Dear Customer, Congratulations for having chosen a top-quality Immergas product, able to assure well-being and safety for a long period of time. As an Immergas Customer, you can also count on an Authorised A er-Sales centre, prepared and updated to guarantee constant e ciency of your boiler.
SAFETY SYMBOLS USED. GENERIC HAZARD Strictly follow all of the indications next to the pictogram. Failure to follow the indications can generate hazard situa- tions resulting in possible harm to the health of the operator and user in general. ELECTRICAL HAZARD Strictly follow all of the indications next to the pictogram.
ATTENTION: e Victrix Tera Vip boiler has been designed for wall mounted installation only; for central heating and check the environmental operating production of domestic hot water for domestic use conditions of all parts relevant to in- and similar purposes.
Page 7
- Installation of gas appliances, ue ex- It is just as important that the intake grids and exhaust terminals are not obstructed. haust pipes and combustion air intake It is recommended to check that no ue gas recircula- pipes is forbidden in places with a re tion is found in the air sample points (0.5% maximum risk (for example: garages, closed parking permitted CO...
Page 8
Risk of damage due to corrosion caused by unsuitable ATTENTION: combustion air and environment. - Type B open chamber boilers must not Spray, solvents, chlorine-based detergents, paints, glue, be installed in places where commer- ammonium compounds, powders and similar cause cial, artisan or industrial activities take place, product and ue duct corrosion.
MAIN DIMENSIONS. Key: V - Electrical connection G - Gas supply AC - Domestic hot water outlet AF - Domestic hot water inlet SC - Condensate drain (minimum internal diameter Ø 13 mm) R - System return M - System ow Height Width (mm) Depth (mm)
An aqueous solution must be made with potential pollution class of water 2 (EN 1717:2002). e materials used for the central heating circuit of Immergas boilers resist ethylene and propylene glycol based antifreeze liquids (if the mixtures are prepared perfectly).
CYCLOIDAL FILTER UNIT. - Place a container under the lter to collect the water contained e magnetic cycloidal lter is standard supplied in the boiler. in it. Allows to detect the ferrous residues present in the system's water. - Remove the clip and pull out the magnetic cartridge by pulling anks to the two cocks it facilitates maintenance by cleaning the it downwards.
(i.e. downstream from the pipes connecting the system to the appliance), according to the manufacturer’s instructions. e Immergas connection unit, supplied as an optional kit, also includes the gas cock, whose installation instructions are provided in the kit.
In order to meet the system requirements established by EN 1717 in terms of pollution of drinking water, we recommend installing the IMMERGAS anti-back ow kit to be used upstream of the cold water inlet connection of the boiler. We also recommend using a category 1, 2 or 3 heat transfer uid (ex: water + glycol) in the boil- er’s primary circuit (CH circuit), as de ned in standard EN 1717.
A er-sales Service. It is recommended to contact ATTENTION: a quali ed company (e.g. the Immergas Authorised A er-Sales the manufacturer declines any respon- Technical Assistance Service) for replacement to avoid a hazard.
44/40 and 41 eliminating jumper X40 (Fig. 37). Make sure that the On/O thermostat contact is “dry”, i.e. independent of the mains voltage, • On/O Immergas digital chrono-thermostat. otherwise the P.C.B. would be damaged. Any Comando Amico e chrono-thermostat allows:...
1.12 IMMERGAS FLUE SYSTEMS. Immergas supplies various solutions separately from the boilers regarding the installation of air intake terminals and ue exhaust, which are fundamental for boiler operation. ATTENTION: the boiler must be installed exclusive- ly with an original Immergas “Green Range”...
1.13 TABLES OF RESISTANCE FACTORS AND EQUIVALENT LENGTHS OF “GREEN RANGE” FLUE SYSTEM COMPONENTS. Resistance Length TYPE OF DUCT Factor in m of concentric pipe Ø 80/125 Concentric pipe 80/125 Ø m 1 Ø 80/125 90° concentric bend Ø 80/125 45° concentric bend Terminal complete with concentric horizontal intake-exhaust Ø...
