Select Units; Analog Output Settings; Set Analog Output Mode - Vaisala CARBOCAP GMW90 Series User Manual

Carbon dioxide, temperature, and humidity transmitters
Hide thumbs Also See for CARBOCAP GMW90 Series:
Table of Contents

Advertisement

Chapter 4 _________________________________________________________________ Operation

Analog Output Settings

NOTE
NOTE
VAISALA ________________________________________________________________________ 43

Select Units

Use the UNIT command to select metric or non-metric output units.
Only affects data shown on the display and service port, has no effect on
the analog and digital outputs. This command is not available on the
digital output models (for example, GMW95).
UNIT [x]<cr>
Where
x
=
Selects the unit type to output:
m = metric units, for example, Celsius
n = non-metric units, for example, Fahrenheit
Example:
>unit m
Unit
If you want to change analog output settings, you must set the
transmitter's configuration DIP switch 8 to position Custom. If the
switch is set to DIP, the settings are view-only.
Commands for configuring analog outputs are not available on digital
output models (for example, GMW95).

Set Analog Output Mode

Use the AMODE command to set the analog output mode and error
level. Note that you cannot change between analog output types, for
example, from voltage to current output.
AMODE [channel lo_value hi_value error_value]<cr>
where
channel
= Analog output channel, 1 ... 3.
lo_value
= Low limit of the channel.
hi_value
= High limit of the channel.
error_value = Error value of the channel.
: Metric