9.7.3
Ambient temperature
Maximum permitted ambient temperature during operation in hazardous areas with potentially
explosive atmosphere
Positioner
6DR710* and 6DR711*
9.7.4
Electrical specifications
Analog input (AI) HART / 4 ... 20 mA
Terminals 6(+) and 7(-)
For connecting to circuits with the following
peak values
Analog output (AO) 4 ... 20 mA
Terminals 61(+) and 62(-)
For connecting to circuits with the following
peak values
Analog output (AO) galvanically isolated from
the analog input (AI)
Test voltage
9.8
Mobile IQ app and AW050 Bluetooth adapter
9.8.1
SITRANS mobile IQ
Software requirements
Required Android version
Required iOS version
Bluetooth
SIPART PS100
Compact Operating Instructions, 05/2021, A5E50188940-AA
9.8 Mobile IQ app and AW050 Bluetooth adapter
Temperature class T4
-20°C ≤ Ta ≤ +80°C
Basic electronics with explosion protection
Ex "ia"
U
≤ 30 V
i
I
≤ 100 mA
i
P
≤ 750 mW
i
C
≤ 6 nF
i
L
≤ 221 μH
i
U
≤ 30 V
i
I
≤ 100 mA
i
P
≤ 750 mW
i
C
≤ 7 nF
i
L
≤ 66 μH
i
7.0 or higher
12.0 or higher
BLE 4.2 or higher
Ex "ic"
U
≤ 30 V
i
I
≤ 100 mA
i
-
C
≤ 6 nF
i
L
≤ 221 μH
i
U
≤ 30 V
i
I
≤ 100 mA
i
-
C
≤ 7 nF
i
L
≤ 66 μH
i
840 V DC, 1 s
Technical specifications
Ex "ec", "tb"
U
≤ 30 V
n
I
≤ 100 mA
n
-
-
-
U
≤ 30 V
n
I
≤ 100 mA
n
-
-
-
49