SECTION 5 – TECHNICAL DATA
1 0 0 0
1 0 0
1 0
1
1
TABLE 3 – ETHYLENE & PROPYLENE GLYCOL CORRECTION FACTORS
ETHYLENE GLYCOL
TONS
% WEIGHT
COMPR
kW
10
0.985
0.997
20
0.981
0.996
30
0.974
0.995
40
0.966
0.991
50
0.957
0.989
Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges.
46

HEAT EXCHANGER FLOW, GPM

Y L AA E v a p o ra to r P re s s u re D ro p (S I U n its )
C
W a te r F lo w R a te (l/s )
CURVE
A
B
C
D
E
°
PRESS
GPM
F/
FREEZE PT
DROP
TON
24.1
1.034
26
24.9
1.062
16
26.1
1.096
5
27.5
1.134
-10
29.1
1.172
-32
A
B
1 0
MODEL YLAA
240SE, 195HE, 220HE
320SE, 360SE, 260HE, 300HE
400SE, 435SE, 350HE, 455HE
485SE, 440HE
390HE, 515HE
PROPYLENE GLYCOL
TONS
% WEIGHT
COMPR
kW
10
0.983
0.996
20
0.974
0.995
30
0.961
0.990
40
0.946
0.98
50
0.928
0.984
FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
D
E
1 0 0
°
PRESS
GPM
F/
FREEZE PT
DROP
TON
24.2
1.048
27
24.4
1.086
19
25.1
1.134
8
26.0
1.186
-5
27.2
1.247
-25