SECTION 7 – UNIT CONTROLS
S Y S
X
S P
D P
These displays show suction and discharge pressures
for each system. The discharge pressure transducer is
optional on some models.
If the optional discharge transducer is not installed, the
discharge pressure would display 0 PSIG (0 barg).
The minimum limits for the display are:
Suction Pressure: 0 PSIG (0 barg)
Discharge Pressure: 0 PSIG (0 barg)
The maximum limits for the display are:
Suction Pressure: 400 PSIG (27.58 barg)
Discharge Pressure: 650 PSIG (44.82 barg)
S Y S
X
H O U R S
2 = X X X X X,
S Y S
X
S T A R T S
2 = X X X X X,
The above two messages will appear sequentially for
each system. The first display shows accumulated
running hours of each compressor for the specific
system. The second message shows the number of starts
for each compressor on each system.
Run times and starts will only be dis-
played for the actual number of sys-
tems and compressors on the unit.
A total of 99,999 hours and starts can be logged before
the counter rolls over to "0".
L O A D
T I M E R
U N L O A D
T I M E R
This display of the load and unload timers indicate
the time in seconds until the unit can load or unload.
Whether the systems loads or unloads is determined by
how far the actual liquid temperature is from setpoint.
A detailed description of unit loading and unloading is
covered under the Capacity Control topic.
146
=
7 2 . 1
P S I G
= 2 2 7 . 0
P S I G
1 = X X X X X
3 = X X X X X
1 = X X X X X
3 = X X X X X
5 8
S E C
0
S E C
C O O L I N G
2
O F
The display COOLING DEMAND indicates the current
"step" in the capacity control scheme when in Return
Water Control Mode. The number of available steps
are determined by how many compressors are in the
unit. In the above display, the "2" does not mean that
two compressor are running but only indicates that the
capacity control scheme is on step 2 of 8. Capacity
Control is covered in more detail in this publication
which provides specific information on compressor
staging (for Return Water Control only).
T E M P
E R R O R
T E M P
R A T E
The COOLING DEMAND message will be replaced
with this message when Leaving Chilled liquid control
is selected. This message indicates the temperature
error and the rate of change of the chilled liquid
temperature.
L E A D
S Y S T E M
S Y S T E M
This display indicates the current LEAD system. In this
example system 2 is the LEAD system, making system
1 the LAG system. The LEAD system can be manually
selected or automatic. Refer to the programming under
the "OPTIONS" key. The Lead System display will only
appear on a two system unit.
A unit utilizing hot gas bypass should
be programmed for MANUAL with
system 1 as the lead system. Failure
to do so will prevent hot gas operation
if system 2 switches to the lead system
when programmed for AUTOMATIC
LEAD/LAG.
FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
D E M A N D
8
S T E P S
X X X . X ° F
X X X . X ° F / M
I S
N U M B E R
2