Program Key - York YLAA0285SE Manual

Air-cooled scroll chillers with microchannel condenser coils style a (50 hz) 57 - 142 ton
Table of Contents

Advertisement

FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020

PROGRAM KEY

There are several operating parameters under the
PROGRAM key that are programmable. These setpoints
can be changed by pressing the PROGRAM key, and
then the ENTER/ADV key to enter Program Mode.
Continuing to press the ENTER/ADV key will display
each operating parameter. While a particular parameter
is being displayed, the ↑ (UP) and ↓ (DOWN) arrow
keys can be used to change the value. After the value is
changed, the ENTER/ADV key must be pressed to enter
the data into memory. Table 11 shows the programmable
limits and default values for each operating parameter.
The following are the displays for the programmable
values in the order they appear:
D I S C H A R G E
d
C U T O U T
=
DISCHARGE PRESSURE CUTOUT is the discharge
pressure at which the system will shutdown as monitored
by the optional discharge transducer. This is a software
shutdown that acts as a backup for the mechanical high
pressure switch located in the refrigerant circuit. The
system can restart when the discharge pressure drops
40 PSIG (2.76 barg) below the cutout point.
If the optional discharge pressure transducer is not
installed, this programmable safety would not apply.
It should be noted that every system has a mechanical
high pressure cutout that protects against excessive
high discharge pressure regardless of whether or not the
optional discharge pressure is installed.
S U C T I O N
C U T O U T
=
The SUCTION PRESSURE CUTOUT protects the
chiller from an evaporator freeze-up. If the suction
pressure drops below the cutout point, the system will
shut down. Typically, the cutout should be set to 80 PSIG
(5.52 Bars) from water cooling.
There are some exceptions when the
suction pressure is permitted to tem-
porarily drop below the cutout point.
Details are explained under the topic
of SYSTEM SAFETIES.
JOHNSON CONTROLS
P R E S S U R E
5 7 0
P S I G
P R E S S U R E
80 . 0
P S I G
L O W
A M B I E N T
C U T O U T
The LOW AMBIENT TEMP CUTOUT allows the user
to select the chiller outside ambient temperature cutout
point. If the ambient falls below this point, the chiller
will shut down. Restart can occur when temperature rises
2 °F (1.11 °C) above the cutout setpoint.
L E A V I N G
L I Q U I D
C U T O U T
=
The LEAVING LIQUID TEMP CUTOUT protects
the chiller from an evaporator freeze-up. Anytime the
leaving chilled liquid temperature drops to the cutout
point, the chiller shuts down. Restart will be permitted
when the leaving chilled liquid temperature rises 2 °F
(1.11 °C) above the cutout setpoint.
When water cooling mode is programmed (OPTIONS
key), the value is fixed at 36.0 °F (2.22 °C) and cannot
be changed. Glycol cooling mode can be programmed
to values listed in Table 11.
A N T I
R E C Y C L E
=
6 0 0
The programmable anti-recycle timer assures that
systems do not short cycle, and the compressor motors
have sufficient time to dissipate heat after a start.
This timer is programmable under the PROGRAM
key between 300 – 600 seconds. Whenever possible,
to reduce cycling and motor heating, the anti-recycle
timer should be adjusted as high as possible. The
programmable anti-recycle timer starts when the first
compressor in a system starts. The timer begins to count
down. If all the compressors in the circuit cycle off,
a compressor within the circuit will not be permitted
to start until the anti-recycle timer has timed out. If
the lead system has run for less than 5 minutes, three
times in a row, the anti-recycle timer will be extended
to 10 minutes, if currently programmed for les than 10
minutes.
F A N
C O N T R O L
P R E S S U R E
The Fan Control On-Pressure is the programmed
pressure value that is used to stage the condenser fans
on, in relation to discharge pressure. Refer to Condenser
Fan Control in the "Unit Operation" section of this IOM
and Tables 19, 20, 21 and 22.
SECTION 7 – UNIT CONTROLS
T E M P
=
2 5 . 0 ° F
T E M P
3 6 . 0 ° F
T I M E R
S E C
O N
=
X X X
P S I G
157
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents