERCULES PRO 6 MAGIS HERCULES PRO 6 Low temperature (30/35) Colder zones Average zones Hotter zones Parameter Value Annual energy consumption for the central heating mode (Q...
  • Page 57: Magis Hercules Pro 6

    MAGIS HERCULES PRO 4-6-9 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE MAGIS HERCULES PRO 6 MAGIS HERCULES Water flow temperature °C PRO 6 Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (w.b.)
  • Page 58 MAGIS HERCULES PRO 4-6-9 26.1 “POWER” AND “ABSORPTION” IN COOLING MODE MAGIS HERCULES PRO 6 MAGIS HERCULES Water flow temperature °C PRO 6 Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (kW)
  • Page 59: Product Fiche (Regulation 811/2013) Magis Hercules Pro 9

    MAGIS HERCULES PRO 4-6-9 PRODUCT FICHE (REGULATION 811/2013) MAGIS HERCULES PRO 9 MAGIS HERCULES PRO 9 MAGIS HERCULES PRO 9 Low temperature (30/35) Colder zones Average zones Hotter zones Parameter Value Annual energy consumption for the central heating mode (Q...
  • Page 60: Magis Hercules Pro 9

    MAGIS HERCULES PRO 4-6-9 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE MAGIS HERCULES PRO 9 MAGIS HERCULES Water flow temperature °C PRO 9 Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (w.b.)
  • Page 61 MAGIS HERCULES PRO 4-6-9 28.1 “POWER” AND “ABSORPTION” IN COOLING MODE MAGIS HERCULES PRO 9 MAGIS HERCULES Water flow temperature °C PRO 9 Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (kW)
  • Page 62: Technical Data Magis Hercules Pro 4 - 6 - 9

    MAGIS HERCULES PRO 4-6-9 TECHNICAL DATA MAGIS HERCULES PRO 4 - 6 - 9 Central heating circuit Power in CH mode with water set at 35 °C 4.40 6.00 9.00 Power in CH mode with water set at 45 °C 4.20...
  • Page 63: Product Fiche (Regulation 811/2013) Magis Hercules Pro 12

    MAGIS HERCULES PRO 12-14-16 PRODUCT FICHE (REGULATION 811/2013) MAGIS HERCULES PRO 12 MAGIS HERCULES PRO 12 MAGIS HERCULES PRO 12 Low temperature (30/35) Colder zones Average zones Hotter zones Parameter Value Annual energy consumption for the central heating mode (Q...
  • Page 64 MAGIS HERCULES PRO 12 T-14 T-16 T 30.1 PRODUCT FICHE (REGULATION 811/2013) MAGIS HERCULES PRO 12 T MAGIS HERCULES PRO 12T MAGIS HERCULES PRO 12T Low temperature (30/35) Colder zones Average zones Hotter zones Parameter Value Annual energy consumption for the central heating mode (Q...
  • Page 65: Magis Hercules Pro 12

    MAGIS HERCULES PRO 12-14-16 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE MAGIS HERCULES PRO 12 MAGIS HERCULES PRO Water flow temperature °C Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (w.b.) (kW)
  • Page 66 MAGIS HERCULES PRO 12-14-16 31.1 “POWER” AND “ABSORPTION” IN COOLING MODE MAGIS HERCULES PRO 12 MAGIS HERCULES PRO Water flow temperature °C Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (kW) (kW)
  • Page 67: Product Fiche (Regulation 811/2013) Magis Hercules Pro 14

    MAGIS HERCULES PRO 12-14-16 PRODUCT FICHE (REGULATION 811/2013) MAGIS HERCULES PRO 14 MAGIS HERCULES PRO 14 MAGIS HERCULES PRO 14 Low temperature (30/35) Colder zones Average zones Hotter zones Parameter Value Annual energy consumption for the central heating mode (Q...
  • Page 68 MAGIS HERCULES PRO 12 T-14 T-16 T 32.1 PRODUCT FICHE (REGULATION 811/2013) MAGIS HERCULES PRO 14 T MAGIS HERCULES PRO 14T MAGIS HERCULES PRO 14T Low temperature (30/35) Colder zones Average zones Hotter zones Parameter Value Annual energy consumption for the central heating mode (Q...
  • Page 69: Magis Hercules Pro 14

