Immergas System Manager Kit Instructions And Warnings
Immergas System Manager Kit Instructions And Warnings

Immergas System Manager Kit Instructions And Warnings

Hide thumbs Also See for System Manager Kit:
Table of Contents

Advertisement

Quick Links

System
IE
Instructions and
Manager Kit
warnings
Installer
User
Electronic control
Maintenance technician

Advertisement

Table of Contents
loading

Summary of Contents for Immergas System Manager Kit

  • Page 1 System Instructions and Manager Kit warnings Installer User Electronic control Maintenance technician...
  • Page 3 Dear Customer, We wish to complement you for having chosen a top-quality Immergas product, that can assure you long-term well-being and safety. As an Immergas customer you can also count on Qualified Post-Sales Service, prepared and updated to guarantee constant efficiency of your "System Manager Kit".
  • Page 4: Table Of Contents

    1.4.3 Operation in summer mode with cooling......................10 1.4.4 Operation in winter mode .............................10 1.4.5 Room antifreeze function ............................11 Programming the “system manager kit” ....................12 Domestic hot water temperature setting ......................12 Domestic hot water temperature setting on boiler side ..................13 Setting comfort and reduced room temperature ....................13...
  • Page 5 INDEX PAGE Wiring diagrams ........................... 55 System manager - power supply connection......................55 System manager - connection to Audax Top 6/8/12/16 ErP................55 System manager - connection to Audax Top 18/21 ErP..................56 System manager - connection to Magis Pro and Magis Combo..............56 System manager - connection to boiler through TA input.
  • Page 6: Foreword

    • The instruction manual must be considered a part of the “System Manager Kit” and must be “kept for future reference”. • The “System Manager Kit” is intended only for the use for which it has been expressly designed. Any other use must be considered improper and therefore dangerous.
  • Page 7: Descriptions Of Controls

    DESCRIPTIONS OF CONTROLS Fig. 1-1 BUTTONS DESCRIPTION Key: 1. Button to change the operating mode summer/ The button (1 Fig. 1-1) allows you to change the operating winter/stand-by ( mode of the system, specifically: • Summer (only DHW management). 2. Access button to submenus ( •...
  • Page 8: Description Of The Display Screen

    - Programming menu for clock and time periods (4 daily enabled; on-off time periods for the comfort temperature); - “Info” menu, to view the “System Manager Kit” input comfort temperature is active; data (ex. external temperature, flow temperature, set flow temperature, DHW temperature, solar storage operating with energy savings programme (re- tank probe temperature);...
  • Page 9: Start-Up

    The antifreeze function is also provided in the mode: 00.0 % stand-by, summer and winter. 1.4.1 Functioning in stand-by mode With the “System Manager Kit” in stand-by mode, the Fig. 1-2 symbol is displayed (see Fig. 1-5). The system can only work in case of room antifreeze request.
  • Page 10: Operation In Summer Mode With Cooling

    (see Paragraph 2.3). (see Paragraph 2.3). The “System Manager Kit” is factory set as shown in The “System Manager Kit” is factory set as shown in the table below. If this should not satisfy requirements, the table below.
  • Page 11: Room Antifreeze Function

    1.4.5 Room antifreeze function Note: this function is only active in the winter, stand-by and summer mode. The antifreeze function has maximum priority with respect to other settings. When ambient temperature drops below 5°C a central heating request at minimum setting is made.
  • Page 12: Programming The "System Manager Kit

    PROGRAMMING THE 08:50 10/06/11 “SYSTEM MANAGER KIT” Programming of the “System Manager Kit” allows to set/ (Hou..clips dis.) modify the following parameters: Set COMFORT: 00 °C - DHW temperature setting; Set ECO 00 °C - comfort and low temperature levels;...
  • Page 13: Domestic Hot Water Temperature Setting On Boiler Side

    DOMESTIC HOT WATER TEMPERATURE S e t r o o m S 0 2 SETTING ON BOILER SIDE SUMMER WITH FREEZ- ZN 2 From the main screen, press arrows until the boiler side domestic hot water temperature figure is Comfort: 25.0 °C displayed (Fig.
  • Page 14: User Settings

