S o l a r
s y s t e m
Collector
Max. temp: 140.0°C
Fig. 5-34
- Limit t. Oce this value has been exceeded the solar
circuit pump stops working.
S o l a r
s y s t e m
Collector
COOLING
Enable: Yes
Max. T.: 120.0°C
Fig. 5-35
- Enable:(Yes / No). This forces the solar pump to exceed
the set max T. even if the set max T. for the domestic
hot water is reached (it avoids stagnating);
- Max t. The solar circuit pump starts working again to
cool the solar manifold when this value is exceeded. The
pump switches off if the temperature of the manifold
decreases or if the temperature of the storage tank
reaches 90°C. In any case, the limit set in the "W05"
screen of (Fig. remains. 5-34).
N.B.: As soon as the temperature of the manifold falls
below the set set-point this function is disabled. The
storage tank's cooling system is also enabled when the
temperature of the solar manifold falls 5°C below that
of the storage tank.
S o l a r
s y s t e m
Collector
OUTPUT TEMPERATURE
Enable: Yes
Min. T.: 10.0°C
Fig. 5-36
- Enable: (Yes / No);
- T. min.: (10÷90°C) the solar circuit pump is enabled
to start operating only if the temperature set on the
manifold is reached.
W 0 5
S o l a r
Collector
ANTIFREEZE PROT.
Enable: Yes
Min. T.: 04.0°C
Fig. 5-37
- Enable (Yes / No). This allows the pump to be enabled
to start heating the solar manifold in case of very low
temperatures.
W 0 6
- Min.t. (-10÷10°C). The solar circuit pump is enabled
to start working if the external temperature falls below
this value.
S o l a r
Solar return probe
Enable: Yes
Fig. 5-38
- Enable (Yes / No). This allows the probe located on
the solar circuit return to start working; The measured
value will only be displayed.
• Integration. In this section it is possible to define
auxiliary sources to be used to integrate the central
heating or integration mode of action.
Press the arrows
Press the
I n t e g r a t i o n
W 0 7
Integration info
Disp.:
Integr.: Contemporarly
Fig. 5-39
- Type of integration. (Gas boiler, electric resistance); type
of boiler integration:
- room thermostat connection;
- external probe connection
- connection with Modbus protocol.
28
s y s t e m
s y s t e m
and select "08. Integration".
button to enter the submenu.
ELECTRIC RES.
W 0 8
W 0 9
X 0 1