    MAGIS HERCULES PRO 12-14-16 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE MAGIS HERCULES PRO 14 MAGIS HERCULES PRO Water flow temperature °C Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (w.b.) (kW)
  • Page 70 MAGIS HERCULES PRO 12-14-16 33.1 “POWER” AND “ABSORPTION” IN COOLING MODE MAGIS HERCULES PRO 14 MAGIS HERCULES PRO Water flow temperature °C Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (kW) (kW)
  • Page 71: Product Fiche (Regulation 811/2013) Magis Hercules Pro 16

    MAGIS HERCULES PRO 12-14-16 PRODUCT FICHE (REGULATION 811/2013) MAGIS HERCULES PRO 16 MAGIS HERCULES PRO 16 MAGIS HERCULES PRO 16 Low temperature (30/35) Colder zones Average zones Hotter zones Parameter Value Annual energy consumption for the central heating mode (Q...
  • Page 72 MAGIS HERCULES PRO 12 T-14 T-16 T 34.1 PRODUCT FICHE (REGULATION 811/2013) MAGIS HERCULES PRO 16 T MAGIS HERCULES PRO 16T MAGIS HERCULES PRO 16T Low temperature (30/35) Colder zones Average zones Hotter zones Parameter Value Annual energy consumption for the central heating mode (Q...
  • Page 73: Magis Hercules Pro 16

    MAGIS HERCULES PRO 12-14-16 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE MAGIS HERCULES PRO 16 MAGIS HERCULES PRO Water flow temperature °C Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (w.b.) (kW)
  • Page 74 MAGIS HERCULES PRO 12-14-16 35.1 “POWER” AND “ABSORPTION” IN COOLING MODE MAGIS HERCULES PRO 16 MAGIS HERCULES PRO Water flow temperature °C Air temperature °C Max. output Max. absorbed Max. output Max. absorbed Max. output Max. absorbed d.b. (kW) (kW)
  • Page 75: Technical Data Magis Hercules Pro 12 - 14 - 16

    MAGIS HERCULES PRO 12-14-16 TECHNICAL DATA MAGIS HERCULES PRO 12 - 14 - 16 (SINGLE-PHASE) Central heating circuit Power in CH mode with water set at 35 °C 12.00 14.00 16.00 Power in CH mode with water set at 45 °C 11.50...
  • Page 76 MAGIS HERCULES PRO 12 T-14 T-16 T 36.1 TECHNICAL DATA MAGIS HERCULES PRO 12 - 14 - 16 T (THREE-PHASE) 12 T 14 T 16 T Central heating circuit Power in CH mode with water set at 35 °C 12.00 14.00...
  • Page 77: Chart Of The Head Flow Rate Available To The Direct Zone (Standard)

    MAGIS HERCULES PRO 4-6-9 37 CHART OF THE HEAD FLOW RATE AVAILABLE TO THE DIRECT ZONE (STANDARD) MAGIS HERCULES PRO 4-6-9 is supplied as standard with a PRO is standard supplied with an electronic low consumption primary circulator, modulating with low electrical consumption,...
  • Page 78 Power absorbed by the system pump (dotted area) 37.1 ZONE 1 (DIRECT) FLOW CIRCULATOR PUMP SETTINGS AND CONFIGURATIONS MAGIS HERCULES PRO 4-6-9 is equipped with 2 circulator - Proportional head (ΔP-V) This allows the pressure level (head) to be proportionally reduced pumps with speed regulator.
  • Page 79: Additional Mixed Zones For Magis Hercules Pro 4 - 6 - 9

    MAGIS HERCULES PRO 4-6-9 ADDITIONAL MIXED ZONES FOR MAGIS HERCULES PRO 4 - 6 - 9 38.1 SECOND ADDITIONAL MIXED ZONE KIT CODE 3.030855 38.2 THIRD ADDITIONAL MIXED ZONE CODE 3.030856...
  • Page 80 MAGIS HERCULES PRO 4-6-9 38.3 CHART OF THE HEAD FLOW RATE AVAILABLE TO THE MIXED ZONE (OPTIONAL) MAGIS HERCULES PRO 4-6-9 is designed for the construc- The graph below is for determining the available head for the tion of mixed systems with differentiated temperature (e.g.; a individual zones.
  • Page 81 Power absorbed by the system pump (dotted area) 38.4 MIXED ZONE (OPTIONAL) CIRCULATOR PUMP SETTINGS AND CONFIGURATIONS MAGIS HERCULES PRO 4-6-9 is standard equipped with 1 - Proportional head (ΔP-V) This allows the pressure level (head) to be proportionally reduced direct circulator pump for zone 1.
  • Page 82: Chart Of The Head Flow Rate Available To The Direct Zone (Standard)

