Cascade parameter
Battery manage
Simultaneous
Fig. 5-54
- Activation band. The cascade generators are activated/
deactivated if the common delivery probe is outside the
set-point range ± temperature / 2 set (E.g. 45° flow 10
set-point, range = 40 ÷ 50 °C).
Cascade parameter
Activation Band to
start or stop on HP
in the battery:
Fig. 5-55
- Heating mode. In case of heating or cooling mode it
corresponds to the wait time before the activation or
deactivation of a machine.
Cascade parameter
Heat mode
Activat. time : 000 min
Deactiv. time: 000 min
Fig. 5-56
C01
C02
10.0°C
C03
32
- DHW mode. In case of DHW request it corresponds
to the wait time before the activation of a machine.
Cascade parameter
Sanitary mode
Activat. time :
Deactiv. time:
Fig. 5-57
N.B.: the total activation time (DHW and heating) of
the machines in set configuration must be less than the
integration time (if present).
- Reversing period. In presence of several heat pumps
one can perform a rotation in the activation of the first
heat pump in the cascade management. The parameter
sets the for how many days the heat pump stays the first
one to be activated.
Cascade parameter
Period used to reverse
the rotation of
the hp:
Fig. 5-58
C04
000 min
000 min
C05
0 day/s