BOILER
START-UP (INITIAL CHECK).
- (TECHNICIAN)
To commission the boiler:
- ensure that the declaration of conformity of
installation is supplied with the appliance;
- make sure that the type of gas used corresponds
to boiler settings;
- check connection to a 230V-50Hz power mains,
correct L-N polarity and the earthing connec-
tion;
- make sure the central heating system is filled
with water and that the manometer indicates a
pressure of 1÷1.2 bar.
- check that the air vent valve cap is open and that
the system is well deaerated;
- switch the boiler on and check correct igni-
tion;
- check the ∆p gas values in domestic hot water
and central heating modes;
- check the CO
in the fumes at maximum and
2
minimum flow rate;
- check activation of the safety device in the event
of no gas, as well as the relative activation time;
- check activation of the main switch located upstre-
am from the boiler and in the boiler;
- check that the intake and/or exhaust terminals
are not blocked;
- ensure activation of all adjustment devices;
- seal the gas flow rate regulation devices (if set-
tings are modified);
- check the production of domestic hot water;
- check sealing efficiency of water circuits;
- check ventilation and/or aeration of the instal-
lation room where provided.
If any checks/inspection give negative results, do
not start the boiler.
SK
3
UVEDENIE KOTLA DO
PREVÁDZKY (PREDBEŽNÁ KONTROLA).
- (TECHNIK)
Počas uvádzania kotla do prevádzky je nutné:
- skontrolovať prítomnosť prehlásenia o zhode
danej inštalácie;
- skontrolovať, či použitý plyn odpovedá tomu,
pre ktorý je kotol určený;
- skontrolovať pripojenie k sieti 230V-50Hz,
správnosť polarity L-N a uzemnenia;
- skontrolovať, či je vykurovací systém naplnený
vodou podľa ručičky na manometre, ktorý má
ukazovať tlak 1÷1,2 bar;
- skontrolovať, či sú klobúčiky odvzdušňovacích
ventilov otvorené a či je zariadenie dobre
odvzdušnené;
- zapnúť kotol a skontrolovať správnosť zapále-
nia;
- skontrolovať hodnoty ∆p plynu v režime ohrevu
úžitkovej vody a vykurovania;
- skontrolovať CO
v spalinách pri maximálnom
2
a minimálnom výkone;
- skontrolovať, či bezpečnostné zariadenia pre
prípad výpadku plynu pracuje správne a dobu,
za ktorú zasiahne;
- skontrolovať zásah hlavného spínača umiest-
neného pred kotlom a v kotli;
- skontrolovať, či nasávací systém a výfukové
koncové kusy nie sú upchaté;
- skontrolovať zásah regulačných prvkov;
- zaplombovať regulačné zariadenie prietoku
plynu (ak by sa nastavenie mali zmeniť);
- skontrolovať ohrev úžitkovej vody;
- skontrolovať tesnosť vodovodných okruhov;
- skontrolovať ventiláciu a/lebo vetranie v mie-
stnosti, kde je kotol inštalovaný tam, kde je to
potreba.
Ak by výsledok len jednej kontroly súvisiacej s
bezpečnosťou bol negatívny, nesmie byť zariadenie
uvedené do prevádzky.
175
BG
3
ПУСКАНЕ В УПОТРЕБА НА
ТОПЛОГЕНЕРАТОРА (ПЪРВОНАчАЛНА
ПРОВЕРКА). - (ТЕХНИК)
За пускане в експлоатация на топлогенератора
трябва:
- да се провери съществува ли декларация за
съответствие на инсталацията;
- да се провери съответства ли използвания
газ на този, за който е предназначен
топлогенератора;
- да се провери свързването към мрежа 230V-
50Hz, спазването на поляритета L-N и
свързането със земята;
- да се провери дали отоплителната инсталация
е пълна с вода, проверявайки дали стрелката
на манометъра на топлогенератора показва
налягане от 1÷1,2 bar;
- д а с е п р о в е р и д а л и к а п а ч е т о н а
обезвэдушителния клапан е отворено и дали
инсталацията е напълно обезвъздушена;
- да се запали топлогенератора и да се провери
правилното запалване;
- да се проверят стойностите ∆p на газа при
режим санитарен и отопление;
- да се провери CO2 на дима при максимален
и минимален капацитет;
- да се провери задействането на защитното
приспособление в случай, на липса на газ и
съответното време задействане;
- да се провери намесата на главния прекъсвач
поставен на рамата на топлогенератора и в
топлогенератора;
- да се провери дали терминалите за засмукване
и/или отвеждане не са запушени;
- да се провери задействането на регулиращите
органи;
- да се затворят плътно механизмите за
регулиране на дебита на газтта (при всяка
една промяна в регулирането);
- да се провери производството на санитарна
топла вода;
- да се провери уплътнението на водните
кръгове;
- д а с е п р ов е ри в е н т и ла ц и я т а и / и л и
проветривостта на избраното за инсталация
помещение.
При наличието на един негативен резултат от
проверката по безопасността, не се позвлява
пускане на уреда в употреба.

Advertisement

Table of Contents
loading

Table of Contents