    USER SETTINGS U s e r s e t t i n g D 0 3 Press the button to enter the navigation menu. Electric energy prices Press buttons until selecting menu “02. SET. USER”. Elet.F1: 000.00 c€/kWh N a v i g a t i o n m e n u Elet.F2: 000.00 c€/kWh...
  • Page 15: Programming Operating Time In Comfort Mode

    - “Fancoil” in winter. The option exclusively allows fan Press arrows to confirm (YES) or cancel coils to be used in winter operation mode. This option (NO) any option. Press the button to validate may only be selected if it is provided for in the system the modification.
  • Page 16: Weekly Hourly Program

    For convenient selection, the bottom part displays the Press the button to enter the menu. graphics of the relevant calendar being selected (Fig. Press buttons to access screen “Comfort T. 2-18). Ranges”. T . c o m f o r t c l i p s K 0 6 T .
  • Page 17 Proceed in the same way to set the end date of the holiday. The start and end date (restart will take place on the end date) will disable DHW and central heating/cooling op- eration; central heating is set at 5°C (all zones) to control ambient antifreeze.
  • Page 18: Information

    INFORMATION - Dew point Info DEW POINT Press the button to access the programming menu. Press buttons until selecting menu “04. INFO” Zone 01: 00.0 °C (Fig. 3-1). N a v i g a t i o n m e n u TIME PROGRAMS Fig.
  • Page 19 - Puffer temperature - Machine efficiency Info Info COP calculation Puffer temperature Minimum: 02.00 Puffer set: 00.0 °C Audax 1: 02.93 Puffer temp.: 00.0 °C 1: 3.52 2: 2.97 Plant circ.: 3: 4.01 4: 2.98 Pre-heating: Fig. 3-12 Fig. 3-8 - Additional functions probes temperature - Tonnes of CO saved by using the heat pump...
  • Page 20: Diagnostics And Errors

    00.0 °C As well as the error codes referring to the functioning 00.0 % A0036 state of the system, the“System Manager Kit” also checks its own functioning state, indicating any malfunctions. RESET ERRORS Press the button to display the “Alarms log” or via Fig.
  • Page 21: Assistance Menu

    (example: Audax Top 6 ErP submenus are protected by a code (which can be used connected to the system manager). exclusively by the Immergas technician) while others are also visible to the user. Information The submenus that are available to the user are: Heat pump 1 •...
  • Page 22: Functions Protected By Code

    • Operating hours. It is possible to read the operating • System definition. Within this menu it is possible to hours of the heat pump, the auxiliary central heating set the features of the system that need to be managed. and the solar pump.
  • Page 23 Using the screen shown here below it is possible to choose S y s t e m d e f i n i t i o n P 0 2 which zone will be displayed in the user's main menu. Zone 01: HEAT S y s t e m...
  • Page 24 - Number of pumps. (1 pump, 2 pumps, solar disabled). Attention: if the generator switch-off signal is active, the cooling stage is also deactivated. It is possible to select the options for the solar heating in- tegration function (Puffer) with the screen shown below. System definition S y s t e m d e f i n i t i o n...
  • Page 25 - Max Heat.corr. Max correction during central heating R e g u l a t i o n T 0 1 mode. - Cool.Max corr. Max correction during cooling mode. Enable external temperature probe System definition Setpoint correction NOT USED Upd.
  • Page 26 - Set max. / Max. external. It lets you set maximum and R e g u l a t i o n T 0 5 maximum external temperature of the zone in high External temp. limit temperature. Heating phase The device leaves the factory set up with the following curves: Min ext.: 00.0 °C...
  • Page 27 Anti-legionel. Function that takes the DHW storage S o l a r s y s t e m W 0 1 tank temperature to 65°C. Function possible only with boiler or electric resistance integration. Solar pump 1 D H W Q 0 3 Anti-legionel ∆T on.:...
  • Page 28 S o l a r s y s t e m W 0 5 S o l a r s y s t e m W 0 8 Collector Collector ANTIFREEZE PROT. Max. temp: 140.0°C Enable: Yes Min. T.: 04.0°C Fig.
  • Page 29 N.B.: When the high temperature zone is enabled it is - Settings. It allows setting: only possible to choose gas boiler. Based on the type of - DHW wait time. It is the maximum wait time before boiler available, it is possible to choose whether it can activating the DHW integration.
  • Page 30 R e s e t c o u n t e r R 0 1 I n t e g r a t i o n X 0 6 Reset? Sanitary integr. info Heating pump: Integration: Sanitary integr: Solar pump 1: Sanitary hyst.: 20.0°C Solar pump 2:...
  • Page 31 • Cascade parameters. This menu is activated only if the M a n u a l A 0 6 heat pumps are more than one (max. 4). The manager EXP. OPTIONAL deals with the activation and deactivation of the heat Solar pump 2: pumps according to the parameters set and to a possible H.T.
  • Page 32 - DHW mode. In case of DHW request it corresponds Cascade parameter to the wait time before the activation of a machine. Battery manage Cascade parameter Sanitary mode Simultaneous Activat. time : 000 min Deactiv. time: 000 min Fig. 5-54 - Activation band.
  • Page 33 - Orientation. In presence of several heat pumps com- In case of configuration problems, the initial address of a machine can be restored (address 11). municating with each other, setting the machines with different addresses is required. Cascade parameter Reset Audax Top Machine Address Type: 18/21 ErP...
  • Page 34: List Of Programmable Parameters