Page 18
Resistance Length Length Length Length TYPE OF DUCT Factor in m of concen- in metres in metres in m of concen- tric pipe Ø 60/100 of a Ø 80 pipe of a Ø 60 pipe tric pipe Ø 80/125 Intake m 7.3 Concentric pipe Ø...
- the ue exhaust must be connected to its own single chimney ) or ducted directly outside via a vertical terminal for direct exhaust (B ) or via an Immergas ducting system (B e technical regulations in force must be respected. Cover kit assembly (Fig. 13).
100. In this case the special extensions must be requested. Immergas also provides a Ø 60/100 simpli ed terminal, which in combination with its extension kits allows you to reach a maxi- mum extension of 11.9 metres.
1.16 CONCENTRIC VERTICAL KIT INSTALLATION. • Type C con guration, sealed chamber and fan assisted. Concentric vertical intake and exhaust kit. is vertical terminal is connected directly to the outside of the building for air intake and ue exhaust. N.B.: the vertical kit with aluminium tile enables installation on terraces and roofs with a maximum slope of 45% (approx 25°) and the height between the terminal cap and half-shell (374 mm for Ø...
1.17 SEPARATOR KIT INSTALLATION. Type C con guration, sealed chamber and fan assisted. • Separator kit Ø 80/80. is kit allows air to come in from outside the building and the exhaust to exit from the chimney, ue or intubated duct through divided ue exhaust and air intake pipes.
1.18 ADAPTOR C9 KIT INSTALLATION. Kit Assembly. is kit allows an Immergas boiler to be installed in "C " con g- - Mount the components of kit "C9" on the door (A) of the ducting uration, with combustion air intake directly from the sha where system (Fig.
Page 28
Technical data. e dimensions of the sha s must ensure a minimum gap be- tween the outer wall of the smoke duct and the inner wall of the sha : 30 mm for circular section sha s and 20 mm in the event of a square section sha (Fig.
Ø80 complete exhaust terminal, 1m of Ø 80 pipe in exhaust, two of the regulations in force. 90° Ø 80 bends at boiler outlet for connecting to the ducting Immergas ducting system. system and two direction changes of the exible hose inside the chimney/technical slot.
1.20 CONFIGURATION TYPE B, OPEN CHAMBER AND 1.22 FLUES, CHIMNEYS, CHIMNEY POTS AND FAN ASSISTED FOR INDOORS. TERMINALS. e appliance can be installed inside buildings in B or B mode; e ues, chimneys and chimney caps for the evacuation of com- in this case, all technical rules and national and local regulations bustion products must be in compliance with applicable standards.
1.23 WATER TREATMENT SYSTEM FILLING. As already mentioned in the previous paragraphs, a treatment of the thermal and domestic system water is required, in compliance with the local standards in force. e parameters that in uence the duration and proper oper- ation of the heat exchanger are the water's PH, total hardness, conductivity, and oxygen, together with the system's processing residues (any welding residues), any oil present and corrosion...
1.27 BOILER START UP IGNITION . If necessary, the bypass can be regulated to system requirements To commission the boiler (the operations listed below must only be from minimum (bypass closed) to maximum (bypass open). performed by quali ed personnel and in the presence of sta only): Adjust using a at-head screwdriver.
Page 33
Pump release. If a er a long period of inactivity, the circulator is blocked, adjust the screw in the centre of the head in order to manually release the motor sha . Take great care during this operation to avoid damage to the motor. Bypass Regulation (Part.
1.30 KITS AVAILABLE ON REQUEST. • System shut-o valve kits without inspection lter (on request). e boiler is designed for installation of system interception cocks to be placed on ow and return pipes of the connection assembly. is kit is particularly useful for maintenance as it allows the boiler to be drained separately without having to empty the entire system.
