If you experience a problem with the UPS, please refer to the Troubleshooting section in this manual to correct the problem. If the problem is not corrected, please collect information so that the Technical Support personnel can more effectively assist you. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US-IB00, L20US-IB60, L20US-IB00 UPS...
Page 8
ABLE AULT NFORMATION ............................ 60 ABLE LARM NFORMATION ) ......................64 ABLE ELAY CONTACTS COMMUNICATION CARD 10 S ............................65 ABLE PECIFICATIONS 11 P ........................... 70 ABLE ROBLEMS AND SOLUTIONS L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US-IB00, L20US-IB60, L20US-IB00 UPS...
Denotes a warning. It calls attention to a procedure that, if not correctly performed or adhered to, could result in injury or loss of life. Do not proceed beyond a caution note until the indicated conditions are fully understood and met. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Phone support Available 24 * 7 * 365 by phone at (510) 498 3333. • Other regions Available 24 * 7 * 365 by phone at (972) 73 2403139 • L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Test before touching. WARNING! (Fuses): To reduce the risk of fire, replace only with the same type and size of fuse. WARNING! Unit intended for installation in a controlled environment. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Page 12
Remove watches, rings, or other metal objects. • Use tools with insulated handles. • Wear rubber gloves and boots. • Do not lay tools or metal parts on top of batteries. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
2nd-stage: Constant Voltage in order to vitalize battery and make sure batteries are fully • charged. 3rd stage: floating mode. • This 3-stage charging method will extend life of the batteries and guarantee fast charging. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Backup time required will indicate the battery size needed. If the load is less than the UPS • nominal power rating, then actual backup time is longer. The following options are available with extra charge: • SNMP/WEB card • Relay card • Parallel connection • L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
1. One end of a USB cable connects to the computer, the other end connects to the USB port on the UPS. 2. Open the software Muser5000, click “system” button. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Figure 6 Muser5000 communication setting page 4. On the main page of Muser5000, click the button of “Append”, then goes to a window of “Append equipment”. Password is YDC3350. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
6. Click the button “Append”, then the connection between UPS & computer is accomplished. CAUTION! When the UPS works on inverter: If you want to use PC to set the output voltage and frequency, you must shut down the inverter first. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
If the AC mains input power fails, the inverter, which obtains power from the battery, supplies the critical AC load. There is no power interruption to the critical load. The UPS will automatically return to Normal Mode when AC recovers. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
AC load. This is to avoid paralleling of unsynchronized AC sources. This interruption is programmable but typically set to be less than an electrical cycle e.g., less than 15ms (50Hz) or less than 13.33ms (60Hz). L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
UPS will transfer from bypass to Inverter and supplies power from the battery, and then the LCD shows all related information on the screen. SINGLE INPUT: Mains Input DUAL INPUT: Mains Input and Bypass Input Figure 13 ECO mode L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Switch on the MAINS to simulate utility recovery, the rectifier will restart automatically • after 20 seconds and the inverter will supply to the load. The UPS can be loaded up to its maximum capacity during load test. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Switch to normal operation (from mechanical bypass) 4.2.5. CAUTION! Never attempt to switch the UPS back to normal operation until you have verified that there are no internal UPS faults L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Refer to the important safety instructions for standard model in this manual. • Turn on the OUTPUT breaker. • Trigger the cold start button. Position 5 in the figure below. • L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
4. Open the OUTPUT breaker. The UPS shuts down. 5. To completely isolate the UPS from AC Mains, all input switches of Utility shall be completely off, which includes the ones for rectifier and bypass. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
At the window of “Data Set”, click “Ups ID”, write a value for the parallel UPS ID at the • right side, such as “1”, then click “Set” as shown in below picture. If the UPS sounds a “beep”, that means the setting is correct. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
After setting the UPS systems needed to be paralleled, power off all the UPS systems. • Connect all the UPS systems in parallel cable installation, and then power on the UPS systems. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
4.3. LCD control panel Overview 4.3.1. Figure 19 LCD control panel introduction Table 5 LCD and LED display Fault LED Bypass mode LED Battery mode LED Inverter work LED LCD display L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Logo Home Current page fault and event Data page Data 4.3.3. Displays the flow state of the UPS work, and quickly enters real-time data by clicking on the block. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
