Electrical Information; Table 5 - Micropanel Power Supply; Table 6 - Voltage Range - York YLAA0285SE Manual

Air-cooled scroll chillers with microchannel condenser coils style a (50 hz) 57 - 142 ton
Table of Contents

Advertisement

FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
TABLE 5 – MICROPANEL POWER SUPPLY
UNIT VOLTAGE
UNIT
MODELS w/o
VOLTAGE
CONTROL
TRANS
-17
-28
MODELS w/
-40
CONTROL
-46
TRANS
-50
-58
A. Minimum #14 AWG, 75 °C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
It is possible that multiple sources of
power can be supplying the unit power
panel. To prevent serious injury or
death, the technician should verify
that NO LETHAL VOLTAGES are
present inside the panel AFTER dis-
connecting power, PRIOR to working
on equipment.
TABLE 6 – VOLTAGE RANGE
VOLTAGE CODE
-17
-28
-40
-46
-50
-58
JOHNSON CONTROLS

ELECTRICAL INFORMATION

CONTROL
MCA
POWER
NOTE A
115-1-60/50
15A
200-1-60
15A
230-1-60
15A
380-1-60
15A
460-1-60
15A
380/415-1-60
15A
575-1-60
15A
VOLTAGE RANGE
UNIT POWER
200-3-60
230-3-60
380/415-3-60
460-3-60
380/415-3-50
575-3-60
SECTION 5 – TECHNICAL DATA
OVER CURRENT PROTECTION,
SEE NOTE B
MIN
MAX
10A
15A
10A
15A
10A
15A
10A
15A
10A
15A
10A
15A
10A
15A
The unit evaporator heater uses
120VAC. Disconnecting 120VAC
power from the unit, at or below freez-
ing temperatures, can result in damage
to the evaporator and unit as a result
of the chilled liquid freezing.
MIN.
MAX.
180
207
342
414
342
517
NF DISC Sw
30 A / 240V
30 A / 240V
30 A / 240V
30 A / 480V
30 A / 480V
30A / 415V
30 A / 600V
220
253
440
506
440
633
49
5 5