  Connecting the Inverter to AC Grid
 4. If required, ground the conduit by connecting it to the grounding bar, as shown
above.
Connecting the Inverter to AC Grid
For connecting the inverter to AC grid, use a 14–4 AWG cable.
For more wiring information, refer to the SolarEdge Recommended AC
Wiring Application Note , available on the SolarEdge website at
http://www.solaredge.com/files/pdfs/application-note-recommended-
wiring.pdf.
To connect to AC grid:
 1. Turn off the AC circuit breaker on the distribution panel.
 2. Strip 2.5'' / 60 mm of the external cable insulation and strip 0.6'' / 15 mm of the
internal wire insulation.
 3. Pass the AC cable through the conduit.
 4. Connect the wires to the AC terminals as shown below.

Connecting the DC Strings to the Inverter

Connect the string to the DC input pairs. If required, connect additional strings in
parallel using an external combiner box/branch cables before connecting to the
inverter.
Single Phase Energy Hub Inverter with Prism Technology MAN-01-00842-1.3
Figure 13: Insulation Stripping – AC Cable
Figure 14: AC connection