User's Guide _______________________________________________________________________
30 ___________________________________________________________________ M211659EN-C
Connecting a Common AC Power Supply
to Several Transmitters
If you are connecting a common 24 VAC power supply to several
transmitters, make sure to connect the same terminal to +Vs and –Vs on
all transmitters. This will avoid a short-circuit through the shared
common line at the controller; see Figure 20 below.
Supply
24 VAC
voltage
Supply
voltage
Figure 20
Connecting a Common AC Power Supply
GMW90
+Vs
OUT
Signal
output
GND
-Vs
GMW90
+Vs
OUT
Signal
output
-Vs
GND
CONTROLLER
Shared
common
line
1310-046