1.16 ANTIFREEZE PROTECTION.
Assembly instructions.
- Wind the heating cable (d13) around the con-
nection pipes and safety valve.
- The wiring of the antifreeze kit must be
connected to the indoor unit as shown in the
relative instruction booklet.
Attention: the graphic representation of the
heating cable is purely indicative.
Minimum temperature -5°C.
The electronics of the indoor unit comes standard
with an antifreeze function that activates the elec-
tric resistance when the temperature in the Solar
Container or Domus Container falls below 4°C.
The antifreeze function is only guaranteed if:
- the indoor unit is connected properly to the
electrical circuit and is constantly powered;
- the essential components are not faulty.
In these conditions the product is protected against
freezing up to an ambient temperature of -5°C.