    LIST OF PROGRAMMABLE PA- RAMETERS “Main” menu. n° Range Value Value Description parameter adjustment default customis. Stand-by, Summer, Air Functioning modes Stand-by conditioning, Winter DHW time program0.s No / Yes Set DHW manual 10 - 60 Set DHW comfort 10- 50 (60 with boiler) Set DHW ECO 10- 50 (60 with boiler) Set DHW boiler (separate circuit)
  • Page 35 “User settings” menu. n° Range Value Value Description parameter adjustment default customis. Party mode No / Yes Type of gas Methane / LPG Methane Gas price 1 - 900,00 c€ 100.00 Gas price 1 - 900,00 c€ 70.00 Unit of measurement LPG gas m3 / l / kg litre F1 Electricity price...
  • Page 36 “Clock” menu. n° Range Value Value Description parameter adjustment default customis. Time 0 - 23 Minutes 0 - 59 Monday / Tuesday / Wednesday / Thursday Day of the week / Friday / Saturday / Sunday Day of year 1 - 31 Month of year 1 - 12 Year...
  • Page 37 n° Range Value Value Description parameter adjustment default customis. CAL1, CAL2, Zone 1: Tuesday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 1: Wednesday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 1: Thursday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 1: Friday CAL1 CAL3,CAL4 CAL1, CAL2, Zone 1: Saturday CAL1 CAL3,CAL4 CAL1, CAL2,...
  • Page 38 n° Range Value Value Description parameter adjustment default customis. CAL1, CAL2, HT Zone: Friday CAL1 CAL3,CAL4 CAL1, CAL2, HT Zone: Saturday CAL1 CAL3,CAL4 CAL1, CAL2, HT Zone: Sunday CAL1 CAL3,CAL4 CAL1, CAL2, DHW: Monday CAL1 CAL3,CAL4 CAL1, CAL2, DHW - Tuesday CAL1 CAL3,CAL4 CAL1, CAL2,...
  • Page 39 n° Range Value Value Description parameter adjustment default range Absent, Rem. Control, Remote panel, Zone Disp. Remote panel Control, Temp-humid probe Thermostat No / Yes Humidistat No / Yes P. Dew Point No / Yes En. Dehumid. No / Yes Mode Hot, Cold, Hot/Cold Zone name...
  • Page 40 n° Range Value Value Description parameter adjustment default range Audax Top 6 / 8 / 12 Audax Top 6 / 16 / Audax Top 6 Audax 2017 / - - Audax 6 / 8 / 10 / 16 Audax Top 6 Magis Pro Configuration Two pipes / Four pipes Two pipes...
  • Page 41 n° Range Value Value Description parameter adjustment default range System decoupling Yes/No System probe Yes/No Photovoltaic Yes/No Activation time 1-120 Increase time 1-20 Max Heat correction 0-10 Max Cool correction 0-10 Activation time 1-120 Increase time 1-20 Max Heat correction 0-10 Max Cool correction 0-10...
  • Page 42 n° Range Value Value Description parameter adjustment default customis. Isteresi sanitario (DHW hysteresis) 3 - 7 DHW circuit Separate, Common Common Legionella enabling No / Yes Legionella cycle day Monday, Tuesday, Monday Wednesday, Thurs- day, Friday, Saturday, Sunday Legionella cycle time 00:00 - 24:00 07:00 DHW recirculation enabling...
  • Page 43 n° Range Value Value Description parameter adjustment default customis. DHW wait time 1 - 540 min Central heating wait time 1 - 540 min Domestic hot water priority time 1 - 540 min Central heating priority time 1 - 540 min Integration band 0 - 20 Minimum integration temperature...
  • Page 44: Notes For Zone Devices

