Show Transmitter Status - Vaisala CARBOCAP GMW90 Series User Manual

Carbon dioxide, temperature, and humidity transmitters
Hide thumbs Also See for CARBOCAP GMW90 Series:
Table of Contents

Advertisement

Chapter 4 _________________________________________________________________ Operation
VAISALA ________________________________________________________________________ 39

Show Transmitter Status

Use the STATUS command to view detailed information on transmitter
model and configuration.
STATUS [function]<cr>
where
Function = Optional switch to display a more detailed status for
BACnet or Modbus protocol (available on transmitter
models with digital output). Available switches
are -bacnet and –modbus.
Example (display detailed BACnet status):
>status –bacnet
* BACnet module (BACNET) *
BACnet protocol
MAC
Device Instance
Name
Location
Description
MAX_MASTER
Node type
Baud setting
Current baudrate
Baudrate locked
Baud detection interval: 10 s
DCC
Valid frames
Invalid frames
Unwanted frames
Lost tokens
Failed TX
: active
: 0 (00h)
: 6 (00000006h)
: GMW95R_ H2930002
: Location
: Description
: 127 (7Fh)
: Master
: Auto
: 19200 8N1
: No
: Communication enabled
: 0
: 0
: 0
: 0
: 0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents