Example (change Description to main_hall, and reinitialize the BACnet
stack):
>pass 9000
>bacnet description main_hall
Description
>bacnet reinit
Reinitialize signaled to BACnet stack.
Set CO
Indicator LED Parameters
2
On transmitter models with indicator LEDs, you can use the TRAF
command to show or set CO
LEDs off.
TRAF [step1 step2 step3]<cr>
TRAF [quant]<cr>
where
step1
= The yellow LED is lit above this ppm limit (default 800).
step2
= The red LED is lit above this ppm limit (default 1200).
step3
= The red LED starts blinking above this ppm limit
(default 5000).
quant
= Quantity that controls the LEDs. Options are:
CO2 – LEDs controlled by CO
NONE – LEDs disabled.
Example (set indicator LED limits to 900, 1500 and 5000 ppm):
>traf 900 1500 5000
Traffic quantity
Traffic step 1
Traffic step 2
Traffic step 3
Traffic threshold
>
Example (disable indicator LEDs):
>traf none
Traffic quantity
Traffic step 1
Traffic step 2
Traffic step 3
Traffic threshold
>
: main_hall
indicator LED limits. You can also turn the
2
level (default).
2
: CO2
: 900.00 ppm
: 1500.00 ppm
: 5000.00 ppm
: 20.00 ppm
: Disabled
: 800.00 ppm
: 1200.00 ppm
: 5000.00 ppm
: 20.00 ppm