NOTES FOR ZONE
DEVICES
7.1

NOTES FOR ZONE CONTROL

POWER
Mode
MODE
HUM
SLEEP
CLOCK
TEMP
N.B.: The zone controls must be configured so that
they work correctly with the system manager, and the
address in particular must be set up using the following
procedure:
1 - press the UP key;
2 - within three seconds press the DOWN key;
3 - when the term "PAr" appears on the main area, release
the DOWN key keeping the UP key down and press
the TEMP key within three seconds.
Procedure to change parameters
In this mode, all symbols are shut off, except for the
following fields:
888
indicates the value of the parameter currently be-
ing changed;
88:88
indicates the name of the parameter currently
being changed;
To set the parameters proceed as follows:
88:88
1 -The field
is flashing. Select the parameter you
need to change using the UP/DOWN keys, then press
TEMP.
88:88
2 -The field
is flashing. Set the desired value using
the UP/DOWN keys, then press TEMP.
3 -Repeat the actions from point 1 to complete all of the
desired operations.
4 -To exit parameter change and save the changes that
have been made, simply keep TEMP pressed down
for 3 seconds.
Fig. 7-1
135
To exit parameter change without saving the changes that
have been made, simply wait 60 seconds after pressing
the last key, or press SLEEP. 45 seconds after pressing the
last key the name of the parameter or the numerical value
will flash. If the parameters regarding communication
(Ad01) are changed, communication will be re-initialised
from the zone control.
Below we provide the meanings for the operating pa-
rameters:
Ad01 - Network address for the zone control (1÷32)
- Default 2;
Ad02 - Supervisor address - (Do not change)
Br01 - Baud rate - (Do not change)
Br02 - Baudrate supervision - (Do not change)
En01 - Enable buzzer (0÷1) - Default 1.
Pc01 - Room probe calibration - (Do not change)
30
rEL - Release firmware indication - (Do not change)
Prot - Select protocol - (Do not change)
The required addresses are:
21 = Zone 1
22 = Zone 2
23 = Zone 3
24 = Zone AT
N.B.: The zone control cannot be used to programme
the time periods, which can only be programmed on
system manager, but it will be possible to manage the
request to operate the zone being referred to manually
by setting the desired set.
7.2
NOTES FOR REMOTE
ZONE CONTROL
Please refer to the relevant instructions sheet for instal-
lation instructions. The required addresses to use are:
31 = Zone 1
32 = Zone 2
33 = Zone 3
34 =
Zone AT
On the zone remote control it is possible to set:
- operation mode.
- room set point.
- room humidity set point.
The following can also be displayed:
- zone room temperature.
- relative humidity.
- current DHW set.
- zone flow set.
- generic alarm signal.
- activation of:
-
heat pump.
-
boiler.
-
zone antifreeze.
-
zone pump.
-
zone dehumidification.
44