Immergas 3.023355 Instruction Sheet

Hide thumbs Also See for 3.023355:
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

Foglio istruzioni
ed avvertenze
Warning and
instruction sheet
IT
IE
COD. 3.023355
KIT COLLEGAMENTO
SCAMBIATORE
POMPA DI CALORE
MAGIS HERCULES
MAGIS HERCULES
HEAT PUMP
EXCHANGER
CONNECTION KIT

Advertisement

Table of Contents
loading

Summary of Contents for Immergas 3.023355

  • Page 1 COD. 3.023355 KIT COLLEGAMENTO Foglio istruzioni ed avvertenze SCAMBIATORE POMPA DI CALORE MAGIS HERCULES MAGIS HERCULES Warning and instruction sheet HEAT PUMP EXCHANGER CONNECTION KIT...
  • Page 2: Avvertenze Generali

    IL PRESENTE FOGLIO È DA LASCIARE ALL'UTENTE ABBINATO AL LIBRETTO ISTRUZIONI DI CALDAIA AVVERTENZE GENERALI. L’installazione o il montaggio improprio dell’ a pparecchio e/o dei Tutti i prodotti Immergas sono protetti con idoneo imballaggio da componenti, accessori, kit e dispositivi Immergas potrebbe dare luogo trasporto.
  • Page 3 Attenzione: rispettare l'orientamento del circolatore come rap- Collegare i componenti del kit come descritto di seguito. presentato in Fig. 2. - Fissare lo scambiatore di calore al telaio utilizzando le viti fornite - Montare la sonda di mandata (13) sul tubo (7) il più vicino pos- in dotazione.
  • Page 4: Schema Elettrico

    COLLEGAMENTI ELETTRICI DEI COMPONENTI DI CALDAIA. Aprire il vano allacciamento (gestore sistema) (17) e collegare i vari componenti del kit (Fig. 2): - Posizionare il relè (16) sulla guida DIN libera (orizzontale) (18), mantenendo il led in basso. - Effettuare i collegamenti come descritto nello schema elettrico (Fig.
  • Page 5 POMPA DI CIRCOLAZIONE CIRCUITO IMPIANTO - Prevalenza proporzionale (ΔP V) (Rif. 3 Fig. 4). Consente di RAFFRESCAMENTO E RISCALDAMENTO (REGOLAZIONE ridurre proporzionalmente il livello di pressione (prevalenza) al CON SELETTORE A MANOPOLA). diminuire della richiesta da parte dell’impianto (riduzione della I circolatori sono equipaggiati con un’...
  • Page 6 POMPA DI CIRCOLAZIONE CIRCUITO IMPIANTO Altre funzioni: RAFFRESCAMENTO E RISCALDAMENTO (REGOLAZIONE - La funzione di sfiato della pompa si attiva premendo a lungo CON SELETTORE A PULSANTE). (3 secondi) il tasto di comando (Rif. 1 Fig. 6) ed esegue automa- Le caldaie vengono fornite con 2 circolatori entrambi muniti di ticamente lo sfiato della pompa.
  • Page 7 Guasti, cause e rimedi circolatore impianto. Guasti Cause Rimedi Fusibile elettrico difettoso Controllare i fusibili Pompa non funzionante con ali- mentazione di corrente inserita. La pompa è priva di tensione Eliminare l'interruzione dell'alimentazione di tensione Aumentare la pressione del sistema entro in campo consentito Cavitazione a causa di una pressione di La pompa genera dei rumori.
  • Page 8: General Warnings

    This instruction manual provides technical information for the regulations in force, according to the manufacturer’s instructions installing the Immergas kit. As for the other issues related to kit and by professionally qualified staff, intending staff with specific installation (e.g. safety in the work site, environment protection, technical skills in the plant sector, as envisioned by the Law.
  • Page 9 Attention: observe the orientation of the circulator, as shown in Connect the lit components as described below. Fig. 2. - Fit the heat exchanger to the frame using the screws supplied. - Mount the flow probe (13) on the pipe (7) as close as possible to - Connect the pipes in sequence starting from the heat exchanger the circulator (9) by moving the insulation slightly.
  • Page 10: Wiring Diagram

    ELECTRIC CONNECTIONS OF THE BOILER COMPONENTS. Open the connection compartment (system manager) (17) and connect the various kit components (Fig. 2): - Position the relay (16) on the free DIN guide (horizontal) (18), keeping the LED at the bottom. - Make the connections as described in the wiring diagram (Fig.
  • Page 11 CIRCULATION PUMP SYSTEM CIRCUIT COOLING turning the selector switch clockwise in the relative power scale. AND HEATING (ADJUSTMENT WITH KNOB SELECTOR - Proportional head (ΔP V) (Ref. 3 Fig. 4).This allows the pres- SWITCH). sure level (head) to be proportionally reduced as the system heat The circulators are equipped with electronic control that allows to demand decreases (flow rate reduction).
  • Page 12 CIRCULATION PUMP SYSTEM CIRCUIT COOLING AND The pump venting function starts and lasts 10 minutes. HEATING (REGULATION WITH BUTTON SELECTOR The two sets of upper and lower LEDs (Ref. 5 Fig. 6) flash alter- SWITCH). nately every 1 second. The appliances are supplied with two circulators both equipped To interrupt, press the control key (Ref.
  • Page 13: Troubleshooting

    Troubleshooting. Faults Causes Solutions Faulty electrical fuse Check the fuses Pump not working with power supply on. The pump is without voltage Eliminate the power supply cut-off Increase the system pressure within the allowed field The pump generates noise Cavitation due to insufficient flow pressure Check the head setting and eventually set a lower head Increase the delivery value The building does not heat up.
  • Page 16 N.B.: correct periodic maintenance is highly recommended. Il libretto istruzioni è realizzato in carta ecologica This instruction booklet is madeof ecological paper. Immergas TOOLBOX L’App studiata da Immergas per i professionisti The App designed by Immergas for professionials Disponibile su Disponibile su Disponibile su immergas.com...