    MAGIS HERCULES PRO 12-14-16 39 CHART OF THE HEAD FLOW RATE AVAILABLE TO THE DIRECT ZONE (STANDARD) MAGIS HERCULES PRO 12-14-16 is supplied as standard with PRO is standard supplied with an electronic low consumption a primary circulator, modulating with low electrical consump-...
  • Page 83 Head available at speed Min ÷ Max Power absorbed by the system pump (dotted area) 39.1 ZONE 1 FLOW CIRCULATOR PUMP SETTINGS AND CONFIGURATIONS MAGIS HERCULES PRO 12-14-16 is equipped with 2 circu- - Proportional head (ΔP-V) lator pumps with speed regulator.
  • Page 84: Additional Mixed Zones For Magis Hercules Pro 12-14-16

    MAGIS HERCULES PRO 12-14-16 ADDITIONAL MIXED ZONES FOR MAGIS HERCULES PRO 12-14-16 40.1 SECOND ADDITIONAL MIXED ZONE KIT CODE 3.030943 40.2 THIRD ADDITIONAL MIXED ZONE CODE 3.030944...
  • Page 85 MAGIS HERCULES PRO 12-14-16 40.3 CHART OF THE HEAD FLOW RATE AVAILABLE TO THE MIXED ZONE (OPTIONAL) MAGIS HERCULES PRO 12-14-16 is designed for the con- The graph below is for determining the available head for the struction of mixed systems with differentiated temperature (e.g.;...
  • Page 86 Head available at speed Min ÷ Max Power absorbed by the system pump (dotted area) 40.4 MIXED ZONE (OPTIONAL) CIRCULATOR PUMP SETTINGS AND CONFIGURATIONS MAGIS HERCULES PRO 12-14-16 is standard equipped with - Proportional head (ΔP-V) This allows the pressure level (head) to be proportionally reduced 1 direct circulator pump for zone 1.
  • Page 87: Dehumidifier

    MAGIS HERCULES PRO DEHUMIDIFIER Designed to be coupled to cooling plants with radiant panels, the dehumidifier allows to keep the percentage of relative humidity in the room within the comfort values, preventing the possible formation of condensate on the walls.
  • Page 88 MAGIS HERCULES PRO 41.2 TECHNICAL DATA Coolant R134a Humidity removed in neutral air condition litres/24h 20.1 Cooling capacity 1250 Nominal water input Head losses Water supply temperature operating field °C 15 ÷ 45 work humidity field 40 ÷ 90 Air flow rate...
  • Page 89: Introduction With Commentary To The Diagrams: Main Applications

    - CH phase active: The Remote zone panel placed in the room activates consent in the winter phase; in this diagram MAGIS HERCULES PRO is integrated through the 3 kW electric resistance(s) (optional), to be inserted in the hydronic module/ inertial storage tank.
  • Page 90: Hydraulic Diagram: Magis Hercules Pro With 1 Direct Zone (Hot / Cold With Dehumidification) + Photovoltaic

    MAGIS HERCULES PRO HYDRAULIC DIAGRAM: MAGIS HERCULES PRO WITH 1 DIRECT ZONE (HOT / COLD WITH DEHUMIDIFICATION) + PHOTOVOLTAIC Hot / Cold Water-DHW network KEY: 1 - Outdoor unit (inclusive of external probe) 2 - Indoor unit 3 - Zone remote panel...
  • Page 91 MAGIS HERCULES PRO 43.1 WIRING DIAGRAM: MAGIS HERCULES PRO WITH 1 DIRECT ZONE (HOT / COLD WITH DEHUMIDIFICATION) + PHOTOVOLTAIC DISPLAY CONTROL PANEL TERMINAL BLOCK BUS communication connection Indoor unit with Outdoor unit. AWG 20/22 type shielded cable KEY: Outdoor unit...
  • Page 92: Hydraulic Diagram: Magis Hercules Pro With 3 Zones (1 Direct And 2 Mixed) + Solar Thermal Systems

