5.2
Grounding
The positioner is grounded via the mounting kit or via grounding with thread M4 on the
enclosure,
5.3
Electrical connection
①
②
③
④
Figure 5-1
5.4
Pneumatic connection
Supply pressure PZ
For safety reasons, the supply pressure PZ can be fed after installation only if the positioner is
switched to the "NO INIT" mode when an electrical signal is available.
Note
Specifications regarding air quality
Observe the specifications regarding the air quality, see section "Technical specifications
> Pneumatic data (Page 44)".
SIPART PS100
Compact Operating Instructions, 05/2021, A5E50188940-AA
⑨
in the figure "Overview of the device components (Page 5)".
Digital input or switching amplifier
Power source 12 to 30 V DC
HART connector
Signal source 4 to 20 mA
Wiring diagram
WARNING
5.4 Pneumatic connection
⑤
Digital output
⑥
Analog output of position feedback
⑦
Analog input current input 4 to 20 mA
⑧
Digital input (floating contact)
Connecting
29