INSTRUCTIONS FOR USE AND • Do not open or tamper with the ap- MAINTENANCE. pliance. GENERAL WARNINGS. • Do not take apart or tamper with the ATTENTION: intake and exhaust pipes. • Never expose the wall-mounted boiler • Only use the user interface devices listed in to direct vapours from a cooking sur- this section of the booklet.
Page 37
- do not use electrical switches, plugs, door professionally authorised company as required bells, telephones or intercom devices in the by current legislation. Contact the manufac- building; turer for disposal instructions. - call an authorised company (e.g. Immergas A er-Sales Service).
CLEANING AND MAINTENANCE. To preserve the boiler's integrity and keep the safety features, performance and reliability, which distin- guish it, unchanged over time, you must execute maintenance operations on a yearly basis in com- pliance with what is stated in the relative point at “annual check and maintenance of the appliance”, in compliance with national, regional, or local standards in force.
2.4 USING THE BOILER. e boiler is supplied as per standard with Aqua Ce- Before ignition make sure the heating system is lled with water leris device function deactivated to safeguard energy and that the manometer (8) indicates a pressure of 1 - 1.2 bar. consumption.
(1) (1) If the block or anomaly persists, contact an authorised company (e.g. Immergas Technical A er-Sales Service) (2) The anomaly can only be verified in the list of errors in the “Information” menu...
Page 41
(1) probes temperature dri detected (1) If the block or anomaly persists, contact an authorised company (e.g. Immergas Technical A er-Sales Service) (2) The anomaly can only be verified in the list of errors in the “Information” menu...
INFORMATION MENU. By pressing the button “ “, the “Information menu” is activated for at least 1 second, displaying some boiler operating parameters. To scroll through the various parameters, press the buttons “DHW regulation” “ “. With the menu active on the indicator (19) the parameter via the letter “d”...
Periodically check the system water pressure. e boiler pressure anti-freeze liquid and installation of the Immergas Antifreeze Kit gauge should read a value of between 1 and 1.2 bar. in the boiler. In the case of prolonged inactivity (second case), we...
With regard to the above, only use Immergas original spare parts when replacing parts. If additional documentation needs to be consulted for extraordinary maintenance, contact the Authorised Immergas A er-Sales Service.
Intervention time must be less than 10 seconds. the combustion chamber. It is also forbidden to use alkaline or acid detergents. Victrix Tera Vip - Check the integrity of the insulating panels inside the com- at nominal at minimum bustion chamber and if damaged replace them.
Clean the above components e gas conversion operation must be carried out by and ensure correct installation of the terminal, check correct an authorised company (e.g. Immergas A er-Sales Technical setting of the gas valve (O -Set setting) and correct percentage Assistance Service).
(does not detach from burner); S1 = 121 (6050 rpm) Maintenance interventions must be carried out by S1 = 127 (6350 rpm) G230 an authorised company (e.g. Immergas A er-Sales Technical Assistance Service). ADJUSTMENT. Attention: the CO veri cation operations must be carried out...
3.11 PROGRAMMING THE P.C.B. e rst digit of the central indicator (19) shows the family of the e boiler is prepared for possible programming of several operation parameter, while the second digit shows its number. By pressing parameters. By modifying these parameters as described below, the the domestic hot water / D.H.W.
Page 51
Custom- Param- Parameter Description Range Default ised value eter Max DHW De nes the maximum heat output percentage of the boiler during the 0 - 100 % 100 % output D.H.W. phase compared to the maximum heat output available Min CH output De nes in percentage the minimum output in central heating mode 0 - P2 G20 = 85 De nes the maximum heat output percentage of the boiler during the central...
Page 52
Custom- Param- Parameter Description Range Default ised value eter Establishes the display lighting mode. 0 : the display lights up during use and lowers a er 15 seconds of inactivity. Display In the case of anomaly the display ashes. 0 - 2 lighting 1 : display lighting o .
3.12 PASSWORD PROTECTED SPECIAL FUNCTIONS. e function is activated from boiler in o mode by pressing and Attention: the boiler is equipped with some special functions, access holding the buttons “Reset”, “Info” and “Stand-by” for more tan to which is granted if this is in stand-by ( 5 seconds.