    NOTES FOR ZONE To exit parameter change without saving the changes that have been made, simply wait 60 seconds after pressing DEVICES the last key, or press SLEEP. 45 seconds after pressing the NOTES FOR ZONE CONTROL last key the name of the parameter or the numerical value will flash.
  • Page 45 The zone remote control manages the heating/cooling Ignition. Press and hold the “on / off ” button; the of the associated zone. remote control goes into stand-by and displays the operating modes, the room temperature and the time. The functions valid for the secondary remote zone con- trol are enabled with: - Buttons to the side of the display (Ref.
  • Page 46 Fig. 7-5 Fig. 7-7 N.B.: when selecting the temperature relating to the time Select the function and adjust the time slots. slot, one can also set the boiler in OFF mode “ ” that - Select the interval of days that one wishes to program, allows to switch the boiler off in the pre-set time interval.
  • Page 47: Notes For Remote Zone Panel

    Function lock. In conjunction with the activation of the By pressing the new selector, the zone flow set and the time slots, the manual room temperature control mode system active dhw set can be displayed. is disabled; this status is signalled by the activation of the Anomalies display.
  • Page 48 12:34 Fr 3 Jan 2014 20.6 °C 13°C Room set 21.0°C Mode Menu Key: 1 - Main parameters switch with button to confirm and save data 2 - Left context button 3 - Right context button 4 - Display Fig. 7-12 Once the device has been powered, it goes into the Dehumidify and cool room in progress status prior to switch-off.
  • Page 49 The lower part of the display shows the parameter that can be changed (it varies according to configuration). Once the system has captured the data (indicated with the text “Attesa dati... ” (Waiting for data...), it is possible to change the value by turning the main switch and pressing to confirm the parameter change.
  • Page 50 - Once you have accessed the menu, adjust the various • Time programme. Time slots (Calendars from 1 to 4) items highlighted by turning the main switch. Set the are assigned to Zones in these menus. You can assign value and save it by pressing the main switch. Each the calendar to a single day or to a group of days.(single time it is saved, it moves to the next item.
  • Page 51 Fig. 7-17 Menu Set Point Zona [ ... ] Orologio e Programmi [ ... ] Informazioni [ ... ] Assistenza [ ... ] Lingua [ ... ] Esci Indietro Hereunder is a list of available menus MAIN MENU Menu item Description Zone Set Point Defines the operating parameters to manage the zone...
  • Page 52 Clock and programs menu Customised Menu item Description Range Default value Defines the time range for operation in Time slots Comfort and Economy mode Mon - Zone Program Time zone scheduling Cal 1 Information Menu Menu item Description Outside temperature External temper.
  • Page 53: Notes For Heat Pumps Board

    NOTES FOR HEAT PUMPS NOTES FOR MAGIS COMBO The A11, T02 parameters and the parameter families BOARD UXX, RXX, IXX are automatically set by the system Using the manager involves modifying the addresses manager. contained within heat pumps (see heat pump booklet). Settings required: The required addresses are: - A12 = OFF;...
  • Page 54 Certain manual functions of the machine can be enabled. Definit. System Audax Top 18/21 - N.1 Manual management Reduction function Audax Top 18/21 - N.1 circulation pump test Enabl. Reduction: Power in reduced: 000 % circulation pump sp. Flow switch: Fig.
  • Page 55: Wiring Diagrams

