Wiring diagram with generic alarm and
external gas valve.
The boiler is set up for the management of any ge-
neric alarms. In addition, it is possible to connect
an external gas valve to be connected to an LPG
tank. All relays can be configured as a generic
alarm and as an external gas valve.
The diagram shows relay 2 as a generic alarm. In
this case it is necessary to jump pins 57 and 58
Brown
Brown
Blue
Blue
Fig. 3-5
Wiring diagram with chiller control
(cooling only).
The boiler is set up to manage a chiller. The
supply voltage occurs simultaneously with the
request from the Comando Amico Remoto re-
mote control
. In the event this configuration
V2
Brown
Brown
Blue
Blue
Fig. 3-6
of connector X25 positioned on the relay board.
While relay 3 is configured as an external gas
valve supply.
The ''generic alarm'' signal is enabled whenever
one of the envisioned anomalies occurs in the
boiler (see boiler book under ''Troubleshoot-
ing''). The ''external gas valve supply'' control is
enabled together with a burner ignition request
in the boiler.
RELAY BOARD
RELAY BOARD
INTEGRATED P.C.B.
INTEGRATED P.C.B.
is used, it is necessary to jump pins 57 and 58 of
connector X25 positioned on the relay board.
Attention: to prevent the chiller electronic con-
trol from damage, the signal control must not be
live. Interrupt a 230V relay between the chiller
and relay board as indicated in the diagram.
RELAY BOARD
RELAY BOARD
INTEGRATED P.C.B.
INTEGRATED P.C.B.
Brown
Brown
Blue
Blue
42
Models with Aquaceleris: remove the P.C.B.
to a relay disconnecting connector X5 from the
integrated P.C.B. Then, set relay 1 as "Aquaceleris
PTC Supply Voltage" and connect resistance
"E11" as indicated.
GENERIC ALARM
GENERIC ALARM
SIGNALLER
SIGNALLER
LPG
LPG
Models with Aquaceleris: remove the P.C.B.
to a relay disconnecting connector X5 from the
integrated P.C.B. Then, set relay 1 as "Aquaceleris
PTC Supply Voltage" and connect resistance
"E11" as indicated.