3.15 FLUE INSTALLATION FU . 3.17 "CHIMNEY SWEEP” FUNCTION. To activate the “Flue” function access the special functions as When activated, this function forces the boiler to variable described in Par. 3.12 and select the “FU” function. output for 15 minutes. In this state all adjustments are excluded and only the safety Attention: before performing the test, ensure that the condensate thermostat and the limit thermostat remain active.
3.18 SOLAR PANELS COUPLING FUNCTION. e boiler is prepared to receive pre-heated water from a system of solar panels up to a maximum temperature of 65°C. In any case, it is always necessary to install a mixing valve on the hydraulic circuit upstream of the boiler, on the cold water inlet.
3.22 CASING REMOVAL. • Front panel (Fig. 52). To facilitate boiler maintenance the casing can be completely 4) Open the door (e1), remove the cover caps (c) and loosen screws removed as follows: (d). • Lower grid (Fig. 51). 5) Pull the front panel (e) towards you and release it from its lower 1) Loosen the two screws (a).
Page 57
• Control panel (Fig. 54). • Sides (Fig. 55). 9) Press the hooks on the side of the control panel (i). 11) Loosen screws (k) of side fastening (j). 10) Tilt the control panel (i) towards you. 12) Remove the sides by extracting them from their rear seat (Ref. X). Rif.
TECHNICAL DATA. VARIABLE HEAT OUTPUT. N.B.: the power data provided in the table are obtained with 0.5 m long intake/exhaust pipe. Gas ow rates refer to net calori c value at a temperature of 15°C and at a pressure of 1013 mbar. METHANE (G20) PROPANE (G31) PROP.
KEY FOR DATA NAMEPLATE. Cod. Md Sr N° Cod. PIN Type Qnw/Qn min. Qnw/Q max. Pn min. Pn max. Class CONDENSING N.B.: the technical data are provided on the data plate on the boiler Model Cod. Md Model code Sr N° Serial Number Check Cod.
Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY (*) High temperature mode means 60°C on return and 80°C on ow. (**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return...
Page 62
PRODUCT FICHE IN COMPLIANCE WITH REGULATION 811/2013 . Parameter value punto soluzioni srl Annual energy consumption for the central heating "!! VICTRIX TERA VIP 44.0 GJ mode (Q Annual electricity consumption for the domestic hot 27 kWh water function (AEC) Annual fuel consumption for the domestic hot water 18.0 GJ...
In case you should wish to install an assembly, starting from the devices, integration heat pumps, temperature controllers). Victrix Tera Vip boiler, use the assembly charts in (Fig. 58 and 61 Use board (Fig. 58) for “assemblies” related to the central heating To complete it properly, ll the relevant spaces (as shown in the mode (e.g.: boiler + temperature controller).
Page 64
Parameters for lling in the assembly chart. Parameter Victrix Tera Vip ‘I’ ‘II’ ‘III’ 1.11 ‘IV’ 0.44 * to be established by means of table 5 of Regulation 811/2013 in case of “assembly” includ- ing a heat pump to integrate the boiler. In this case the boiler must be considered as the main appliance of the assembly.
Page 65
Facsimile for lling in the domestic hot water production system package che. :DWHU KHDWLQJ HQHUJ\ HI¿FLHQF\ RI FRPELQDWLRQ ERLOHU ‘I’ Stated ORDG SUR¿OH Solar contribution )URP WKH ERDUG RI WKH VRODU GHYLFH Auxiliary electricity ( 1.1 x ‘I’ 10 % ) ‘II’...
Page 66
Parameters for lling in the DHW package che. Parameter Victrix Tera Vip ‘I’ ‘II’ ‘III’ * to be determined according to Regulation 811/2013 and transient calculation methods as per Notice of the European Community no. 207/2014. Domestic hot water production system package che.
Page 68