    WIRING DIAGRAMS SYSTEM MANAGER - POWER SUPPLY CONNECTION. Fig. 9-1 POWER SUPPLY ALIMENTAZIONE 230 Vac 50 Hz PWM 0/10V J8 ISOLATED input voltage: 24Vac (+10%-15%); 50/60Hz 48Vdc (36Vmin...71Vmax) max power:8VA/6W Key: A13 - System manager T1 - Class II transformer of at least 30 VA with 24 Vac output voltage (not supplied with the System manager) Note: - Max.
  • Page 56: System Manager - Connection To Audax Top 18/21 Erp

    SYSTEM MANAGER - CONNECTION TO AUDAX TOP 18/21 ERP. Fig. 9-3 J8 ISOLATED GNX + - Modbus Connection Collegamento Modbus Shielded type cable cavo schermato tipo AWG 20/22 AUDAX TOP 18/21 ErP Key: A13 - System manager SYSTEM MANAGER - CONNECTION TO MAGIS PRO AND MAGIS COMBO. Modbus type connection Fig.
  • Page 57: System Manager - Connection To Boiler Through Ta Input

    SYSTEM MANAGER - CONNECTION TO BOILER THROUGH TA INPUT. Fig. 9-5 PWM 0/10V J8 ISOLATED Key: A13 - System manager A3 - Boiler board (generic) input voltage: K2 - Relay EMR 12 V DC 24Vac (+10%-15%); 50/60Hz 48Vdc (36Vmin...71Vmax) max power:8VA/6W Note: - The K2 relay contact must be connected to the boiler TA clamps SYSTEM MANAGER - CONNECTION TO SUPERIOR ERP BOILER THROUGH EXTERNAL...
  • Page 58: System Manager - Connection To Victrix Tt Boiler Through External Probe Input

    SYSTEM MANAGER - CONNECTION TO VICTRIX TT BOILER THROUGH EXTERNAL PROBE INPUT. Fig. 9-7 Cable section ≥ 1 mm Key: A13 - System manager PWM 0/10V A3 - Boiler P.C.B. J8 ISOLATED Note: - In the boiler configuration menu set parameter “P7” “external probe correction”...
  • Page 59: System Manager - Expansions Power Supply Connection

    SYSTEM MANAGER - EXPANSIONS POWER SUPPLY CONNECTION. Fig. 9-9...
  • Page 60: System Manager - Expansion Communication Cable Connection

    9.10 SYSTEM MANAGER - EXPANSION COMMUNICATION CABLE CONNECTION. Fig. 9-10 Serial Address 1 2 4 8 Expanding Adresses Indirizzi Espansione Serial Address 1 2 4 8 Address Indirizzo 1 1 2 4 8 Address Indirizzo 2 1 2 4 8 Address Indirizzo 3 1 2 4...
  • Page 61: System Manager - Ta Request Connection With 1 Fixed Zone

    9.11 SYSTEM MANAGER - TA REQUEST CONNECTION WITH 1 FIXED ZONE. Fig. 9-11 PWM 0/10V J8 ISOLATED Key: A13 - System manager TA - Request contact from system input voltage: 24Vac (+10%-15%); 50/60Hz 48Vdc (36Vmin...71Vmax) max power:8VA/6W 9.12 SYSTEM MANAGER - CONNECTION TO 1 SLOPING ROOF THERMAL SOLAR SYSTEM. Fig.
  • Page 62: System Manager - Connection To 2 Sloping Roofs Thermal Solar System

    9.13 SYSTEM MANAGER - CONNECTION TO 2 SLOPING ROOFS THERMAL SOLAR SYSTEM. Fig. 9-13...
  • Page 63: System Manager - Solar Return Probe Connection

    M50 - DHW priority valve (2 points) B2 - Storage tank upper part probe Note: - The B2 probe is fitted as standard on input voltage: 24Vac (+10%-15%); 50/60Hz the Immergas storage tanks 48Vdc (36Vmin...71Vmax) - Control (J10): max power:8VA/6W Open -> switch to system Closed ->...
  • Page 64: System Manager - Connection To Electric Dhw Integration Resistance

    R2: - Activation relay DHW resistance integration, type EMR 12Vdc R3: - Support relay EMR 230/24Vac 16A (not supplied) Note: - The B2 probe is fitted as standard on the Immergas storage tanks. 9.17 SYSTEM MANAGER - CONNECTION TO ELECTRIC CENTRAL HEATING INTEGRATION RESISTANCE.
  • Page 65: System Manager - Puffer Probe Connection