    MAGIS HERCULES PRO HYDRAULIC DIAGRAM: MAGIS HERCULES PRO WITH 3 ZONES (1 DIRECT AND 2 MIXED) + SOLAR THERMAL SYSTEMS Hot / Cold Water-DHW network KEY: - Outdoor unit (inclusive of external probe) - Indoor unit - Flat solar collectors...
  • Page 93 MAGIS HERCULES PRO 44.1 WIRING DIAGRAM: MAGIS HERCULES PRO WITH 3 ZONES (1 DIRECT AND 2 MIXED) + SOLAR THERMAL SYSTEMS DISPLAY CONTROL PANEL TERMINAL BLOCK BUS communication connection Indoor unit HYDRO 3-4 TERMINAL BLOCK with Outdoor unit. AWG 20/22 type shielded...
  • Page 94 MAGIS HERCULES PRO 44.2 WIRING DIAGRAM: MAGIS HERCULES PRO WITH 3 ZONES (1 DIRECT AND 2 MIXED) + SOLAR THERMAL SYSTEMS SECONDARY PANEL TERMINAL BLOCK (LOWER PART) SOLAR CONTROL UNIT TERMINAL BLOCK B12 B11 Requested by HYDRO FS KEY: B3-3 - Zone 3 flow probe...
  • Page 95: Optional For Magis Hercules Pro

    DOMINUS Interface board kit - for remote control via App 3.026273 Code SPECIFIC OPTIONALS FOR MAGIS HERCULES PRO MODELS 4-6-9 Additional mixed zone 2 kit - including the low consumption circulator pump and mixing valve. 3.030855 It can be installed inside the indoor unit casing Additional mixed zone 3 kit - including the low consumption circulator pump and mixing valve, expansion.It can...
  • Page 96 MAGIS HERCULES PRO OTHER OPTIONALS FOR ALL MODELS Code Safety marker thermostat kit - for direct zone 3.019229 Condensate antifreeze heating cable kit - for outdoor condensing unit 4-6 kW 3.027385 Wall installation brackets kit for outdoor condensing unit 3.022154 Double electronic anode kit - protects the storage tank from eddy currents 3.025003...
  • Page 97 DECLARATION OF CONFORMITY OF THE PRODUCT To download the updated declaration of conformity of the product, please refer to the IMMERGAS website: www.immergas.com...
  • Page 98: Solar Thermal System Coupling Kit

    • Hydraulic fittings to complete the installation. The kit is sent partly already assembled and wired, ready to be fixed inside the MAGIS HERCULES PRO. NOTE: To complete the solar thermal circuit it is necessary The kit also contains the drain fitting, the pipe and can for glycol to provide one or two exclusively flat solar collectors (e.s.
  • Page 99 MAGIS HERCULES PRO 46.1 ASSEMBLY OF SOLAR THERMAL SYSTEM COUPLING KIT...
  • Page 100 MAGIS HERCULES PRO 46.2 OPTIONAL FOR COMPLETING THE SOLAR SYSTEMS Code Solar panels CP4 XL flat-plane manifold characterised by 4 connections with a useful surface of 2.31 m 3.022664 CP4 M flat-plane manifold characterised by 4 connections with a useful surface of 1.84 m 3.022876...
  • Page 101 During the useful life of the products, performance is affected by external factors, e.g. the hardness of the DHW, atmospheric agents, deposits in the system and so on. The declared data refer to new products that are correctly installed and used in observance of the Standards in force. N.B.: correct periodic maintenance is highly recommended.
  • Page 102 Immergas TOOLBOX The App designed by Immergas for professionals Disponibile su Disponibile su Disponibile su To request further specific details, sector Professionals can also use the following e-mail address: consulenza@immergas.com UNI EN ISO 9001:2015 SISTEMA DI QUALITÀ CERTIFIED CERTIFICATO QUALITY SYSTEM...

Table of Contents