Liquid & Refrigerant Sensor Test Points; Table 25 - Entering/Leaving Chilled Liquid Temp. Sensor, Temperature/Voltage Correlation - York YLAA0285SE Manual

Air-cooled scroll chillers with microchannel condenser coils style a (50 hz) 57 - 142 ton
Table of Contents

Advertisement

SECTION 9 – SERVICE AND TROUBLESHOOTING
TABLE 25 – ENTERING/LEAVING CHILLED LIQUID
TEMP. SENSOR, TEMPERATURE/
VOLTAGE CORRELATION
VOLTAGE
TEMP °F
(Signal Input
to Return)
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
182
TEMP °C
1.33
-12
1.39
-11
1.46
-10
1.51
-9
1.58
-8
1.65
-7
1.71
-6
1.78
-4
1.85
-3
1.91
-2
1.98
-1
2.05
0
2.12
1
2.19
2
2.26
3
2.33
4
2.40
6
2.47
7
2.53
8
2.60
9
2.65
10
2.73
11
2.80
12
2.86
13
2.92
14
2.98
16
3.05
17
3.11
18
3.17
19
3.23
20
3.29
21
3.34
22
3.39
23
3.45
24
3.5
26
3.54
27
Liquid & Refrigerant Sensor Test Points
(Table 25)
Entering Chilled Liquid Sensor
J6-5 = +5VDC regulated supply to sensor.
J6-8 = VDC input signal to the I/O board. See
Table 25 for voltage readings that correspond
to specific liquid temperatures.
J6-2 =
drain (shield connection = 0VDC) Return
Leaving Chilled Liquid Temperature Sensor
J6-4 = +5VDC regulated supply to sensor.
J6-7 = VDC input signal to the microboard. See
Table 25 for voltage readings that correspond
to specific liquid temperatures.
J6-1 = drain (shield connection = 0VDC) Return
FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
JOHNSON CONTROLS