    9.18 SYSTEM MANAGER - PUFFER PROBE CONNECTION. Power Supply Fig. 9-18 ALIMENTAZIONE 230 Vac 50 Hz PWM 0/10V J8 ISOLATED J9 input voltage: 24Vac (+10%-15%); 50/60Hz 48Vdc (36Vmin...71Vmax) max power:8VA/6W A15 - 4 Serial Address 1 2 4 8 Serial Address 24Vac 1 2 4 8...
  • Page 66: System Manager - Three-Way Integration Connection In Systems With Puffer

    9.20 SYSTEM MANAGER - THREE-WAY INTEGRATION CONNECTION IN SYSTEMS WITH PUFFER. Fig. 9-20 Power Supply ALIMENTAZIONE 230 Vac 50 Hz A (caldaia) Boiler Heating Pump AB (puffer) B (pompa di calore) Boiler A (caldaia) Heating Pump B (pompa di calore) AB (puffer) Indirizzi Addresses...
  • Page 67: System Manager - Expansion Zone Pump Connection

    9.21 SYSTEM MANAGER - EXPANSION ZONE PUMP CONNECTION. Fig. 9-21 Key: A15 - Zone expansion kit M10 - Zone pump Note: - Configure the expansion address as indicated Expanding Addresses Indirizzi Espansione Serial Address 1 2 4 8 Address Indirizzo 1 1 2 4 8 Serial Address...
  • Page 68: System Manager - Expansion Zone Mixer Connection

    9.23 SYSTEM MANAGER - EXPANSION ZONE MIXER CONNECTION. Fig. 9-23 Close chiude Key: A15 - Zone expansion kit M31 - Zone mixing valve Note: - Configure the expansion address as indicated Expanding Addresses Indirizzi Espansione Serial Address 1 2 4 Address Indirizzo 1 Serial...
  • Page 69: System Manager - Connection To Zone Room Thermostats

    9.25 SYSTEM MANAGER - CONNECTION TO ZONE ROOM THERMOSTATS. Fig. 9-25 Key: A15: - zone expansion kit S20 - Zone room thermostat or potential-free contact to request Note: - Configure the expansion address as indicated. Indirizzi Addresses Serial Espansione Expanding Address 1 2 4 8 Indirizzo 1...
  • Page 70: System Manager - Connection To Dehumidifier Kit

    9.26 SYSTEM MANAGER - CONNECTION TO DEHUMIDIFIER KIT. Fig. 9-26...
  • Page 71: System Manager - High-Temperature Zone Valves Connection

    9.27 SYSTEM MANAGER - HIGH-TEMPERATURE ZONE VALVES CONNECTION. Fig. 9-27 Power Supply ALIMENTAZIONE 230 Vac 50 Hz Key: A15 - Address 4 zone expansion kit Y5 - High temperature two-way valve Y6 - Low temperature two-way valve Note: - Configure the expansion address as indicated A15-4 Addresses...
  • Page 72: System Manager - Thermal Discharge Connection

    9.29 SYSTEM MANAGER - THERMAL DISCHARGE CONNECTION. Power Supply ALIMENTAZIONE Fig. 9-29 230 Vac 50 Hz Key: A15-5 - Address 5 zone expansion kit M7 - Thermal discharge circulator pump B22 - Boiler source probe B33 - Cold source probe Note: - Configure the expansion address as indicated A15 - 5...
  • Page 73: System Manager - Audax Top 6/8/12/16 Erp Coil Connection

    9.31 SYSTEM MANAGER - AUDAX TOP 6/8/12/16 ERP COIL CONNECTION. Fig. 9-31 Key: A13 - System manager PWM 0/10V J8 ISOLATED Note: - The set addresses are configured on the system manager. input voltage: 24Vac (+10%-15%); 50/60Hz 48Vdc (36Vmin...71Vmax) max power:8VA/6W Modbus type connection AWG 20 / 22 type shielded cable AUDAX TOP ErP 1...
  • Page 74: System Manager - Audax Top 18/21 Erp Coil Connection

