NOTES FOR HEAT PUMPS
BOARD
Using the manager involves modifying the addresses
contained within heat pumps (see heat pump booklet).
The required addresses are:
11 = Heat pump 1
12 = Heat pump 2
13 = Heat pump 3
14 = Heat pump 4
8.1

NOTES FOR MAGIS PRO

The A11, T02 parameters and the parameter families
UXX, RXX, IXX are automatically set by the system
manager.
Settings required:
- A12 = OFF;
- A13 = 1;
- A21 = 11;
- A22 = OFF;
- P06 = IN;
The ranges of integration and priority times are reduced
to:
- 1 - 240 minutes
Definit. System
Configuration
Magis Pro
Two pipes conn.
Fig. 8-1
- Two pipes connection. The device is used by connect-
ing only the flow and return pipes.
- Four pipes connection. The device is used by con-
necting the system and dhw flow and return pipes (for
information contact the Support Service).
If optional external probe is used:
- connect the optional external probe to Magis Pro.
- Select R01 = IU.
- Disconnect and reconnect power supply from the
device.
8.2

NOTES FOR MAGIS COMBO

The A11, T02 parameters and the parameter families
UXX, RXX, IXX are automatically set by the system
manager.
Settings required:
- A12 = OFF;
- A13 = 1;
- A21 = 11;
- A22 = OFF;
- P06 = IN;
The ranges of integration and priority times are reduced
to:
- 1 - 240 minutes
In the X01 page set the "Disp. " = "Boiler with external
probe" parameter to enable the potential burner ignition.
If optional external probe is used:
- connect the optional external probe to Magis Combo.
- Select R01 = IU.
- Disconnect and reconnect power supply from the
device.
8.3

NOTES FOR AUDAX TOP 18/21 ERP

With these machines, the circulation pumps operation
logic can be configured.
P12
Definit. System
Audax Top 18/21 - N.1
Circ.pump config. - online
Mode
Speed Minimum
Speed Maximum
Delta T
Fig. 8-2
The parameters are:
- Mode. Enable the pump operation with speed set "Max.
speeed" or the modulating mode with tracking of the
"Modulating" temperature differential.
- Minimum speed. Value of minimum speed used in
modulating operation.
- Maximum speed. Value of maximum speed used in
modulating operation.
- Delta T.Temperature delta to be maintained with
modulating operation.
A machine power reduction can be set.
53
P13
: Max sp.
:
00 %
:
000 %
:
00.0 °C