FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
Option 9 – Condenser Fan Control Mode:
F A N
C O N T R O L
D I S C H A R G E
Condenser fans are controlled by discharge pressure
only. This mode must be chosen.
or
F A N
C O N T R O L
A M B I E N T
&
Do not select this option on R-410A chillers.
Option 10 – Manual Override Mode:
M A N U A L
O V E R R I D E
D I S A B L E D
This option allows overriding of the daily schedule
that is programmed. MANUAL OVERRIDE MODE
– DISABLED indicates that override mode has no
effect.
or
M A N U A L
O V E R R I D E
E N A B L E D
Manual Override Mode is enabled. This is a service
function and when enabled, will allow the unit to
start when shut down on the daily schedule. It will
automatically be disabled after 30 minutes.
Option 11 – Current Feedback Options
Installed:
C U R R E N T
N O N E
This mode should be selected when the panel is not
equipped with current sensing capability.
or
C U R R E N T
O N E
P E R
This mode should be selected when an optional
2ACE Module is installed to allow combined current
monitoring of all systems by sensing current on the
incoming line.
or
JOHNSON CONTROLS
P R E S S U R E
D S C H
P R E S S
M O D E
M O D E
F E E D B A C K
F E E D B A C K
U N I T
C U R R E N T
O N E
P E R
This mode should be selected when an optional
2ACE module is installed to allow individual current
monitoring of each system. SYS 1 input is to J7 of the
I/O. SYS 2 input is to J8 of the I/O.
Option 12 – Power Fail Restart:
P O W E R
F A I L
A U T O M A T I C
Chiller auto restarts after a power failure.
P O W E R
F A I L
M A N U A L
After a power failure, the UNIT switch must be toggled
before restart at the unit is allowed. NORMALLY
MANUAL RESTART should NOT BE SELECTED.
Option 13 – Soft Start Enable/Disable:
S O F T
D I S A B L E D
SOFT START "DISABLED" MUST be selected on all
chillers.
This message may not be viewable on non-European
chillers.
Option 14 – Unit Type:
U N I T
L I Q U I D
The UNIT TYPE message cannot be modified under
the unit keys.
"LIQUID CHILLER" must be dis-
played, or damage to compressors or
other components will occur if oper-
ated in the HEAT PUMP or CON-
DENSING UNIT modes.
If unit type needs to be changed to make the unit a liquid
chiller, remove power and then remove the jumper
between J11-7 and J11-12 on the I/O Board. Reapply
power to the micropanel and the microprocessor will
store the change.
SECTION 7 – UNIT CONTROLS
F E E D B A C K
S Y S T E M
R E S T A R T
R E S T A R T
S T A R T
T Y P E
C H I L L E R