    9.32 SYSTEM MANAGER - AUDAX TOP 18/21 ERP COIL CONNECTION. Fig. 9-32 Key: AUDAX TOP 18/21 ErP A13 - System manager n°1 Note: - The set addresses are configured on the system manager. Modbus type connection AWG 20 / 22 type shielded cable AUDAX TOP 18/21 ErP n°2 PWM 0/10V...
  • Page 75: System Manager - Connection To Humidistat

    9.33 SYSTEM MANAGER - CONNECTION TO HUMIDISTAT. Fig. 9-33 Key: A15 - Zone expansion kit S50 - Zone humidistat On/Off Note: - Configure the expansion address as indicated Expanding Addresses Indirizzi Espansione Serial Address 1 2 4 8 Indirizzo 1 Address 1 2 4 8 Address...
  • Page 76: System Manager - Connection To Boiler Alarm Signal

    9.35 SYSTEM MANAGER - CONNECTION TO BOILER ALARM SIGNAL. Fig. 9-35 PWM 0/10V J8 ISOLATED input voltage: 24Vac (+10%-15%); 50/60Hz 48Vdc (36Vmin...71Vmax) max power:8VA/6W Key: A13 - System manager Note: - If you wish to connect a boiler alarm signal, remove the jumper and bring the alarm signal on clamps B6 - GND.
  • Page 77: System Manager - Connection To Photovoltaic System

    9.37 SYSTEM MANAGER - CONNECTION TO PHOTOVOLTAIC SYSTEM. Fig. 9-37 Key: A15-5 - Zone expansion kit with address 5 PV - On/Off contact from photovoltaic system Note: - Configure the expansion address as indicated. A15-5 Addresses Indirizzi Serial Expanding Espansione Address 1 2 4 8 Serial...
  • Page 78: System Manager - Connection To Zone Remote Controls

    9.38 SYSTEM MANAGER - CONNECTION TO ZONE REMOTE CONTROLS. Fig. 9-38...
  • Page 79: System Manager - Connection To Zone Remote Panels

    9.39 SYSTEM MANAGER - CONNECTION TO ZONE REMOTE PANELS. Fig. 9-39 PWM 0/10V J8 ISOLATED input voltage: 24Vac (+10%-15%); 50/60Hz Remote zone panel 48Vdc (36Vmin...71Vmax) Pannello remoto di zona max power:8VA/6W Key: A3 - System manager Zone remote panel: control panel (by default with Audax Top ErP) 9.40 SYSTEM MANAGER - CONNECTION TO THERMOFLUE.
  • Page 80: System Manager - Connection To Domotics With Digital Signals

    9.41 SYSTEM MANAGER - CONNECTION TO DOMOTICS WITH DIGITAL SIGNALS. Fig. 9-41 Key: A15 - Zone expansion kit with address 5 A26 - Domotic system. Note: - Configure the expansion address as indicated. - Contact “domotics” management is executed using the following configurations: Stand-by Winter Summer...
  • Page 81: System Manager - Connection To Domotics With Communication Protocol

    9.42 SYSTEM MANAGER - CONNECTION TO DOMOTICS WITH COMMUNICATION PROTOCOL. Fig. 9-42 PWM 0/10V Domotics manage- J8 ISOLATED ment system input voltage: 24Vac (+10%-15%); 50/60Hz Serial Card 1 48Vdc (36Vmin...71Vmax) max power:8VA/6W Key: Note: - Communication protocols: Winload A3 - System manager Carel Modbus 9.43 SYSTEM MANAGER - CONNECTION TO COMMON FLOW PROBE.
  • Page 82: List Of Anomalies

    LIST OF HT Zone room temperature probe A0128 ANOMALIES. malfunction alarm A0129 Zone 1 humidity probe anomaly A0130 Zone 2 humidity probe anomaly Alarm Alarm Description A0131 Zone 3 humidity probe anomaly Code A0133 Zone 1 dehumidifier fault alarm Domestic hot water boiler/inlet probe A0012 A0134 Zone 2 dehumidifier fault alarm...
  • Page 84 NOTE: correct periodic maintenance is highly recommended. Follow us on Immergas Italia Immergas TOOLBOX The App designed by Immergas for professionals immergas.com To request further specific details, sector Professionals can also use the following e-mail address: consulenza@immergas.com Immergas S.p.A.