Flue evacuation takes place correctly.
03
b
If the anomaly persists, replace the P.C.B.
ERROR 04
The overheating safety thermostat functions regularly.
04
The connector and relative wiring between gas valve and P.C.B.
are OK.
Replace the gas valve. If the anomaly persists, replace the P.C.B.
ERROR 05
The wiring between the flow probe and the board (connector X9
terminals 10-11) is OK.
05
Replace the NTC flow probe. If the anomaly persists, replace the P.C.B.
ERROR 10
The boiler manometer displays a pressure exceeding 0.8 bar.
10
The wiring between the absolute pressure switch and the board is OK.
Check/replace the system pressure switch. If the anomaly persists, replace the P.C.B.
ERROR 12
The wiring between the storage tank probe and the board (connector
X9 terminals 6-7) is OK.
12
Replace the storage tank NTC probe. If the anomaly persists, replace the P.C.B.
ERROR 15
The boiler could display the 06 error
The board is configured as boiler with storage tank.
(presence of the jumper between clamps 6-7 of the connector X7).
15
Replace the P.C.B.
STHCkW ed 04/09
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Clean/restore the correct functionality of the flue extraction elements,
checking lengths and any obstructions.
Clean/restore the correct functionality of the condensation module
No
checking that there are no combustion impurities deposited on the heat
exchanger (soot, oxidations, etc..).
Contacts resistance block
Check the wiring and cleanliness of the electric connection, the continuity
No
of the thermostat contact and replace if necessary.
Restore the electric connection/replace the wiring.
No
Flow probe anomaly
Restore the electric connection/replace the wiring.
No
Insufficient system pressure
Restore the correct pressure by acting on the system filling valve.
N.B.: in this case it is always advisable to ensure that there are no leaks
No
in the central heating plant and check the correct factory-set value of the
expansion vessel.
Restore the electric connection/replace the wiring.
No
Storage tank probe anomaly
The boiler prevents functioning in DHW mode but can function in CH mode.
Restore the electric connection/replace the wiring.
No
Wiring configuration error
N.B.: This board can be used for instant type boilers (VICTRIX Superior kW)
or with storage tank (VICTRIX ZEUS Superior kW ). The board automatically
recognises the type of boiler by means of the relative wiring of the P.C.B.
For the HERCULES Condensing boiler check the PRESENCE of the
No
connection jumper between clamps 6-7 of the connector X7.