View the voltage and current of the main, bypass, output, battery (can also be entered through by real-time data block), View the status of the switches, dry contacts, through clicking on the block, enter the corresponding data window. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Main 4.3.4.1. Click the main block to enter the main data display window. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Bypass 4.3.4.2. Click the bypass block to enter the bypass data display window. Output 4.3.4.3. Click the output block to enter the output data display window. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Battery 4.3.4.4. Click the battery block to enter the battery data display window. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Status info 4.3.4.5. Click the Status info to enter the Status info display window. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Alarm 4.3.5. View the alarm and history of the UPS, and open or close the buzzer. Current alarm 4.3.5.1. Click Current alarm to enter the current alarm display window. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Click return to return to the previous window, click home page to return to the main page. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Setting 4.3.6. There are two levels of access: The basic setting for user settings • Advanced setting for technical personnel • L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Basic setting 4.3.6.1. Click basic setting, log in with the correct password. The user password is “111111”. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Password 4.3.6.3. Click password icon, enter user password setting page, input old password and new password, then click save confirm to save the change. Password format is six digits. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
10~63, default value is 63. Backlight time: LCD backlight delay time, click the text to input new value and click save config icon to save. Value range is 1~255, default value is 60. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Click the text to select other value or input new value and click save config icon to save. Rs485 address: UPS communication ID, address range is 1~15,default is 1. • Rs485 Baud Rate: Baud rate: 2400, 4800, 9600, 14400, 19200, default is 9600. • L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
The value range is ±1%, ±2%, ±4%, ± 5%, ±10%(default). Bypass Rate Tracking Rate: Inverter frequency tracking to bypass frequency rate. The value range is 0.5~2Hz/s and is 1 by default. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Page 50
3 to 10 and is 10 by default. EPO Transfers To BYP: Specifies whether transfers to bypass mode when press EPO button. The default value is Disable. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
4.3.7. Click advanced setting, input the correct password. The user password is “191210”. NOTE! This operation is recommended to be operated by professionals, or under the guidance of professionals. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
1 to 2, default value is 1, maximum allowed value is 2, because only two UPSes of this model can be connected in a parallel system. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Output Volt Level: Output voltage level. The value can be 120 and 127. • Output Volt Adjust (%): Inverter voltage regulated. The value can be -5%~0~+5%, step • is 0.5%, default value: 0. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Single Battery Capability: Must modify the value to actual configuration. The value can • be 7~2000. Boost/Float Conversion(month): Set up boost charge and float charge conversion time. • The value can be 0~24, default value is 0. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Page 56
Aver charging Duration: boost charge time limit, the value can be 1–999 min, and is 240 • by default. EOD Battery Volt(V/Cell): End of discharge voltage. The value can be 1.60~1.90 and is • 1.80 by default. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
IN 01: The default value is INV ON. IN 02: The default value is INV OFF. IN 03: The default value is Close. IN 04: The default value is Close. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Page 58
The default value is Bypass Mode. OUT 03: The default value is BATT Low Volt. OUT 04: The default value is Online Mode. NOTE! Each dry contact can be N.O or N.C. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Timing daily 4.3.8.2. Modify the check date, time, and check time (10S (default), 10min, EOD). Timing weekly 4.3.8.3. Modify the check date, time, and check time (10S (default),10min, EOD). L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Single OFF: turns the Inverter OFF and transfers the load to bypass. • Single ON: Inverter ON. • Parallel OFF: Inverter OFF all parallel UPS systems in parallel. • Parallel ON: Inverter ON all parallel UPS systems. • L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Battery test 4.3.9.2. 10S: battery test for 10s • 10min: battery test for 10min • EOD: battery test to EOD • 10%: battery test down 10% capability. • L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Fault clear 4.3.9.3. Clear the current fault (not for all faults). Monitor and LCD software version 4.3.10. L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
INVERTER LED blinking seconds Once per 2 Mains Volt. Abnormal INVERTER LED blinking seconds Once per 2 REC Comm. Error INVERTER LED blinking seconds Once per 2 Mains input lost seconds L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Page 69
FAULT LED blinking seconds Once per second BYPASS LED blinking BPS Phase Reversed Once per second BYPASS LED blinking Once per 2 BPS Unable To Trace BYPASS LED blinking seconds L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Remote UPS monitoring and management can be performed through HTTP, SNMP, • SSH, Telnet; Complete equipment event handling (including event recording and notification); • Can be extended to connect 2 channels of temperature and humidity monitoring • modules; L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
The relay communication card contains six dry contact outputs and one dry input. The inputs and outputs are factory programmed according to functions listed in the Table. Figure 21 Relay contacts (dry contact card) L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Page 76
As per IEC 62040-3, 0 to 40°C (32 to 104°F) Storage Temperatur -25℃/ 13°F ~55℃/ 131 °F (no battery) Environment 0~95% noncondensing Humidity Acoustical Noise from <58dB 1M distance Altitude Up to 3280.84 ft without derating L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Page 77
Standards Approving Agency TUV RHEINLAND CHINA & CCIC Agency Standard Tested UL1778 5th Edition Canadian Approvals CSA 22.2-107.3-14 EMI Approvals FCC Part15 Subpart B Class A/ ANSI C63.4 2014 L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Battery LED is Battery breaker does not Switch on the battery breaker. If flashing but switch on, or batteries are batteries are damaged, need to replace whole group batteries, L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...
Page 79
Switch on the power breaker. panel does not switch ON. Buzzer beeps UPS is out of order Consult with your local agent continuously and for repair LCD indicates 1,3,5,9,15, etc. fault codes L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US- IB00, L20US-IB60, L20US-IB00 UPS...