  Connecting the AC Grid to the Inverter or to the DC Safety Switch
Connecting the AC Grid to the Inverter or to the DC
Safety Switch
Use AC cable in a diameter of 19 mm to 28 mm. For three phase connection, use a
standard cable with five wires (L1,L2,L3 + N + PE) or three wires (L1,L2,L3 + PE) cable .
The cross section of the conductor of the wires must be 4 mm² to 16 mm².
When using a stranded wire, the use of ferrule is at installer discretion.
For more wiring information refer to the SolarEdge Recommended AC
Wiring Application Note , available on the SolarEdge website at
http://www.solaredge.com/files/pdfs/application-note-recommended-
wiring.pdf.
Connecting the AC Grid to the Inverter
To connect the AC grid to the inverter:
1. Turn OFF the AC circuit breaker.
2. Release the  six Allen screws of the inverter cover and carefully move the cover
horizontally before lowering it.
CAUTION!
When removing the cover, make sure not to damage internal components.
SolarEdge will not be held responsible for any components damaged as a
result of incautious cover removal.
3. Expose 10 mm to 11 mm / 0.4 '' of wire insulation ( Figure 15 ).
Figure 15: 5-Wire AC Cable - Insulation Stripping
Three Phase Inverter with SetApp Configuration PN: SEXXK-XXXXIXXXX