Set Bacnet Parameters - Vaisala CARBOCAP GMW90 Series User Manual

Carbon dioxide, temperature, and humidity transmitters
Hide thumbs Also See for CARBOCAP GMW90 Series:
Table of Contents

Advertisement

Chapter 4 _________________________________________________________________ Operation
VAISALA ________________________________________________________________________ 61

Set BACnet Parameters

Use the BACNET command to show or set some of the transmitter's
BACnet parameters. You can also use the BACNET command to
reinitialize the BACnet stack of the transmitter without having to reset or
power cycle the transmitter.
BACNET [parameter_name [parameter_value]] [reinit]<cr>
where
parameter_name = Name of the BACnet parameter to change.
parameter_value = New value of the parameter. See descriptions above
reinit
= Reinitializes the BACnet stack. Must be given as the
Example (show BACnet parameters):
>pass 9000
>bacnet
Instance
Name
Location
Description
Password
MAX_MASTER
COV_Interval
Autobaud_Interval
Available parameters are:
Instance: BACnet instance number. Unsigned value
in range 0 ... 4194302.
Name: BACnet Object_Name shown in the Device
object. String value, no spaces.
Description: BACnet Description shown in the
Device object. String value, no spaces.
Location: BACnet Location shown in the Device
object. String value, no spaces.
Password: Password used in ReinitializeDevice
service. String value, no spaces.
MAX_MASTER: Max_Master parameter in Device
object. Unsigned value, range 1 ... 127.
for allowed values.
only argument for the BACNET command.
: 6 (00000006h)
: GMW95R_ H2930002
: Location
: Description
: 1234
: 127 (007Fh)
: 0
: 10